CARLO GAVAZZI NLG13D724 Series User Manual Download Page 11

conductors separately from the

power conductors.

- Avoid installation during storms.

- Do not dispose of the packaging

in the environment.

W

IRING

It is recommended to use conduc-

tors with section and length ade-

quate to the terminals, currents

and distances involved, ensuring

that the conductors are not exces-

sively tight, that their positioning

avoids potential cuts or squashing

and that they are not in the way of

people or things.

The models named “SA” and “SC”

are equipped with fixed screw ter-

minals for direct wiring on the

module.

The modules named with “DA” and

“DC” are equipped with plug-in ter-

minals, that allow the wiring on

female connectors far from the

module. 

Once wired-on, the female con-

nectors can be connected to the

male ones fixed on the module.

T

ERMINALS CODING

The plug-in terminals of the “DA”

and “DC” models are coded so that

it is possible only one combination

to connect ALL the female connec-

tors on the corresponding male. 

P

OWER SUPPLY

Connect the A1 & A2 terminals

respectively to the positive and

negative poles of the DC power

supply source. The negative sup-

ply terminal of the ESPE must be

connected to the same negative

pole of the DC power supply sour-

ce to which is connected the A2

terminal of the safety module (see

examples in this manual).

I

NPUT

The module is designed to be dri-

ven (input terminals S11 and S22)

by two static PNP inputs: each

ESPE PNP output transistor has

the emitter internally connected to

the supply of the ESPE, so each

ESPE output has only one wire

coming from the collector. With this

configuration the system

light barrier can reach safety cate-

gory 4 according to EN 954-1 and

EN13849-1.

The light barrier can be also driven

by only one static PNP input (see

the examples in this manual): with

this device the system

light barrier can reach safety cate-

gory 2 according to EN 954-1 and

EN13849-1.

The safety module is enabled to

close the safety outputs only if both

input contacts are operated. 

The connection between the ESPE

and the safety module depends on

the ESPE outputs type as listed

below:

-

ESPE with two one-wire outputs

(PNP-type or relay-type)

: con-

nect one output to the S11 termi-

11

Summary of Contents for NLG13D724 Series

Page 1: ...Manuale Utente User Manual Manuale Utente User Manual MODULI DI SICUREZZA MODULI DI SICUREZZA SAFETY SAFETY MODULE MODULE NLG13D NLG13D...

Page 2: ...17 DATI TECNICI TECHNICAL DATA 20 INDICE T INDICE TABLE OF CONTENTS ABLE OF CONTENTS 2 INTRODUCTION 10 FUNCTION 10 INSTALLATION 10 Warning 10 Wiring 11 Terminals coding 11 Power supply 11 Input 11 ST...

Page 3: ...delle cen traline si intendono Azionati o attivati nel caso in cui l ESPE presenti raggi non interrotti riarmo attivato sia ali mentato e non vi siano guasti nel sistema In questa condizione le uscit...

Page 4: ...o ed al polo negativo della sorgente di alimentazione DC Il negativo di alimentazione dell ESPE DEVE coincidere con il negativo della ali mentazione del modulo vedi figu re con esempi INGRESSI Il modu...

Page 5: ...azioni in cat 2 preve dere un test interrompendo i raggi dell ESPE con la periodicit indivi duata nelle relative norme Il modulo abilitato a chiudere le uscite sicure solo se entrambi i ter minali S11...

Page 6: ...e del pulsante di START trascorra un tempo di almeno 500 ms Uguale intervallo deve tra scorrere tra l apertura del pulsan te di START e la sua richiusura nel caso di chiusura degli ingressi a START gi...

Page 7: ...e aperte e aperta con uscite sicure chiuse PRECAUZIONI DI UTILIZZO L ESPE deve essere installato in posizione tale da assicurare che l operatore non possa raggiun gere la zona pericolosa quando esisto...

Page 8: ...collegati Il modulo non prevede manuten zione interna E necessario perio dicamente ed a macchina e modu lo disalimentati pulire il modulo di sicurezza ed i relativi dispositivi di comando e di attuaz...

Page 9: ...etto comportamento del sistema deve essere verifica to da un dispositivo di pi alto livello ad esempio dalla macchi na in cui la coppia modulo barrie ra installata oppure da un dispositivo di controll...

Page 10: ...achinery Directives NOTE The input terminals of the module are intended to be operated when the light beams are not interrupted the ESPE and the module are correctly supplied and there are not fault c...

Page 11: ...als respectively to the positive and negative poles of the DC power supply source The negative sup ply terminal of the ESPE must be connected to the same negative pole of the DC power supply sour ce t...

Page 12: ...PE with one relay two wires output connect the output wires to the S11 and S22 terminals short circuit S11 with S22 lea ving S12 not connected fig 10 max Safety cat 2 For safety cat 2 applications a p...

Page 13: ...500 ms from the operated status of the input contacts to the pushing of the START button The same delay is necessary between the START button releasing and re operating if the input terminals have be...

Page 14: ...s verify that the auxiliary output is closed when the safety outputs are open and that the auxiliary output is open when the safety outputs are clo sed USAGE PRECAUTIONS The ESPE must be carefully ins...

Page 15: ...verify the integrity of the module external device system The safety module doesn t require internal maintenance it must be periodically cleaned with plant and module powered off together with all th...

Page 16: ...short circuit between its outputs in the event of short circuit betwe en the ESPE safety outputs the ESPE must switch off the safety outputs NOTE The ESPE NLG13D724 module system is part of the safe t...

Page 17: ...FIGURE E TABELLE FIGURES AND TABLES 17 Fig 1 Schema circuitale dei moduli NLG13D724 NLG13D724 circuit diagram Fig 2 Diagramma funzionale Functional diagram mod SC e and DC...

Page 18: ...uscite PNP a 1 filo Two 1 wire PNP outputs Fig 4 ESPE 2 uscite a rel a 1 filo Two 1 wire relay outputs Fig 5 ESPE 1 uscita PNP a 1 filo One 1 wire PNP output Fig 6 ESPE 1 uscita a rel a 1 filo One 1 w...

Page 19: ...cita a rel a 2 fili One 2 wires relay output Fig 9 ESPE 1 uscita PNP a 2 fili One 2 wires PNP output Fig 7 ESPE 2 uscite PNP a 2 fili Two 2 wires PNP outputs Fig 8 ESPE 2 uscite a rel a 2 fili Two 2 w...

Page 20: ...supply 24 Vdc 15 10 Assorbimento Current drain 70 mA 24Vdc a vuoto no load Potenza assorbita Power Drain max 5 VA Categoria sic Safety Category 4 EN954 1 and EN13849 1 Performance Level e EN13849 1 P...

Page 21: ...ts closed max 150 ms Contemporaneit alla chiusura tra gli ingressi input channel simul taneity during outputs closing infinita infinite Ritardo tra azionamento ingressi e attivazione START input opera...

Page 22: ...ili ai morsetti Cross Section and type of the cables to connect to the termi nals 0 05 3 mm2 AWG 30 12 Rigido e flessibile in rame 60 C o 75 C stranded or solid wire 60 or 75 C copper conductor Coppia...

Page 23: ...according to the norm EN ISO 13849 1 2008 The EMC Directive 2004 108 EC EN 61000 6 3 Generic Emission Standard Residential commercial and light industry EN 61000 6 2 Generic Immunity Standard Industr...

Page 24: ...CARLO GAVAZZI si riserva il diritto di apportare modifiche senza preavviso CARLO GAVAZZI reserves the right to make changes without prior notice 8021008 Mod NLG13DB24...

Reviews: