CARLO GAVAZZI NLG13D724 Series User Manual Download Page 13

ted, and the START circuit has

been activated, as described in

this user manual.

A

UXILIARY OUTPUT

An auxilary NC voltage free relay

output is available between the 41-

42 terminals. It must be used only

for signalling functions and not for

safety functions.

OPERATING MODE

With manual START configuration,

the safety outputs close, if the swit-

ches connected to S11 & S22 are

operated, when the NO START

pushbutton is pushed. With auto-

matic START configuration, the

safety outputs close as soon as

both the switches connected to

S11 & S22 are operated. The CH1

& ChH2 LED turn on.

Releasing even one input contact

(S11 and/or S22) forces immedia-

tely the safety outputs to an open

status. The LED relative to the

channel whose input has been

released turns off.

A new operating cycle is possible

only after releasing both input con-

tacts and then operating them

again (and pushing the START

button, if the safety module has

been set up with manual START

configuration).

For the “SC” and “DC” models it is

necessary a minimum delay of 500

ms from the operated status of the

input contacts to the pushing of the

START button. The same delay is

necessary between the START

button releasing and re-operating,

if the input terminals have been

previously operated with the

START button already pushed. 

In the models with monitored

manual START configuration, if the

NO START button gets welded, the

safety outputs cannot close their

contacts any more.

TEST & ACTIVATION

The following operations must be

repeated when the module is

installed and every time the wiring

is changed and at regular intervals

by carrying out in sequence all the

steps described below avoiding

any type of dangerous condition

for the operators. 

STEP 1

Check the integrity, the

correct installation, the correct

positioning on the machine and the

correct functioning of all the devi-

ces connected to the inputs and to

the outputs of the safety module.

Check also the correct wiring of all

the devices.

STEP 2

Power on the safety

module: the 

POWER

LED turns on

(this LED has to be considered ON

in all the steps of this sequence).

The 

CH1

and 

CH2

are off.

Operate the input contacts: the

safety outputs are open and the

CH1

&

CH2

are off (if the module is

configured for automatic START,

13

Summary of Contents for NLG13D724 Series

Page 1: ...Manuale Utente User Manual Manuale Utente User Manual MODULI DI SICUREZZA MODULI DI SICUREZZA SAFETY SAFETY MODULE MODULE NLG13D NLG13D...

Page 2: ...17 DATI TECNICI TECHNICAL DATA 20 INDICE T INDICE TABLE OF CONTENTS ABLE OF CONTENTS 2 INTRODUCTION 10 FUNCTION 10 INSTALLATION 10 Warning 10 Wiring 11 Terminals coding 11 Power supply 11 Input 11 ST...

Page 3: ...delle cen traline si intendono Azionati o attivati nel caso in cui l ESPE presenti raggi non interrotti riarmo attivato sia ali mentato e non vi siano guasti nel sistema In questa condizione le uscit...

Page 4: ...o ed al polo negativo della sorgente di alimentazione DC Il negativo di alimentazione dell ESPE DEVE coincidere con il negativo della ali mentazione del modulo vedi figu re con esempi INGRESSI Il modu...

Page 5: ...azioni in cat 2 preve dere un test interrompendo i raggi dell ESPE con la periodicit indivi duata nelle relative norme Il modulo abilitato a chiudere le uscite sicure solo se entrambi i ter minali S11...

Page 6: ...e del pulsante di START trascorra un tempo di almeno 500 ms Uguale intervallo deve tra scorrere tra l apertura del pulsan te di START e la sua richiusura nel caso di chiusura degli ingressi a START gi...

Page 7: ...e aperte e aperta con uscite sicure chiuse PRECAUZIONI DI UTILIZZO L ESPE deve essere installato in posizione tale da assicurare che l operatore non possa raggiun gere la zona pericolosa quando esisto...

Page 8: ...collegati Il modulo non prevede manuten zione interna E necessario perio dicamente ed a macchina e modu lo disalimentati pulire il modulo di sicurezza ed i relativi dispositivi di comando e di attuaz...

Page 9: ...etto comportamento del sistema deve essere verifica to da un dispositivo di pi alto livello ad esempio dalla macchi na in cui la coppia modulo barrie ra installata oppure da un dispositivo di controll...

Page 10: ...achinery Directives NOTE The input terminals of the module are intended to be operated when the light beams are not interrupted the ESPE and the module are correctly supplied and there are not fault c...

Page 11: ...als respectively to the positive and negative poles of the DC power supply source The negative sup ply terminal of the ESPE must be connected to the same negative pole of the DC power supply sour ce t...

Page 12: ...PE with one relay two wires output connect the output wires to the S11 and S22 terminals short circuit S11 with S22 lea ving S12 not connected fig 10 max Safety cat 2 For safety cat 2 applications a p...

Page 13: ...500 ms from the operated status of the input contacts to the pushing of the START button The same delay is necessary between the START button releasing and re operating if the input terminals have be...

Page 14: ...s verify that the auxiliary output is closed when the safety outputs are open and that the auxiliary output is open when the safety outputs are clo sed USAGE PRECAUTIONS The ESPE must be carefully ins...

Page 15: ...verify the integrity of the module external device system The safety module doesn t require internal maintenance it must be periodically cleaned with plant and module powered off together with all th...

Page 16: ...short circuit between its outputs in the event of short circuit betwe en the ESPE safety outputs the ESPE must switch off the safety outputs NOTE The ESPE NLG13D724 module system is part of the safe t...

Page 17: ...FIGURE E TABELLE FIGURES AND TABLES 17 Fig 1 Schema circuitale dei moduli NLG13D724 NLG13D724 circuit diagram Fig 2 Diagramma funzionale Functional diagram mod SC e and DC...

Page 18: ...uscite PNP a 1 filo Two 1 wire PNP outputs Fig 4 ESPE 2 uscite a rel a 1 filo Two 1 wire relay outputs Fig 5 ESPE 1 uscita PNP a 1 filo One 1 wire PNP output Fig 6 ESPE 1 uscita a rel a 1 filo One 1 w...

Page 19: ...cita a rel a 2 fili One 2 wires relay output Fig 9 ESPE 1 uscita PNP a 2 fili One 2 wires PNP output Fig 7 ESPE 2 uscite PNP a 2 fili Two 2 wires PNP outputs Fig 8 ESPE 2 uscite a rel a 2 fili Two 2 w...

Page 20: ...supply 24 Vdc 15 10 Assorbimento Current drain 70 mA 24Vdc a vuoto no load Potenza assorbita Power Drain max 5 VA Categoria sic Safety Category 4 EN954 1 and EN13849 1 Performance Level e EN13849 1 P...

Page 21: ...ts closed max 150 ms Contemporaneit alla chiusura tra gli ingressi input channel simul taneity during outputs closing infinita infinite Ritardo tra azionamento ingressi e attivazione START input opera...

Page 22: ...ili ai morsetti Cross Section and type of the cables to connect to the termi nals 0 05 3 mm2 AWG 30 12 Rigido e flessibile in rame 60 C o 75 C stranded or solid wire 60 or 75 C copper conductor Coppia...

Page 23: ...according to the norm EN ISO 13849 1 2008 The EMC Directive 2004 108 EC EN 61000 6 3 Generic Emission Standard Residential commercial and light industry EN 61000 6 2 Generic Immunity Standard Industr...

Page 24: ...CARLO GAVAZZI si riserva il diritto di apportare modifiche senza preavviso CARLO GAVAZZI reserves the right to make changes without prior notice 8021008 Mod NLG13DB24...

Reviews: