Acyclic data for NRGC-PN
Index
Description
Size
Valid Values
1
Auto-addressing
Command/Status
2 bytes
Writing:
1 -> Trigger an auto-addressing of the NRG bus chain on
the next NRGC-PN powerup.
Acyclic data for RG..Ns
Index
Description
Size
Parameters
1
Monitoring
Parameters
2 bytes
Hold current period
2
Alarm Parameters
16 bytes
Alarm Setting
Over voltage limit
Under voltage limit
Over current limit
Under current limit
Over frequency limit
Under frequency limit
Over temperature pre-warning
3
Control Parameters
8 bytes
Output substitute mode
Output substitute value
Firing mode
Time base (for Burst firing mode)
4
RG..N Commands
2 bytes
RG..N command
5
TEACH Parameters
6 bytes
TEACH voltage reference
TEACH current reference
TEACH % load deviation
6
Load Running Hours
2 bytes
Load Running hours
7
SSR History
(read only)
6 bytes
Energy Reading (low)
Energy Reading (high)
SSR ON time
A description of each parameter with an indication of the possible values is listed in the table below
Parameters
Description
Values
Hold current period
Set the no. of cycles over which the
Hold Current Reading is calculated
1
–
32
18 (default)
Alarm Setting
Set the alarm recovery mode
0
→
Automatic (default)
1
→
Manual
Over voltage limit
Set the over and under voltage limit if
desired which will trigger an alarm if
the voltage reading is beyond the
range
Under voltage limit
–
660V
Default (660V)
Under voltage limit
0
–
Over voltage limit
Default (0V)
Over current limit
Set the over and under current limit if
desired which will trigger an alarm if
the current reading is beyond the
range
Under current limit
–
default
value (RG..N dependent)
Under current limit
0
–
over current limit
Default (0A)