![Carel MasterAria User Manual Download Page 18](http://html1.mh-extra.com/html/carel/masteraria/masteraria_user-manual_2557422018.webp)
18
ENG
MasterAria +030220481 - rel. 1.0 - 12.11.2007
Summary table of MasterAria options
Accessory
Accessory
Supplied with MasterAria
electrical panel
Accessory
Setting
P39, P40, P41, P42
Expansion board w/ 4 relays
HYVC000R00
Expansion board w/ 4 triacs
HYVC000T00
Expansion board w/ 0 to 10
Vdc + relays
HYVC000V00
Expansion board w/ 2 triacs
+ 2 relays
HYVC000M00
NO4
(volt.
relay)
NO5
(volt.
relay)
NO6
(relay)
NO7
(relay)
NO4
(volt.
triac)
NO5
(volt.
triac)
NO6
(volt.
triac)
NO7
(volt.
triac)
NO4
(0-10
Vdc)
NO5
(0-10
Vdc)
NO6
(relay)
NO7
(relay)
NO4
(volt.
triac)
NO5
(volt.
triac)
NO6
(relay
2 A)
NO7
(relay
10 A)
0
Output disabled
1
ON/OFF cold water valve
(norm. open)
√
√
√
√
√
√
√
√
√
√
√
√
√
√
2
ON/OFF hot water valve
(norm. open)
√
√
√
√
√
√
√
√
√
√
√
√
√
√
3
Chiller activation signal,
cold water request (norm.
open). Contact closed
with cold/hot water valve
or cold water valve only
active (open with valve
deactivated)
√
√
√
√
√
√
√
√
√
√
√
√
√
√
4
Boiler, heat pump
activation signal, hot
water request (normally
open). Contact closed
with cold/hot water valve
or hot water valve only
active (open with valve
deactivated)
√
√
√
√
√
√
√
√
√
√
√
√
√
√
5
ON/OFF hot/cold water
valve (normally open).
Activated with cooling/
heating request from
controller. Off when are
both deactivated
√
√
√
√
√
√
√
√
√
√
√
√
√
√
6
ON/OFF heater(normally
open) (set parameters P46
& P13)
√
√
√
√
√
√
√
√
√
√
√
√
√
√
7
Alarm (normally open)
√
√
√
√
√
√
√
√
√
√
√
√
√
√
8
DO NOT SELECT
9
3-point valve + (clockwise)
for cold water (hot/cold
water if dip4=OFF)*
√
√
√
√
√
√
10
3-point valve -
(anticlockwise) for cold
water (hot/cold water if
dip4=OFF)*
√
√
√
√
√
√
11
3-point valve + (clockwise)
for hot water (deactivated
if dip4=OFF) *
√
√
√
√
√
√
12
3-point valve -
(anticlockwise) for hot
water (deactivated if
dip4=OFF) *
√
√
√
√
√
√
13
Valve with 0 to 10 Vdc
input for cold water (hot/
cold water if dip4=OFF) *
√
√
14
Valve with 0 to 10 Vdc
input for hot water
(deactivated if dip4 =OFF)
*
√
√
15 DO NOT SELECT
16 DO NOT SELECT
17
0 to 10 Vdc output for
modulating heater control
(from external module).
Set parameters P111,
P117.*
√
√
18
Output (triac or relay) for
man. of ON/OFF heaters
(with hysteresis) on P+I. Set
parameters P111, P112.*
√
√
√
√
√
√
√
√
√
√
√
√
√
√
19
Open 3-point outside
damper*
√
√
√
√
Summary of Contents for MasterAria