background image

µRack 

Cod. CAREL +03P220431 rel. 2.2 dated  10/02/12

 

31

Parameter 

Type  Pos. Display Description 

UOM 

Range 

Default

Notes 

Fan inverter differential 

R/W  U 

r19  Fan inverter differential 

bar 

°C 

0 to 20.0 
0 to 20.0 

18  

Only if the inverter if 

enabled 

Fan rotation 

R/W C  r20 

Type of fan rotation. 
0) NO ROTATION 
1) FIFO 

 

0/1 

For single circuit only 

Fan control 

R/W C  r21 

Type of fan control: 
0) Proportional 
1) Propor integral 
2) Dead band 

 

0 to 2 

For single circuit only 

Integral time (P+I only) 

R/W  C 

r22  Integral time with P+I control  

0 to 999 

600 

Only if PI 

Time between fan start call 

R/W  C 

r23  Minimum time between two successive calls to start different fans 

0 to 999 

xx 

Time between fan stop call 

R/W  C 

r24  Minimum time between two successive calls to stop different fans 

0 to 999 

xx 

Min fan set point 

R/W  C 

r25  Set the lower limit of the fan set point 

bar 

°C 

0 to r26 

-50 to r26 

1.0 

-31.2 

 

Max fan set point 

R/W  C 

r26  Set the upper limit of the fan set point 

bar 

°C 

r25 to 40.0 

r25 to 150 

25.0 
55.3 

 

Fan inverter speedup time 

R/W  C 

r27  Fan inverter speedup time 

0 to 999 

Only if the inverter is 

enabled 

Inverter ramp up time 

R/W 

r28  Set the time taken by the inverter to reach full load 

0 to 999 

10 

Only if the inverter is 

enabled 

Minimum fan inverter output  R/W  C 

r29  Set the minimum operation of the fan inverter 

0 to r30 0 

Only if the inverter is 

enabled 

Maximum fan inverter output  R/W  C 

r30  Set the maximum operation of the fan inverter 

r29 to 100 

100 

Only if the inverter is 

enabled 

Triac impulse duration  

R/W  C 

r31  Duration of the impulse applied to the triac 

ms 

0 to 10  

Only if the inverter is 

enabled 

Enable floating condenser 
control 

R/W C  r32 

Enable the floating condenser control 
0) NO 
1) YES 

 

0 to 1  

 

Condensing Delta T  

R/W  C 

r33  Temperature difference for floating condenser control 

 

-40 to 150 

10 

 

Compressor management 
offset set point 

R/W I  r34 

Compressor bar auxiliary set point offset.  
Used when changing the set point from digital input 

 

-99.9 to 99.9 

 

Alarm menu 

 

 

 

 

 

 

 

 

HP suction 1 alarm 

R/W 

A01  Suction probe 1 alarm: high threshold setting 

bar 

A03 to /19  

9.3 

 

HP suction 1 delay 

R/W 

A02  Suction probe 1 alarm: delay setting 

0 to 999 

60 

 

LP suction 1 alarm 

R/W 

A03  Suction probe 1 alarm: low threshold setting 

bar 

/17 to A01 0 

 

LP suction 1 delay 

R/W 

A04  Suction probe alarm: delay setting 

0 to 999 

60 

 

HP suction 2 alarm 

R/W 

A05  Suction probe 2 alarm: high threshold setting 

bar 

A07… /20 

20 

For two circuits only 

HP suction 2 delay 

R/W 

A06  Suction probe 2 alarm: delay setting 

0 to 999 

60 

 

LP suction 2 alarm 

R/W 

A07  Suction probe 2 alarm: low threshold setting 

bar 

/18 to A05 

For two circuits only 

LP suction 2 delay 

R/W 

A08  Suction probe alarm: delay setting 

0 to 999 

60 

 

HP discharge alarm 

R/W 

A09  Discharge probe alarm: high threshold setting 

bar 

°C 

A10 to /20  
A10 to 150 

20.0   
45.8 

 

LP discharge alarm 

R/W 

A10  Discharge probe alarm: low threshold setting 

bar

°C 

/18 to A09     

-50 to A09 

-50 

 

Discharge delay 

R/W 

A11  Discharge probe alarm: delay setting 

0 to 999 

60 

 

Compressor thermal delay 

R/W 

A12  Compressor thermal overload alarm: delay setting 

0 to 999 

 

HP prevention 
Prevent time 1 

R/W 

A13  Time in which start calls are ignored after prevent HP 

0 to 99 

Only if the prevent is 

enabled 

HP prevention 
Prevent time 2 

R/W I  A14 

If two prevent alarms occur within this time, an excessive prevent frequency 
alarm is generated 

0 to 999 

Only if the prevent is 

enabled 

HP prevention 
Prevent time 3 

R/W I  A15 

If no prevent alarms occur in this period, the high prevent frequency alarm is 
automatically reset 

0 to 99 

30 

Only if the prevent is 

enabled 

High temp. probe threshold: 
B2 

R/W 

A16  High temperature threshold, probe B2  

°C 

-40 to 150 

100 

 

High temp. probe threshold: 
B3 

R/W 

A17  High temperature threshold, probe B3  

°C 

-40 to 150 

100 

 

Delay liquid level alarm 

R/W 

A18  Set the liquid level alarm delay from multifunction input 

0 to 500 

60 

 

Reset ALARMS 

R/W U  A19 

Reset the alarms with manual reset 
0) NO RESET 
1) RESET 

 0/1  0 

 

 

Alarm signal delay 

R/W 

A20  Set alarm signal delay 

0 to 999 

 

Exchange auto->man LP 3 
alarms 

R/W I  A21 

On the 3rd activation, within the set time, the low pressure alarm from 
pressure switch changes from automatic to manual reset. 

0 to 999 

10 

 

OFF due to probe 
disconnected 

R/W I  A22 

Enable unit OFF due to probe disconnected/alarm 
0) NO 
1) YES 

 0/1  0 

 

Maintenance menu 

 

 

 

 

 

 

 

 

All manuals and user guides at all-guides.com

all-guides.com

Summary of Contents for uRack

Page 1: ...Rack Standard compressor racks single two circuit User manual NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT All manuals and user guides at all guides com a l l g u i d e s c o m...

Page 2: ...All manuals and user guides at all guides com...

Page 3: ...nal circuits and mechanisms may be irreparably damaged Do not use corrosive chemicals solvents or aggressive detergents to clean the device Do not use the product for applications other than those spe...

Page 4: ...All manuals and user guides at all guides com...

Page 5: ...al device operation 22 6 2 Compressor hour counter and maintenance alarm 22 6 3 Set point variation from digital input 22 6 4 Type of refrigerant 22 6 5 Auxiliary probe management 22 6 6 Prevent high...

Page 6: ...RODUCED IN FW RELEASE 2 0 FOR MRK0000XX0 41 21 APPENDIX CHANGES INTRODUCED IN FW RELEASE 2 1 42 22 APPENDICE MODIFICHE INTRODOTTE NELLA RELEASE FW 2 2 42 All manuals and user guides at all guides com...

Page 7: ...etic compress ns max 4 ontrol ontrol of the value f parameter protec onfigure all the un onfigure the main modify the access l omes ready for pa d 10 02 12 isplay data in BAR with the same an racks wi...

Page 8: ...dis eric value of a para value is displayed 5 sec to set the pa f parameters is dis eric value of a para ther controlled va 5 sec to select the parameters is dis eric value of a par value is displaye...

Page 9: ...igh Temp Low Temp Probe not connected 1 On when the value read by the discharge probe is displayed 2 If flashing with the ALARM icon indicates the activation of discharge probe alarms High Temp Probe...

Page 10: ...forms a LA m relay it the number of ompressors fan ol and then the fa rding to the numb essors not capa pacity controlled s managed using he compressors an alarm inputs are ing parameter 14 e controll...

Page 11: ...igh low pressure switch fan thermal overload liquid level Unit On Off Voltage free contact Tab 3 b Digital outputs Input Description Type of device connected No1 C1 Compressor 1 fan Power contactor fo...

Page 12: ...0 02 12 12 DIN rail installation Fig 3 b Rack Line L N Rack ext temp probe amb temp probe alarm 4 alarm 2 alarm 1 alarm 3 multifunction D I alarm P Line L N P FCSER00000 FCSER00000 TRADR1W04 24 V All...

Page 13: ...ntia n ssor calls ensures pressors with alar abled is exclude n has been selecte et for the capaci ast to stop first ca rst to stop compressors so a e with the lowest l control is activate ed on vario...

Page 14: ...ssible 1 Pressure equal to point b same call time as the maximum compressor on time 2 Pressure between point b and point b DTNZ type of call between Max on time and Min on time 3 Pressure greater than...

Page 15: ...call a sequence with a higher capacity In the deactivation phase the opposite will occur while in the dead band no compressors will be started or stopped An increase in the requirement will correspond...

Page 16: ...ctive n one compressor n the proportiona stay on that is o oating condenser SET Condenser Liquid re nd MT circuits a pted for the contro pact and offering l re switches and s owing conditions TY it an...

Page 17: ...ty control and the following Minimum time between starts of the same compressor Sets the minimum time that must elapse between two starts of the same compressor This parameter limits the number of sta...

Page 18: ...d DF a n of a dead band sured value excee psed outside of th the measured valu n this case too th ccording to the st rameter r20 is ai ns with active ala excluded from re et ig 5 b e pressure switch h...

Page 19: ...ting Typical application cold rooms cold stores Parameter 13 default 0 independent control Inverter control Proportional band This control requires the inverter set point STPI to be set parameter r18...

Page 20: ...onal control Proportional Integral control T s SP RP T s 10 Volt Min In T s RP SP T s 10 Volt Min In Fig 5 e Key RP Pressure read SP Set point T Time Min In Minimum inverter output value Dead band con...

Page 21: ...triac to zero 3 Increase Max triac until the fan operates at a speed considered sufficient make sure that after having stopped it it starts rotating if left free 4 Copy this value to the Min triac pa...

Page 22: ...e m reds of hours as t to check the num he tens of hours to reset each indiv hown by an alarm from digita ncrease or decrea point when the m er R34 n the installation managed Refrigeran R134a R290 R60...

Page 23: ...t threshold any other compressor start calls are ignored for a set time called Prevent time 1 parameter A13 If between the start of two prevent cycles a time less than Prevent time 2 parameter A14 ela...

Page 24: ...that have mal status ted the initial situ gn of alarm ON u l reset meter 29 fan the are detected thes olved the red LED evices remain disa ted the initial situ f the signal device mal status arms is s...

Page 25: ...3 thermal overload DIN Fan 3 OFF Settable no A25 Fan 4 thermal overload DIN Fan 4 OFF Settable no A26 General fan thermal overload DIN Only signal alarm Preset electronically the fan stop during overl...

Page 26: ...dd erial line must be esponding manua ories rd protected sho otected 22 modifiable by sword 44 modifiab rs password 77 m s in the memory ion from the keyp rect PWD MANUFA ectly accessing th ng SEL acc...

Page 27: ...d 10 02 12 rs with the correspo RER meter n meter d below will be d t available The d Fig 10 a Display Descriptio 00 Set the typ 0 LT 1 MT 2 TWO CI Password S P and L P parameters L P visibility ondin...

Page 28: ...umber of compressors ON with suction probe 2 fault R W C 08 If the suction 2 probe fault or not connected alarm is activated this number of compressors are started These are in any case managed by the...

Page 29: ...layed only if the parameters are enabled 0 AUTO 1 MANUAL 0 1 1 Type of fan thermal overload alarm reset R W C 30 Type of thermal overload generic alarm reset relating to the individual fan Automatic w...

Page 30: ...U r02 Compressor differential first circuit bar C 0 to 20 0 0 5 Compressor set point circuit 2 R W U r03 Compressor set point second circuit bar C r14 tor15 1 0 For two circuits only Compressor differ...

Page 31: ...y R W I A02 Suction probe 1 alarm delay setting s 0 to 999 60 LP suction 1 alarm R W I A03 Suction probe 1 alarm low threshold setting bar 17 to A01 0 LP suction 1 delay R W I A04 Suction probe alarm...

Page 32: ...NO 1 YES M11 Enable ope 0 NO 1 YES M12 Enable ope 0 NO 1 YES M13 Manually o 0 NO 1 YES M14 Manually o 0 NO 1 YES M15 Manually o 0 NO 1 YES M16 Manually o 0 NO 1 YES M17 Manually o 0 NO 1 YES board cod...

Page 33: ...ote supe upervisor are show end from the Rac eceived and sent f B4 B1 B2 ambient air B3 outside air set point circuit 1 ntial circuit 1 set point circuit 2 ntial circuit 2 ction set point 1 ction set...

Page 34: ...pressure for dead band by time r11 R W 44 Condensing temperature delta for floating control r33 R W 45 High temp threshold probe B2 A16 R W 46 High temp threshold probe B3 A17 Tab 14 a Digital variab...

Page 35: ...4 Capacity of compressor 4 06 R 25 Inverter readout 11 R W 26 Multifunction DI configuration 15 R W 27 B1 type probe 16 Flow Index Description Alarm code R 1 Alarm compressor 1 A01 R 2 Alarm compresso...

Page 36: ...r speed up time r ramp up time um inverter output um inverter output mpulse duration uction pressure 1 a ction pressure 1 al uction pressure 2 a ction pressure 2 al scharge pressure a essor thermal o...

Page 37: ...en lectrical standard Closing current to g Maximum closing r 1 B2 B3 B4 CAR he response time 4 NTC temp pro Control signal for C Modulation of imp he configuration o oadless voltage 5 hort circuit cur...

Page 38: ...ard for pe erial board for per ming key with 12 mming key with 23 Rack RS485 DIN No panel No DIN No panel No DIN No panel No DIN No panel No d 10 02 12 2x74 24 Vac with g 24 Vac with con g RS485 prein...

Page 39: ...rs un 0431 rel 2 2 date ix Comp it with fan spe it 2 conden d 10 02 12 pressor r eed regulator ser fans rack cont 39 troller e Fig 17 a Fig 17 b C4 C3 C2 F2 F1 C2 examples 2 C1 2 C1 s of appli ication...

Page 40: ...el 2 2 dated 10 02 12 40 3 compressors unit with 2 fan steps and speed regulator no alarm relay output Fig 17 c 2 compressors unit 3 condenser fans Fig 17 d F1 C3 C2 C1 F2 F1 C2 C1 All manuals and use...

Page 41: ...chan e has been change lue has been chan lue has been chan e has been change lue has been chan e has been change lue has been chan e has been change from seconds to lue has been chan e has been change...

Page 42: ...trings and calculation o rol w more than the difiche in to 2 2 set point has bee _Probe1_Alarm a o increase the pro steps is fixed 5 s n modified 14 d visible to supe acity controlled com capacity con...

Page 43: ...All manuals and user guides at all guides com...

Page 44: ...HQs Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com Cod 03P220431 rack Rel 2 2 10 02 12 All manuals and user guides at...

Reviews: