
NOTE
Figure 11: µA Bar Graph Meter Display
Measuring “High Voltage On” Time
The 9060 High Voltage Controller records the amount of
time the high voltage is triggered on up to 99,999 hours.
This value is display on the kV and µA displays of the unit.
There are two registers that retain this information, one
that may be reset, the other that is permanently retained
in memory. The number of hours the unit’s high voltage
has been on may be displayed by depressing at the same
time the preset 1 and reset buttons (See Figure 12). The
display will show hours of use for 3 seconds. This is the
resettable register.
To reset this register, press the reset button while the hours
are displayed.
To view the non-resettable register, press the preset 2 and
reset buttons at the same time. This display will show the
hours for 3 seconds.
Figure 12: Display “High Voltage On” Time
Front Panel Lockout
This feature locks out any changes to the kV setting from
the front panel of the Controller.
1. Set the kV to the desired value using the front panel
buttons. This must be set prior to installing the jumper.
2. Turn AC power off and access the interior of the
Controller.
3. Place the jumper across the two (2) pins at location 16
on the main PC board (See Figure 14).
4. Close the Controller and turn AC power back on.
Pressing the front panel +, -, or setpoint buttons will
now have no affect on the kV setting.
Figure 13: Lockout Jumper Location
LOCKOUTS
There are lockouts that may be done at the PC board (see
Figure 13). These lockouts may be used individually or in
combination as required. If the jumpers are disconnected,
the original functions are re-enabled. After changing any
jumpers, the AC power must cycled for the new setting to
take affect.
Some lockouts are sealed using sealant to prevent
them from being modified for safety reasons. These
lockouts should
ONLY
be modified by Ransburg
Authorized Representatives.
PRESS AND HOLD
BOTH FOR RESETTABLE
ON TIME REGISTER
PRESS AND HOLD
BOTH FOR NON-RESETTABLE
ON TIME REGISTER
DISPLAY OF “HV ON” TIME IN HOURS
LOCKOUT JUMPER
LOCATIONS
CP-13-04.3 (10/2017)
19 / 29
www.carlisleft.com
OPERATION