“Wellness” +0300060EN - rel. 1.2 - 03.09.2012
installer
user
ser
vice
3. STEAM DISTRIBUTION
For the correct delivery of steam, a steam distributor must be used, sized
according to output of the humidifi er.
In addition, the distributor must be installed in a part of the steam bath
that is easily reached by the hoses running from the humidifi er (see Fig.
3.b as an installation example).
3.1 CAREL jet distributors (SDPOEM00**)
These can be fi tted horizontally or vertically (hole facing upwards).
See page 42 for the models of distributors.
Assembly instructions (see Fig.3.a):
•
make a series of holes on the wall according to the distributor drilling
template;
•
insert the distributor;
•
fasten the fl ange using 4 screws.
3
1,
5
5
0
5
0
3
1,
5
5
0
3
1,
5
3
1,
5
57
,
5
100
C
D
C
A
A
B
B
Fig. 3.a
Key:
A.
steam inlet
B.
condensate drain
C.
steam outlet.
the dimensions of the hole vary depending on the models of
distributor:
model SDPOEM0000: hole made manually, up to 30 mm (1.2”) in
diameter);
model SDPOEM0012: diameter of the hole 12 mm (0.5”);
model SDPOEM0022: diameter of the hole 22 mm (0.9”).
D
drilling template
Note: if steam hoses with an inside diameter of 30 mm (1.2”) are
used, remove the 22 mm (0.9”) steam inlet section.
3.2 CAREL linear distributors for air ducts
(DP***DR0)
Install away from obstacles (curves, branches, changes in cross-section,
grills, fi lters, fans).
Minimum distance between the distributor and the obstacle: 1/1.5 m
(3.3/4.9 ft). Increase the distance if:
•
the air speed increases in the duct,
•
the relative humidity of the air increases before and after humidifi cation,
•
the turbulence decreases.
See page 42 for installation examples.
Assembly instructions (see Fig.3.b):
•
make a series of holes on the wall according to the distributor drilling
template (included in the packaging with the distributor);
•
fasten the fl ange using 4 screws.
Fig. 3.b
B
Y
X
A
X
°
2
1
2
3
4
5
6
8
7
Fig. 3.c
Key:
1
“L”-shaped mounting support (where featured)
2
fl ange gasket
3
steam inlet (ØA)
4
condensate drain (ØB)
5
screw diameter (see the instruction sheet supplied with the distributor)
6
length (depending on the model of distributor, see par. “10.5” page 42)
7
angle (around 2°) for draining the condensate.
8
diameter of the hole on the wall (ØY)
Dimensions in mm (in)
CAREL linear distributors
DP***D22R0
DP***D30R0
DP***D40R0
ØA
22 (0.9”)
30 (1.18”)
40 (1.57”)
ØB
10 (0.4”)
10 (0.4”)
10 (0.4”)
ØY
58 (2.3”)
68 (2.7”)
89 (3.5”)
Ø
35 (1.4”)
45 (1.8”)
60 (2.4”)
X
68 (2.7”)
77 (3.0”)
99 (3.9”)
Tab. 3.a
Important:
Important:
1.
fi t the distributor at a slight incline (at least 2°, to prevent the return
of condensate);
2.
the “L”-shaped mounting support (see part 1 Fig. 3.c) is supplied with
steam distributor models from DP085* to DP025*. For shorter lengths,
the support can be supplied as an option (code 18C478A088).