Motor Controllers AC Variable Frequency Drives
RVBS
Specifications are subjected to change without notice.10/08/2021
13
speed (Disable during
ACC/DEC)
2: Enable during
ACC/constant speed
operation
F26
0x001A
Current Limiter (Level)
20 to 200 (The data is
interpreted as the
rated output current of
the inverter for 100%.)
*2)
180
O
R/W
N
%
F28
0x001C
Electronic Thermal
Overload Protection for
DBR (Usage
Rate, %ED)
0.1 to 50.0
100
O
R/W
N
0.10
%
F29
0X001D
Digital Reference
Frequency
0.00 to 120.00
0
O
R/W
N
0.01H
z
F30
0x001E
Torque Boost 1
0.0 ~ 20.0 (The
percentage is relative
to the F05 "Rated
Voltage at Base
Frequency 1")
50/35
O
R/W
N
0.10
%
F31
0x001F
Dynamic Braking
Operation Selection
0: OFF;
1: ON (Dynamic
braking function is
active in RUN state);
2: ON (Dynamic
braking function is
active In both RUN
and IDLE state)
2
O
R/W
N
-
F32
0x0020
Torque Boost 1 Mode
Select
0: Variable torque load
1: Constant torque
load
2: Auto-torque boost
1
O
R/W
Y
-
*2) The percentage is relative to the rated output current.
External I/O setting (E group)
E01
0x0101
Terminal [DI1] Function
1
Selecting function
1
code data assigns the
corresponding function
to terminals [DI1], [DI2]
as listed in the manual.
[FWD] and {REV]
function cannot
support logic-inverted
assignment (i.e. 1098,
1099)
98
O
R/W
Y
-
E02
0x0102
Terminal [DI2] Function
1
97
O
R/W
Y
-
E07
0x0107
Terminal [30A/B/C]
Function
Selecting function
code data assigns the
corresponding function
to terminals [Y1] and
[30A/B/C] as listed in
the manual.
99
O
R/W
Y
-
E10
0x010A
Frequency Arrival
(Hysteresis width)
0.0 to 10.0
25
O
R/W
N
0.1Hz
E11
0x010B
Frequency Detection
(Level)
0.0 to 120.0
600
O
R/W
N
0.1Hz
E12
0x010C
Frequency Detection
(Hysteresis width)
0.0 to 120.0
10
O
R/W
N
0.1Hz
E13
0x010D
Coefficient for Speed
Indication
0.01 to 200.0
3000
O
R/W
N
-
E14
0x010E
External Braking Signal
(OFF current)
0 to 200
100
O
R/W
N
%
E15
0x010F
External Braking Signal
(OFF frequency)
0.0 to 25.0
10
O
R/W
N
0.1Hz
E16
0x0110
External Braking Signal
(OFF timer)
0.0 to 5.0
10
O
R/W
N
0.1Se
c.
E17
0x0111
External Braking Signal
(ON frequency)
0.0 to 25.0
10
O
R/W
N
0.1Hz
E18
0x0112
External Braking Signal
(ON timer)
0.0 to 5.0
10
O
R/W
N
0.1Se
c.
Control functions (C group)
C10
0x60A
Analog Input
Voltage Offset
-10.0 to 10.0
0
O
R/W
N
0.1%
C11
0x60B
Analog Input
0.0 to 200.0
1000
O
R/W
N
0.1%