Cod. +030220151 - Rel. 2.1 - 04/09/98
55
TECHNICAL FEATURES
Set-point:
-50T90 (-50/+90°C; -58/+194°F)
Power supply
230 ±15%
Consumption
4 VA
Precision
±
1°C,
±
2°F
Case
plastic,
Installation
incorporated
Working temperature
0÷50°C; 32÷122°F
Storage conditions
-10/+70°C; 14/158 °F
Connections
digital inputs and sensor on plug-in connectors, outputs on faston
connectors
Display
2 and a half digits
Signalling:
luminous
acoustic
compressor, continuous cycle, defrosting, fan, IR activated, alarm/ light
alarm buzzer
Inputs
refrigerating room sensor, defrosting sensor, multi-function inputs
Type of sensor:
NTC CAREL 10K
Ω
a 25ºC (for codes see Carel price-list)
Relay outputs (all)
Disconnection of type 1B according to ECC EN 60730-1
Compressor
SPST relay, max.switching capacity: 20A/250V
Defrosting
SPDT relay, max.switching capacity: 8A/250V
Fan
SPST relay, max.switch.capac.: 16A/250V
Light/aux output
SPST relay, max.switch.capac.: 16A/250V
Alarm output
SPDT relay, max.switching capacity: 8A/250V
Kind of environmental pollution
normal
Frontal protection index
IP54
Important warning: the cables to be connected to the controller contacts should resist to the maximum
operating temperature which is determined by considering the expected maximum ambient tempe
the controller overheating equal to 20°C. Moreover, it is necessary to protect the controller with a 1A,
250V
protection fuse should be placed.
CONNECTIONS
Caution: with respect to safety rules follow the
below quoted instructions carefully:
•
The cables to be connected to the controller
contacts should resist the maximum operating
temperature which is determined by considering
the maximum ambient temperature ex
the controller auto-heating equal to 20 °C.
•
Moreover, it is necessary to protect the
controller with a 1A, 250V
fuse.
•
Connect the terminals 12, 15 and 17 to the
same electric potential, as shown in the picture
9 10
13 14
11 12
19 20
17 18
15 16
7
8
5
6
3
4
AMB.
DEF
Dig.In1 Dig.In2
1
2
POWER
230 V~
c
c
c
c
c
SERIAL LINK
Power Supply
Power Supply
ir96