µRack
Cod. CAREL +03P220431 rel. 2.2 dated 10/02/12
35
Alarms sent to the supervisor
Tab. 14.c
Integer variables
Flow
Index
Description
Parameter
R/W
1
Type of unit “/00”
/00
R/W 2
Unit
model
“/01”
/01
R
3
Number of compressors
R/W
4
Number of fans “/09”
/09
R 5
Unit status
0 = Unit ON
1 = OFF from alarm
2 = OFF from supervisor
3 = OFF from remote input
4 = OFF from parameter
5 = Manual operation
6 = Install default
7 = PREVENT IN PROGRESS
R/W
6
Minimum call time for compressor start (dead band)
r07
R/W
7
Minimum call time for compressor stop (dead band)
r09
R/W
8
Minimum compressor ON time
C01
R/W
9
Minimum compressor OFF time
C02
R/W
10
Minimum time between starts of different compressors
C03
R/W
11
Minimum time between starts of the same compressor
C05
R/W 12
Reserved
R/W 13
Reserved
R/W
14
Liquid level alarm delay
A18
R/W 15
Reserved
R/W
16
Number of compressors on in circuit 1 with probe damaged
/07
R/W
17
Number of compressors on in circuit 2 with probe damaged
/08
R/W
18
Number of fans on with probe damaged
/12
R 19
Version of the application
R/W
20
Type of refrigerant
/35
R/W
21
Capacity of compressor 1
/03
R/W
22
Capacity of compressor 2
/04
R/W
23
Capacity of compressor 3
/05
R/W
24
Capacity of compressor 4
/06
R
25
Inverter readout % “
/11
R/W
26
Multifunction DI configuration
/15
R/W
27
B1 type probe
/16
Flow
Index
Description
Alarm code
R
1
Alarm: compressor 1
A01
R
2
Alarm: compressor 2
A02
R
3
Alarm: compressor 3
A03
R
4
Alarm: compressor 4
A04
R 5
Alarm:
fan
1
A22
R 6
Alarm:
fan
2
A23
R 7
Alarm:
fan
3
A24
R 8
Alarm:
fan
4
A25
R
9
Alarm: liquid level
A09
R 10
Alarm: general low suction pressure 1
(from multifunction DI)
A10
R 11
Alarm: general low suction pressure 2
(from multifunction DI)
A11
R
12
Alarm: low discharge pressure
A13
R
13
Alarm: high discharge pressure
A14
R
14
Alarm: low suction pressure 1”
A15
R
15
Alarm: high suction pressure 1
A16
R
16
Alarm: low suction pressure 2
A17
R
17
Alarm: high suction pressure 2 “
A18
R
18
Probe B1 faulty or disconnected
A20
R
19
Probe B2 faulty or disconnected
AB2
R
20
Probe B3 faulty or disconnected
AB3
R
21
Probe B4 faulty or disconnected
A19
R
22
Compressor 1 maintenance
A05
R 23
Compressor
2
maintenance
A06
R
24
Compressor 3 maintenance
A07
R
25
Compressor 4 maintenance
A08
R
26
General discharge pressure switch (from multifunction DI)
A12
R
27
General fan thermal overload
A26
R
28
Prevent high discharge pressure
A27
R
29
Compressors off due to prevent
A28
R
30
Excessive prevent frequency
A29
R
31
High outside temperature
HtE
R
32
High room temperature
HtA