22
“Power+” +0500120IE - rel 1.1 - 02.05.2017
ENG
5.1
Rated values
The table below shows the rated input and output currents, as well as the specifications for sizing the cables (cross-
section, maximum length) and the fuses. The values refer to an operating temperature of 60°C, recommend air flow,
and a switching frequency of 8 kHz, unless otherwise specified.
Model
Ra
ted input
cur
ren
t
(1)
Fuse or t
ype B
cir
cuit br
eaker
Po
w
er cable
cr
oss-sec
tion
Ra
ted output
cur
ren
t
Ra
ted output
po
w
er
(2)
M
ax. t
otal
dissipa
tion
(2)
M
ax. hea
tsink
dissipa
tion
(2)
M
inimum
mot
or cable
cr
oss-sec
tion
M
aximum
mot
or cable
length
(A)
(A)
(mm
2
)
(A)
(kW)
(W)
(W)
(mm
2
)
(m)
PS2**122*****
21-17
25
4
12
3.8
270
150
2.5
5
PS2**061*****
21-17
25
4
6
2.2
240
130
1.5
5
Tab. 5.b
Note:
(1)
Rated input current is referred to minimum and maximum input voltage.
(2)
Referred to following conditions:
• 230Vac/115Vac input voltage;
• 230Vac output voltage;
• rated output current;
• the power output of DCbus is included.
PS2**122***** models are sized to delivery up to 750 W to DCbus output.
PS2**061***** models are sized to delivery up to 440 W to DCbus output.
Recommended air flow
Model
components side
heatsink side (models with finned heatsink only)
(cfm)
(m
3
/h)
(cfm)
(m
3
/h)
PS2**122*****
15
28
24
42
PS2**061*****
15
28
24
42
Tab. 5.c
Note:
Air flow is referred to the heatsink section perpendicular to fins. A duct for conveying air flow is suggested.
If the air flow to heat sink is reduced, the product places itself under protection.
6.
UL NOTES FOR INSTALLATION INSTRUCTIONS
Power+ PDS2 models, which coform to the UL and CSA standards, have UL/CSA mark on the nameplate.
Power+ protection fuses must be provided according to the following table:
Power+
Manufacturer
UL file
Fuse
Nominal current (A)
PS2**122*****
BUSSMANN
E4273
FRS-R-35
35
PS2**061*****
BUSSMANN
E4273
FRS-R-35
35
Note:
other equivalent UL Listed or UL Recognized External Semiconductor Fuses with the same ratings and
in particular with “Clearing I2t” equal or lower than the ones of fuse models indicated in the table.
•
The PSD2 series is classified as Opentype
•
Removable terminal blocks wiring connection must be made with thr female connection supplied with the drive.
CAREL INDUSTRIES reserves the right to modify the features of its products without prior notice.