CARLO GAVAZZI NLG13D724 Series User Manual Download Page 12

12

nal and the other to the S22 ter-

minal, leaving S12 and S21 ter-

minals not connected (fig. 3, 4

max. Safety cat. 4).

-

ESPE with one one-wire output

(PNP-type or relay-type)

: con-

nect the output to the S11 termi-

nal; short-circuit the terminals

S11 with S22, leaving S12 and

S21 not connected (fig. 5, 6,

max safety cat. 2).

-

ESPE with two PNP two-wires

outputs (e.g. optocoupled PNP-

type)

: connect both emitter out-

puts to the S21 terminal and the

collector outputs to the S11 and

S22 terminal, leaving S12  not

connected (fig. 7, max. Safety

cat. 4).

-

ESPE with two relay two-wires

outputs

: connect one wire of

each output channel to the S21

terminal and the other outputs to

the S11 and S22 terminal, lea-

ving S12 not connected (fig. 8,

max. Safety cat. 4).

-

ESPE with one PNP two-wires

output (e.g. optocoupled PNP-

type)

: connect the emitter output

to the S21 terminal and the col-

lector output to the S11 terminal;

short-circuit S11 with S22, lea-

ving S12 not connected (fig. 9

max. Safety cat. 2).

-

ESPE with one relay two-wires

output:

connect the output wires

to the S11 and S22 terminals;

short-circuit S11 with S22, lea-

ving S12 not connected (fig. 10

max. Safety cat. 2).

For safety cat. 2 applications, a

periodic test (interrupting the

ESPE light beam) must be carried

out. The test periodicity is defined

in the relevant standards.

The safety relay is enabled to

close the safety outputs only if both

input switches are operated.

START C

IRCUIT

The safety modules “SA” and “DA”

are set up with not-controlled auto-

matic/manual START. The module

can be employed connecting bet-

ween the S33-S34 terminals either

a NO START pushbutton (for not

monitored manual START) or a

short-circuit (for automatic

START).

The safety modules “SC” and “DC”

are set up with monitored manual

START. The module can be emplo-

yed only connecting between the

S33-S34 terminals a NO START

pushbutton (monitored also for

welding fault). These models can-

not be configured for automatic

START.

S

AFETY

O

UTPUTS

Three NO voltage free safety out-

puts are available between the 13-

14, 23-24 and 33-34 terminals:

their contacts are closed when the

safety module is correctly powe-

red, the input switches are opera-

Summary of Contents for NLG13D724 Series

Page 1: ...Manuale Utente User Manual Manuale Utente User Manual MODULI DI SICUREZZA MODULI DI SICUREZZA SAFETY SAFETY MODULE MODULE NLG13D NLG13D...

Page 2: ...17 DATI TECNICI TECHNICAL DATA 20 INDICE T INDICE TABLE OF CONTENTS ABLE OF CONTENTS 2 INTRODUCTION 10 FUNCTION 10 INSTALLATION 10 Warning 10 Wiring 11 Terminals coding 11 Power supply 11 Input 11 ST...

Page 3: ...delle cen traline si intendono Azionati o attivati nel caso in cui l ESPE presenti raggi non interrotti riarmo attivato sia ali mentato e non vi siano guasti nel sistema In questa condizione le uscit...

Page 4: ...o ed al polo negativo della sorgente di alimentazione DC Il negativo di alimentazione dell ESPE DEVE coincidere con il negativo della ali mentazione del modulo vedi figu re con esempi INGRESSI Il modu...

Page 5: ...azioni in cat 2 preve dere un test interrompendo i raggi dell ESPE con la periodicit indivi duata nelle relative norme Il modulo abilitato a chiudere le uscite sicure solo se entrambi i ter minali S11...

Page 6: ...e del pulsante di START trascorra un tempo di almeno 500 ms Uguale intervallo deve tra scorrere tra l apertura del pulsan te di START e la sua richiusura nel caso di chiusura degli ingressi a START gi...

Page 7: ...e aperte e aperta con uscite sicure chiuse PRECAUZIONI DI UTILIZZO L ESPE deve essere installato in posizione tale da assicurare che l operatore non possa raggiun gere la zona pericolosa quando esisto...

Page 8: ...collegati Il modulo non prevede manuten zione interna E necessario perio dicamente ed a macchina e modu lo disalimentati pulire il modulo di sicurezza ed i relativi dispositivi di comando e di attuaz...

Page 9: ...etto comportamento del sistema deve essere verifica to da un dispositivo di pi alto livello ad esempio dalla macchi na in cui la coppia modulo barrie ra installata oppure da un dispositivo di controll...

Page 10: ...achinery Directives NOTE The input terminals of the module are intended to be operated when the light beams are not interrupted the ESPE and the module are correctly supplied and there are not fault c...

Page 11: ...als respectively to the positive and negative poles of the DC power supply source The negative sup ply terminal of the ESPE must be connected to the same negative pole of the DC power supply sour ce t...

Page 12: ...PE with one relay two wires output connect the output wires to the S11 and S22 terminals short circuit S11 with S22 lea ving S12 not connected fig 10 max Safety cat 2 For safety cat 2 applications a p...

Page 13: ...500 ms from the operated status of the input contacts to the pushing of the START button The same delay is necessary between the START button releasing and re operating if the input terminals have be...

Page 14: ...s verify that the auxiliary output is closed when the safety outputs are open and that the auxiliary output is open when the safety outputs are clo sed USAGE PRECAUTIONS The ESPE must be carefully ins...

Page 15: ...verify the integrity of the module external device system The safety module doesn t require internal maintenance it must be periodically cleaned with plant and module powered off together with all th...

Page 16: ...short circuit between its outputs in the event of short circuit betwe en the ESPE safety outputs the ESPE must switch off the safety outputs NOTE The ESPE NLG13D724 module system is part of the safe t...

Page 17: ...FIGURE E TABELLE FIGURES AND TABLES 17 Fig 1 Schema circuitale dei moduli NLG13D724 NLG13D724 circuit diagram Fig 2 Diagramma funzionale Functional diagram mod SC e and DC...

Page 18: ...uscite PNP a 1 filo Two 1 wire PNP outputs Fig 4 ESPE 2 uscite a rel a 1 filo Two 1 wire relay outputs Fig 5 ESPE 1 uscita PNP a 1 filo One 1 wire PNP output Fig 6 ESPE 1 uscita a rel a 1 filo One 1 w...

Page 19: ...cita a rel a 2 fili One 2 wires relay output Fig 9 ESPE 1 uscita PNP a 2 fili One 2 wires PNP output Fig 7 ESPE 2 uscite PNP a 2 fili Two 2 wires PNP outputs Fig 8 ESPE 2 uscite a rel a 2 fili Two 2 w...

Page 20: ...supply 24 Vdc 15 10 Assorbimento Current drain 70 mA 24Vdc a vuoto no load Potenza assorbita Power Drain max 5 VA Categoria sic Safety Category 4 EN954 1 and EN13849 1 Performance Level e EN13849 1 P...

Page 21: ...ts closed max 150 ms Contemporaneit alla chiusura tra gli ingressi input channel simul taneity during outputs closing infinita infinite Ritardo tra azionamento ingressi e attivazione START input opera...

Page 22: ...ili ai morsetti Cross Section and type of the cables to connect to the termi nals 0 05 3 mm2 AWG 30 12 Rigido e flessibile in rame 60 C o 75 C stranded or solid wire 60 or 75 C copper conductor Coppia...

Page 23: ...according to the norm EN ISO 13849 1 2008 The EMC Directive 2004 108 EC EN 61000 6 3 Generic Emission Standard Residential commercial and light industry EN 61000 6 2 Generic Immunity Standard Industr...

Page 24: ...CARLO GAVAZZI si riserva il diritto di apportare modifiche senza preavviso CARLO GAVAZZI reserves the right to make changes without prior notice 8021008 Mod NLG13DB24...

Reviews: