30
ENG
“ultimateSAM - design” +03U0071EF - rel. 2.0 - 20150301
In order to have just one condensate drain point, use kit SAKC0ST000 (Fig.
3.k). This kit is used to connect the manifold condensate drain to the upright
condensate drain pipe (Fig. 3.l)
Fig. 7.l
The thermostatic steam trap SAKTBH0000 is also available. With this
solution, the quick coupling supplied with the thermostatic steam trap is
not needed.
Fig. 7.m
Example
:
if installing an ultimateSAM SA0HALI000 distribution system
with just one drain trap rather than two, fit a condensate drain pipe kit and
condensate drain “T” connection.
For the code of the pipe that is suitable for the length of the uprights, see
Table 9.a in the Technical specifications manual; in this case, choose a kit
with code SAKCHS1000, and a gas fitting.
The code of the “T” connection, on the other hand, is SAKC0ST000. Then
simply connect the correctly sized drain trap (see par. 7.3).
A certain clearance needs to be allowed for, according to the type of
ultimateSAM SA0* distribution system configuration:
H
H
H
H
H
L
H
H
L
H
L
H
L
L
250 mm
Effective single upright flow-rate ≤ 50kg/h (110lb/h) -> H=150mm (5.9in)
Minimum AHU height: 300mm (11.8in)
Effective single upright flow-rate > 50kg/h (110lb/h) -> H=200mm (7.9in)
Minimum AHU height: 400mm (15.8in)
H
H
H
H
H
L
H
H
L
H
L
H
L
L
250 mm
Effective single upright flow-rate ≤ 50kg/h (110lb/h)
H=150mm (5.9in) L=250mm (9.8in)
Minimum AHU height: 400mm (15.8in)
Effective single upright flow-rate > 50kg/h (110lb/h)
H=150mm (5.9in) L=250mm (9.8in)
Minimum AHU height: 450mm (17.7in)
H
H
H
H
H
L
H
H
L
H
L
H
L
L
250 mm
Effective single upright flow-rate ≤ 50kg/h (110lb/h)
H=150mm (5.9in) L=160mm (6.3in)
Minimum AHU height: 460mm (18.1in)
Effective single upright flow-rate > 50kg/h (110lb/h)
H=200mm (7.9in) L=200mm (7.9in)
Minimum AHU height: 600mm (23.6in)
H
H
H
H
H
L
H
H
L
H
L
H
L
L
250 mm
SAKD0S1000 kit:
(centre distance 235mm(9.3in))
Effective single upright flow-rate ≤ 50kg/h (110lb/h)
H=150mm (5.9in) L=160mm (6.3in)
Minimum AHU height: 535mm (21.1in)
Effective single upright flow-rate > 50kg/h (110lb/h)
H=200mm (7.9in) L=200mm (7.9in)
Minimum AHU height: 635mm (25.0in)