Motor Controllers AC Variable Frequency Drives
RVBS
Specifications are subjected to change without notice.10/08/2021
12
F02
0x0002
Operation Method
1: Terminal command
FWD or REV
2: RUN/STOP keys on
keypad (forward)
3: RUN/STOP keys on
keypad (reverse)
1
O
R/W
Y
-
F03
0x0003
Maximum Frequency 1
25.0 to 120.0
900
O
R/W
Y
0.1Hz
F04
0x0004
Base Frequency 1
25.0 to 120.0
500
O
R/W
Y
0.1Hz
F05
0x0005
Rated Voltage at Base
Frequency 1
0: Output a voltage in
proportion to input
voltage
80 to 240: Output an
AVR-controlled voltage
0
O
R/W
Y
Vrms
F06
0x0006
Maximum Output
Voltage 1
80 to 240: Output an
AVR-controlled voltage
230
O
R/W
Y
Vrms
F07
0x0007
Acceleration Time 1
0.01 to 655
500
O
R/W
N
0.01S
ec.
F08
0x0008
Deceleration Time 1
0.01 to 655
500
O
R/W
N
0.01S
ec.
F09
0x0009
Motor ETH
Characteristic
1: For a general-
purpose motor with
shaft-driven cooling
fan
2: For an inverter-
driven motor with
separately powered
cooling fan
1
O
R/W
N
-
F10
0x000A
Motor ETH Level
0.00: Disable, 0.01 to
100.0
1 to 135% of the rated
current (allowable
continuous drive
current) of the motor
210/329
O
R/W
N
0.01A
rms
F11
0x000B
Motor ETH Thermal
Time Constant
0.5 to 75.0
50
O
R/W
N
0.1Mi
n.
F12
0x000C
Restart Mode after
Momentary Power
Failure (Mode selection)
0: Disable restart (Trip
immediately)
1: Disable restart (Trip
after a recovery from
power failure)
2: Trip after
decelerate-to-stop
4: Enable restart
(Restart at the
frequency at which the
power failure occurred,
for general loads)
5: Enable restart
(Restart at the starting
frequency)
1
O
R/W
N
-
F13
0x000D
Frequency Limiter (High)
0.0 to 120.0
1000
O
R/W
N
0.1Hz
F14
0x000E
Frequency Limiter (Low)
0.0 to 120.0
0
O
R/W
N
0.1Hz
F15
0x000F
DC Braking1 (Start
Frequency)
0.0 to 60.0
0
O
R/W
N
0.1Hz
F16
0x0010
DC Braking1 (Level)
0 to 100 *2)
0
O
R/W
N
%
F17
0x0011
DC Braking1 (Time)
0.00 (Disable),
0.01 to 30.00
0
O
R/W
N
0.01S
ec.
F18
0x0012
Starting Frequency1
0.1 to 60.0
10
O
R/W
N
0.1Hz
F19
0x0013
Starting Frequency1
(Holding time)
0.00 to 10.00
0
O
R/W
N
0.01S
ec.
F20
0x0014
Stop Frequency
0.1 to 60.0
2
O
R/W
N
0.1Hz
F21
0x0015
Motor Sound (Carrier
frequency)
2 to 10
4
O
R/W
N
kHz
F23
0x0017
Stop Frequency (Holding
time)
0.00 to 10.00
0
O
R/W
N
0.01S
ec.
F24
0x0018
Control Mode Selection
1
0: V/f control with slip
compensation inactive
1: Dynamic torque
vector control
2: V/f control with slip
compensation active
1
O
R/W
Y
-
F25
0x0019
Current Limiter (Mode
selection)
0: Disable (No current
limiter works.)
1: Enable at constant
2
O
R/W
N
-