Motor Controllers AC Variable Frequency Drives
RVBS
Specifications are subjected to change without notice.10/08/2021
43
Function
code
Mod.
add.
Description
Def
Min
Max
U.M.
R/W
D02
0x0502
Alarm Code
-
-
-
-
R
D12
0x050C
Latest Alarm Contents
-
-
-
-
R
D13
0x050D
Last Alarm Contents
-
-
-
-
R
D14
0x050E
Second Last Alarm Contents
-
-
-
-
R
D15
0x050F
Third Last Alarm Contents
-
-
-
-
R
5.2
Alarm operation
H30 causes the inverter to generate a mock alarm in order to check whether external sequences function
correctly at the time of machine setup.
Setting the H30 data to "1" displays mock alarm err on the LED monitor. It also issues alarm output ALM (if
assigned to a digital output terminal specified by E06 or E07). (Accessing the H30 data requires simultaneous
keying of "
key +
key.") After that, the H30 data automatically reverts to "0," allowing you to reset the
alarm.
Just as for data (alarm history and relevant information) of those alarms that could occur in running the
inverter, the inverter saves mock alarm data, enabling you to confirm the mock alarm status.
To clear the mock alarm data, use H19. (Accessing the H19 data requires simultaneous keying of "
key +
key.") H19 data automatically reverts to "0" after clearing the alarm data.
Function
code
Mod.
add.
Description
Def
Min
Max
U.M.
R/W
H19
0x0314
Clear Alarm Data
0
0
1
-
R/W
H30
0x031E
Mock Alarm
0
0
1
-
R/W