12
The diagram shows the operating modes of the controller.
Factory-set parameters
Parameter
Code
Set value
Set-Point
St1
50
Differential
P1
5.0
Neutral zone
P3
0
Probe calibration
P14
0.0
Low humidity alarm
P25
0.0
High humidity alarm
P26
99.9
Alarm differential
P27
2.0
Delayed alarm
P28
20
3.7.1 Setting the main parameters
SET-POINT (St1)
hold down
for a few seconds;
St1 appears on the display;
release
;
the SET 1 value flashes on the display;
press / to change its value;
press
to confirm the new St1 value and return to the main window.
Differential (P1)
hold down
for 5 seconds;
“P1”, the first parameter, appears on the display;
press
;
the current value of P1 appears on the display;
press / to change its value;
press
to confirm the new value;
press
to return to the main window.