![Carel MasterAria User Manual Download Page 45](http://html1.mh-extra.com/html/carel/masteraria/masteraria_user-manual_2557422045.webp)
45
ENG
MasterAria +030220481 - rel. 1.0 - 12.11.2007
P01
TA (°C)
P111
P112
ON
OFF
Fig. 5.h
Key:
P111
heater activation delta
P112
heater hysteresis
R
heater
TA
room temperature (control probe)
Table of dipswitch settings
function
n.
function setting
position
heat, cool-enable functions
1
deactivated
OFF
remote cooling/heating (DI2)
2
activated
ON
remote lock active
3
deactivated
OFF
2 coils available
4
deactivated
OFF
electric heater fi tted
5
activated
ON
control probe on “acqua”
terminal
6
activated
ON
Tab. 5.b
Functional diagrams
U
S
S
VF
VC
P114=30
P116=30
100%
P01
TA (°C)
P109=2
P114=30
P115=30
P109=2
P119=20
Fig. 5.g
Important:
drawing not to scale for graphics requirements.
Key:
P114
proportional band for damper (°C/10)
S
outside damper
P115
proportional band for cooling valve (°C/10)
TA
room temperature (control probe)
P116
proportional band for heating valve (°C/10)
VC
heating valve
P109
dead band (°C/10)
VF
cooling valve
P01
set point
U
outputs
Description of the functions
The hot/cold water valve is opened according to the activation delta
•
(default =0) and the P+I algorithm proportional bands;
the outside damper is activated when the air handling unit is started. It
•
closes in the event of antifreeze alarms, activated by digital input DI4;
the heat recovery unit damper is opened in cooling or heating if the
•
conditions are favourable (see the paragraph on the heat recovery
unit);
dirty fi lter alarm via diff erential pressure switch connected to digital
•
input DI5.