18
NRG User Manual | © 2020 | CARLO GAVAZZI LTD.
V1.3 | NRG PROFINET User Manual | © 2020 | CARLO GAVAZZI LTD.
EN
5.3
Diagnostic Data
Alarms from the NRG bus chain are passed as an event driven acyclic command via the PROFINET Diagnostic System.
Alarms are generated from both the NRG controller as well as each NRG solid state relay on the bus chain. The
diagnostic type used for al alarm is the channel diagnosis (USI = 0x8000). Alarms are identified using the slot / subslot
configuration of the NRG bus chain.
NRGC-PN Alarms
Alarm
Severity
Alarm Number
Internal Error
Fault
0x4000
Bus Error
Fault
0x0013
Device Limit Error
Fault
0x4001
Termination Error
Maintenance Demanded
0x4002
Device Conflict Error
Fault
0x4003
Device Unconfigured Error
Fault
0x4004
Device Position Error
Maintenance Required
0x4005
Power Supply out of range
Fault
0x0011
RG..N Alarms
Alarm
Severity
Alarm Number
Mains loss
Fault
0x4020
Load loss / SSR open circuit
Fault
0x4021
Short Circuit
Fault
0x0001
Voltage out of range
Maintenance Demanded
0x4022
Current out of range
Maintenance Demanded
0x4023
Frequency out of range
Maintenance Demanded
0x4024
Over Temperature Prewarning
Maintenance Required
0x4025
Temperature out of range
Fault
0x0005
Load Deviation flag
Maintenance Demanded
0x4026
Internal Error
Fault
0x4027
Device Position Error
Maintenance Required
0x4028
PROFINET Pull / Plug Alarms
In PROFINET, Pull and Plug Alarms occur when modular devices are disconnected (pulled)/ connected (plugged).
Whenever a plug event occurs, the module in question is reparametrized automatically by PLC. These are standard
PROFINET alarms that do not fall under the channel diagnostics.
In the case of the NRG a Pull alarm shall indicate that an RG..N has stopped responding on the chain. When the device
recovers from a Pull either by reconnection or a recovery from a crash, the Plug alarm shall be triggered.
Note
: It is not possible to plug new RG..Ns during runtime.