ALARM PARAMETERS
A0
Alarm and fan differential
C
0.1
+20
°C/°F
0.2
AL
Low temperature alarm (indicates the max. allowed deviation from
the set- point). If = 0 disables the low temperature alarm
F
0
+199
°C/°F
0
AH
High temperature alarm (indicates the max. allowed deviation from
the set-point). If = 0 disables the high temperature alarm
F
0
+199
°C/°F
0
Ad
Temperature alarm delay
C
0
199
min
120
A4
Digital input n.1 configuration
C
0
7
-
0
A5
Digital input n.2 configuration
C
0
7
-
0
A6
Cut-out of compressor by external alarm: 0=OFF, 100=ON Enabled
if either A4 or A5= 1 or 2, see Duty setting and digital input
C
0
100
min
0
A7
Delay in registration of the input <<delayed alarm>> (A4 or A5 = 2)
C
0
199
min
0
F
FAN PARAMETERS
F0
Management of fans: 0 = always activated fans except on specific
phases (see parameters F2, F3, and Fd)
1= fans controlled by a thermostat according to the difference
between ambient temp. and evap. temp.,
2= fans controlled by a thermostat according to the evaporator
temperature
C
0
2
flag
0
F1
Fans activation temperature: if F0=1 it is the minimum difference
between ambient temp. and evap. temp. (t. evap. < t.amb.)
if F0=2, the fan is ON if Evap.temp<Se F1 - A0
the fan is OFF if Evap.temp. > Se F1
F
0
+20
°C/°F
5
F2
Stop fans when compr. is Off (0=no, 1=yes). Active if F0=0
C
0
1
flag
1
F3
Stop fans during defrost (0=no,1=yes).
This parameter is active for any value of F0
C
0
1
flag
1
Fd
Stop after dripping. Active for any value of F0
F
0
15
min
1
H
OTHER SETTING
H0
Address within network
C
0
15
-
0
H1
Selection of relay 4 functioning: 0= auxiliary output, 1=normally de-
energised alarm, 2= normally energised alarm
C
0
2
flag
0
H2
0= buttons inhibited; 2= buttons & IR inhibited; 3=IR inhibited
C
0
3
flag
1
H3
Code to enable remote programming
C
00
199
-
00