![CARLO GAVAZZI RVDFA110020 Advanced User'S Manual Download Page 21](http://html.mh-extra.com/html/carlo-gavazzi/rvdfa110020/rvdfa110020_advanced-users-manual_2558649021.webp)
20
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 23/03/2011
3.8.1 RVDF Size A Installation
S
WITCH
POWER
Potentiometer
REV-0-FWD
S
WITCH
L1 L2
RUN
S
TOP
T1 T2 T3
ENT
D
S
P
FUN
DATA
RE
S
ET
100
~
120V
or
200-240V
50/60 Hz
S
ingle Pha
s
e
s
123.40 mm
4xM4
198.90 mm
3 Pha
s
e
s
IM
NOTE :
1. Power supply cable : #14 AGE (2.0m
2
)
2. Motor cable : #16 AGE (1.25m
2
)
3. Torque value of Screw :
(1). Power/Motor cable (plug in) Therminal:
5kg-cm(4.34 in-lb)
(2). Remote control wire: 4kg-cm(3.47in-lb)
(3). Outer Cover (M4): 6kg-cm(5.20in-lb)
3
PHA
S
E
IM
10V
VI
0V
FW
RE
12V
L1
L2
T1
T2
T3
POWER
S
WITCH
REV -0-FWD
S
WITCH
Potentiometer
AC
100
~
120
or
200
~
240
50/60HZ
NOTE:
(1). Input source: single-phase (L1,L2, )
ensuring that it is connected to a
100~120 or 200~240 supply.
(2). Output Motor: three-phase ( ,T1,T2,T3).
Caution:
•
Do not start or stop the inverter using the
main circuit power.
•
Please always remain REV-0-FWD switch
at 0 position. In order to keep inverter has
no running signal before power-on again
after power supply interrupted.
Otherwise, injury may result.
3.8.2 RVDF Size A Circuit Diagram
3.8.3 RVDF Siza A Connections
4 x Outer cover
s
crew
Plug-in terminal
s
Power
s
upply
cable
Motor cable
,T1,T2,T3
Motor cable
Power
s
upply
cable
L1,L2,
3.8.4 RVDF Size A EMC Mounting
Power
s
upply
cable
L1,L2,
Cutting Length
of cable
s
hield
200mm
Cable
s
hielding
connected to
ground clamp
Note:
TM2 Remote control
cable
s
hould be connect
to ground
s
crew
Length: Max 2M
,T1,T2,T3
Motor cable
3.8 RVDF - IP65 Type
RVDF Advanced User Manual