19
“Power+” +0500120IE - rel 1.1 - 02.05.2017
ENG
3.11 Power+ models with finned heatsink without fan
Power + models with finned heatsink without fan for cooling are devices that need a forced-air system, which is in
charge of the installer.
Assembly
1
2
1 Panel where the inverter is fixed
2
Holes/ screws to use for fixing the inverter to the
panel
Dimensions
71,7
87,1
197
8,4
17,2
14,4
113,4
17,4
41,9
136
41,9
33,5
8
96
9,4
42,8
Important
• Make sure that the final machine complies with UL 508C to ensure product performance, declared by Carel.
• Make sure that on the heat sink is present an air flow equal to 28 m3/h, which flows to the long side of the heatsink,
ie from bottom to top.
• Make sure that temperature long 4 side of heat sink never exceed the given parameters measured at specific
points during the testing conducted by UL.
Important:
the maximum tightening torque is 3 Nm.