“ultimateSAM - design” +03U0071EF - rel. 2.0 - 20150301
37.5 mm
(1.48 in)
82.5 mm
(3.25 in)
Pedestal in
minimized position
Pedestal in
standard position
Fig. 7.f
For sites at which the condensate drains empty into a sump outside of the
duct or AHU, the seal height of the P-trap must be increased by the amount
of static pressure inside the duct.
7.3.1
Condensate drain for SA0 (single-pipe) (optional,
sold separately)
The single-pipe version SA0 features two condensate drains: the first on the
1/2” (GAS or NPT) steam inlet manifold and the second at the end of the 3/8”
(GAS or NPT) uprights.
Fig. 7.g illustrates the typical connection using two condensate drain traps.
Fig. 7.g
A condensate drain pipe for draining outside of the AHU/duct is also as an
option (Fig. 3.h)
To install this, make a hole in the duct as shown on the drilling template. The
outside diameter of the condensate drain pipe is 10 mm.
∅
10 mm (0.39”)
Fig. 7.h
Pos.
Meaning
Opt.
Description
Condensate drain to fit on the
SA0 single pipe
Upright length
mm (in)
A
A= 358 (14)*
SA0AALI0*0
B
B= 510 (20)*
SA0BALI0*0
C
C= 662 (26)*
SA0CALI0*0
D
D= 814 (32)*
SA0DALI0*0
E
E=966 (38)*
SA0EALI0*0
F
F= 1118 (44)*
SA0FALI0*0
G
G= 1270 (50)*
SA0GALI0*0
H
H= 1422 (56)*
SA0HALI0*0
I
I= 1574 (62)*
SA0IALI0*0
J
J= 1726 (68)*
SA0JALI0*0
K
K= 1878 (74)*
SA0KALI0*0
L
L= 2030 (80)*
SA0LALI0*0
Material
S
S = Stainless steel
-
O.D. mm (in)
10
10= 10 mm (0.40)
O.D.
Region
0
Other (GAS)
U
North America (NPT)
Free
0
Tab. 7.e
240 (9.5”)
Fig. 7.i
The thermostatic steam trap SAKTBH0000 (Fig. 3.i, supplied as an option)
can be connected directly to the condensate drain pipe. In this case too, use
a drain trap to drain the condensate from the manifold. The SAKTBH0000
kit should be installed vertically, using the adapter supplied with quick
coupling (Fig. 3.j).
SAKTBH0000
Note: Not available in North America
Fig. 7.j
240 mm
Fig. 7.k