µRack
Cod. CAREL +03P220431 rel. 2.2 dated 10/02/12
14
Also see the paragraph on Time settings.
The program will switch the devices on according to the start-up logic configured and the availability of the devices
DOffZ
DOnZ
NZ
SP
DZN
RP
Fig. 4.b
Compressor dead band with variable times
The user can decide to set a variable time between calls, depending on whether the pressure is moving away from the dead band. In particular, the activation /
deactivation time of the outputs decreases as the distance from the dead band increases. To set this function, the following parameters must be configured:
•
Maximum compressor on time
/ capacity control
(parameter r08)
•
Minimum compressor on time
/ capacity control
(parameter r07)
•
Pressure differential within which the time varies. (parameter r11)
•
Maximum compressor off time
/ capacity control
(parameter r10)
•
Minimum compressor off time
/ capacity control
(parameter r09)
Fig. 4.c
Key:
InPress
Suction pressure
DTNZ
Differential within which the time varies
STPM
Control set point
TOnMax
Maximum compressor on time
RBM
Control band
TOnMin
Minimum compressor on time
NZ
Dead band
TOffMax
Maximum compressor off time
DOnZ
Device activation zone
TOffMin
Minimum compressor off time
DOffZ
Device deactivation zone
In the activation phase, the following cases are possible:
1.
Pressure equal to point b
same call time as the “maximum compressor on time”
2.
Pressure between point b and point b + DTNZ
type of call between “Max on time” and “Min on time”
3.
Pressure greater than or equal to point b + DTNZ
same call time as “Min on time”
In the deactivation phase, on the other hand, the following cases are possible:
1.
Pressure equal to point STPM
same call time as the “maximum compressor off time”
2.
Pressure between point STPM and point STPM - DTNZ
type of call between “Max off time” and “Min off time”
3.
Pressure greater than or equal to point STPM - DTNZ
same call time as “Min off time”
N.B. To make the device call time constant in the activation phase, simply set the times TOnMax and TonMin to the same value. The same is true for the deactivation
phase.
4.4
Number of compressors started with probe 1 fault
In the event of a suction probe fault or not connected alarm, parameter /07 indicates the number of outputs
(compressors and capacity control, configured with
capacity-controlled compressors)
,
forced on, so as to ensure minimum cooling/operation of the installation.
For two circuits, the parameter relating to the second circuit /08 must also be set. This will be related to the probe in the 2nd circuit.
Key:
DOffZ
Device deactivation zone
DOnZ
Device activation zone
NZ
Dead band
DZN
Dead band differential
RP
Suction pressure read
SP
Set point
STPM
RBM
NZ
DOffZ DOnZ
InPress [ºbar]
TOnMin
TOffMin
TOnMax
TOffMax
DTNZ
B
DTNZ