Carel EVD evolution User Manual Download Page 26

25

ENG

“EVD evolution” +030222041 - rel. 1.0 - 01.06.2008

Output

The relay output can be configured to control the solenoid valve or as an 
alarm relay output. See the chapter on “Alarms”.

Parameter/description

Def.

Configuration
Relay configuration:
Disabled;  Alarm relay (open when alarm active);  Solenoid valve 
relay (open in standby);  Valve relay +alarm (open in standby 
and control alarms)

Alarm 
relay

Tab. 6.f

Control status 

6.2 

The  electronic  valve  driver  has  6  different  types  of  control  status,  each 
of  which  may  correspond  to  a  specific  phase  in  the  operation  of  the 
refrigeration unit and a certain status of the driver-valve system.
The status may be as follows:

forced closing:

• 

 initialisation of the valve position when switching the 

instrument on;

standby:

• 

 no temperature control, unit OFF;

wait:

• 

  opening  of  the  valve  before  starting  control,  also  called  pre-

positioning, when powering the unit and in the delay after defrosting;

control:

• 

 effective control of the electronic valve, unit ON;

positioning:

• 

 step-change in the valve position, corresponding to the 

start of control when the cooling capacity of the controlled unit varies 
(only for pLAN EVD connected to a pCO);

stop:

• 

 end of control with the closing of the valve, corresponds to the 

end of temperature control of the refrigeration unit, unit OFF.

Forced closing

Forced  closing  is  performed  after  the  driver  is  powered-up  and 
corresponds to a number of closing steps equal to the parameter “Closing 
steps”, based on the type valve selected. This is used to realign the valve 
to the physical position corresponding to completely closed. The driver 
and the valve are then ready for control and both aligned at 0 (zero). On 
power-up, first a forced closing is performed, and then the standby phase 
starts.

Parametro/description

Def.

Min.

Max.

UOM

Valve
EEV closing steps

500

0

9999

step

Tab. 6.g

Standby

Standby corresponds to a situation of rest in which no signals are received 
to control the electronic valve. This normally occurs:

when  the  refrigeration  unit  stops  operating,  either  when  switched 

• 

off manually (e.g. from the button, supervisor) or when reaching the 
control set point;
during defrosts, except for those performed by reversing of the cycle 

• 

(or hot gas bypass).

In  general,  it  can  be  said  that  the  electronic  valve  driver  is  in  standby 
when the compressor stops or the control solenoid valve closes. The valve 
is closed or open, delivering around 25% of the flow-rate of refrigerant, 
based on the setting of the “valve open in standby” parameter.
In this phase, manual positioning can be activated.

Parameter/description

Def.

Min.

Max.

UOM

Valve open in standby
0=disabled=valve closed;
1=enabled = valve open 25%

0

0

1

-

Tab. 6.h

Pre-positioning/start control

If during standby a control request is received, before starting control the 
valve is moved to a precise initial position.

Parameter/description

Def.

Min.

Max.

UOM

Control
Valve opening at start (evaporator/valve 
capacity ratio)

50

0

100

%

Tab. 6.i

This  parameter  should  be  set  based  on  the  ratio  between  the  rated 
cooling capacity of the evaporator and the valve (e.g. rated evaporator 
cooling capacity: 3kW, rated valve cooling capacity: 10kW, valve opening 
= 3/10 = 33%).

If the capacity request is 100%:

Opening (%)= (Valve opening at start-up);

If the capacity request is less than 100% (capacity control):

Opening  (%)=  (Valve  opening  at  start-up)  ·  (Current  unit  cooling 
capacity), 
where  the  current  unit  cooling  capacity  is  sent  to  the  driver  via  pLAN 
by the pCO controller. If the driver is stand-alone, this is always equal to 
100%.

 

Note:

this procedure is used to anticipate the movement and bring the valve 

• 

significantly closer to the operating position in the phases immediately 
after the unit starts;
if there are problems with liquid return after the refrigeration unit starts 

• 

or in units that frequently switch on-off, the valve opening at start-up 
must be decreased. If there are problems with low pressure after the 
refrigeration unit starts, the valve opening must be increased.  

Wait

When  the  calculated  position  has  been  reached,  regardless  of  the 
time taken (this varies according to the type of valve and the objective 
position),  there  is  a  constant  5  second  delay  before  the  actual  control 
phase starts. This is to create a reasonable interval between standby, in 
which the variables have no meaning, as there is no flow of refrigerant, 
and the effective control phase.  

Control

The control request can be received by the closing of digital input 1 or 
via  the  network  (pLAN). The  solenoid  or  the  compressor  are  activated 
when  the  valve,  following  the  pre-positioning  procedure,  has  reached 
the calculated position. The following figure represents the sequence of 
events for starting control of the refrigeration unit.

Control delay after defrost

Some  types  of  refrigerating  cabinets  have  problems  controlling  the 
electronic valve in the operating phase after defrost. In this period (10 to 
20 min after defrosting), the superheat measurement may be altered by 
the high temperature of the copper pipes and the air, causing excessive 
opening of the electronic valve for extended periods, in which there is 
return of liquid to the compressors that is not detected by the sensors 
connected to the driver. In addition, the accumulation of refrigerant in 
the evaporator in this phase is difficult to dissipate in a short time, even 
after the sensors have started to correctly measure the presence of liquid 
(superheat value low or null). 
The driver can receive information on the defrost phase in progress, via 
digital input 2. The “Start delay after defrost” parameter is used to set a 
delay  when  control  resumes  so  as  to  overcome  this  problem.  During 
this delay, the valve will remain in the pre-positioning point, while all the 
normal sensor alarms procedures, etc. managed.

Parameter/description

Def.

Min.

Max.

UOM

Control
Start delay after defrost

10

0

60

min

Tab. 6.j

 

Important: 

if the superheat temperature should fall below the set 

point, control resumes even if the delay has not yet elapsed.

Summary of Contents for EVD evolution

Page 1: ......

Page 2: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s EVD evolution User manual electronic expansion valve driver...

Page 3: ......

Page 4: ...to open the device in any way other than described in the manual do not drop hit or shake the device as the internal circuits and mechanisms may be irreparably damaged do not use corrosive chemicals s...

Page 5: ......

Page 6: ...oning 17 4 4 Other functions 17 5 CONTROL 18 5 1 Main and auxiliary control 18 5 2 Superheat control 18 5 3 Special control 19 5 4 Auxiliary control 22 6 FUNCTIONS 24 6 1 Inputs and outputs 24 6 2 Con...

Page 7: ......

Page 8: ...play for EVD evolution English EVDIS00ES0 Display for EVD evolution Spanish EVDIS00FR0 Display for EVD evolution French EVDIS00IT0 Display for EVD evolution Italian EVDIS00PT0 Display for EVD evolutio...

Page 9: ...e time required to completely close the electronic valve being controlled while during normal operation the battery is recharged The complete module with batteries code EVBAT00300 and the box for batt...

Page 10: ...seriale di servizio rimuovere il coperchio per potervi accedere Tab 2 a Connection diagram superheat control 2 3 G G0 G G0 VBAT COM1 NO1 1 3 2 4 NET OPEN CLOSE Tx Rx GND DI1 S4 S3 S2 S1 GND DI2 VREF 2...

Page 11: ...idity greater than the 90 or condensing strong vibrations or knocks exposure to continuous water sprays exposure to aggressive and polluting atmospheres e g sulphur and ammonia fumes saline mist smoke...

Page 12: ...he 5 operation was successful UPLOAD the display saves all the values of the parameters on the source driver DOWNLOAD the display copies all the values of the parameters to the target driver RESET all...

Page 13: ...GND DI1 S4 S3 S2 S1 GND DI2 VREF Tx Rx GND DI1 S4 S3 S2 S1 GND DI2 VREF 1 15 3 EVD evolution Fig 2 j Key 1 white A Connection to EVBAT200 300 2 yellow B Connection to electronic pressure sensor SPK 00...

Page 14: ...status of the driver the activation of the protectors any alarms and the status of the relay output Hjgg hXVaYVb 6eZgijgV kVakdaV DC BDE 6A6GB GZaZ 1 2 3 4 5 6 Fig 3 c Key 1 1st variable displayed 2...

Page 15: ...ng the Service 10 parameters E6HHLDG9 Fig 3 e Note if no button is pressed after 5 min the display automatically returns to the standard mode Modifying the Manufacturer parameters The Manufacturer lev...

Page 16: ...on will commence between the two instruments and the driver automatically be enabled for control The main screen will shown on the display which can then be removed and control will be commence when r...

Page 17: ...sure sensor 0 5 to 7 bars for 3 drivers For the first driver select 0 5 to 7 barg For the second and third driver select remote 0 5 to 7 barg Note the range of measurement by default is always in bar...

Page 18: ...an be selected transcritical CO2 hot gas bypass etc as well as so called special control functions which do not involve the superheat activating auxiliary controls that use sensors S3 and or S4 and se...

Page 19: ...superheat temperature in fact corresponds to a situation of probable instability due to the turbulent evaporation process approaching the measurement point of the sensors The expansion valve must the...

Page 20: ...See the EEV system guide 030220810 for further information on calibrating PID control Note when selecting the type of main control both superheat control and special modes the PID control values sugg...

Page 21: ...ressure set point 3 20 290 200 2900 barg psig PID proportional gain 15 0 800 PID integration time 150 0 1000 s PID derivative time 5 0 800 s Tab 5 f Hot gas bypass by temperature This control function...

Page 22: ...le in display mode Control is direct as the pressure increases the valve opens Parameter description Def Min Max UOM SPECIAL Transcritical CO2 coefficient A 3 3 100 800 Transcritical CO2 coefficient B...

Page 23: ...t S4 to modulate the opening of the electronic valve so as to limit the lowering of the temperature read and consequently reach the control set point This is useful in applications such as the multipl...

Page 24: ...Backup sensors on S3 S4 In this case pressure sensor S3 and temperature sensor S4 will be used to replace sensors S1 and S2 respectively in the event of faults on one or both so as to guarantee a high...

Page 25: ...9 3 barg Ratiometric OUT 0 to 5 V Electronic OUT 4 to 20 mA 1 to 4 2 barg 0 4 to 9 2 barg 1 to 9 3 barg 0 to 17 3 barg 0 4 to 34 2 barg 0 to 34 5 barg 0 to 45 barg 0 5 to 7 barg 0 to 10 barg 0 to 18 2...

Page 26: ...at start evaporator valve capacity ratio 50 0 100 Tab 6 i This parameter should be set based on the ratio between the rated cooling capacity of the evaporator and the valve e g rated evaporator cooli...

Page 27: ...reaching 0 steps plus a further number of steps so as to guarantee complete closing Following the stop phase the valve returns to standby t t t t OFF ON R OFF ON ST OFF ON S OFF ON A T4 Fig 6 d Key A...

Page 28: ...s only valid when the driver is performing superheat control Unblock valve is an automatic safety procedure that attempts to unblock a valve that is supposedly blocked based on the control variables s...

Page 29: ...tection threshold 5 40 72 set point superheat K R LowSH protection integration time 15 0 800 s ALARM CONFIGURATION Low superheat alarm delay LowSH 0 alarm disabled 300 0 18000 s Tab 7 b When the super...

Page 30: ...ure alarm delay MOP 0 alarm disabled 600 0 18000 s Tab 7 d The integration time is set automatically based on the type of main control When the evaporation temperature rises above the MOP threshold th...

Page 31: ...will not resume based on the activation of the protector but rather on the reduction in the outside temperature The system will therefore remain in the best operating conditions a little below the thr...

Page 32: ...emote 0 to 10 barg remote 0 to 18 2 barg remote 0 to 25 barg remote 0 to 30 barg remote 0 to 44 8 barg External signal 4 to 20 mA Ratiometric 1 to 9 3 barg I 16 143 A Main control Multiplexed cabinet...

Page 33: ...n Current cooling capacity Control set point Superheat Suction temperature Evaporation temperature Evaporation pressure Condensing temperature Condensing pressure Modulating thermostat temperature EPR...

Page 34: ...50 60 76 Temperature S4 MAXIMUM alarm value C F A 47 46 C Temperature S4 MAXIMUM alarm value 105 Temperature S4 MINIMUM alarm value 200 392 C F A 45 44 CONTROL A Superheat set point 11 LowSH thre shol...

Page 35: ...e of variable A analogue D digital I integer Unit of measure 8 1 In the configuration parameters menu with access by manufacturer password the user can choose the unit of measure for the driver intern...

Page 36: ...irmware version Tab 8 b Digital input status 0 open 1 closed Note the readings of sensors S1 S2 S3 S4 are always displayed regardless of whether or not the sensor is connected Variables only accessibl...

Page 37: ...R Relay status 0 0 1 D 9 8 R ALARMS LOP low evaporation temperature 0 0 1 D 10 9 R MOP high evaporation temperature 0 0 1 D 11 10 R LowSH low superheat 0 0 1 D 12 11 R HiTcond high condensing tempera...

Page 38: ...nfiguration parameter automatic Depends on parameter Sensor S1 alarm manage ment Check the sensor connections Check the Sensor S1 alarm management and Pressure S1 MINIMUM MAXI MUM alarm value paramete...

Page 39: ...g normal operation the relay contact is closed and is open only in standby There is no change in the event of alarms solenoid valve relay alarm during normal operation the relay contact is closed and...

Page 40: ...ealarmisnotlinkedtoanyprotectionfunction It features a threshold and a delay and is useful in the event of sensor or valve malfunctions to protect the compressor using the relay to control the solenoi...

Page 41: ...driver will remain in standby however control will be able to start if the digital input is closed In this case it will start with current cooling capacity 100 case 4 unit in control digital input DI1...

Page 42: ...reaching operating conditions is very low for a few minutes Check that the LowSH threshold is greater than the superheat value measured and that the corresponding protection is activated integration...

Page 43: ...he LOP protection threshold is at the required saturated evaporation temperature between the rated evaporation temperature of the unit and the corre sponding temperature at the calibration of the low...

Page 44: ...iometric pressure sensor 0 to 5 V resolution 0 1 FS measurement error 2 FS maximum 1 typical electronic pressure sensor 4 to 20 mA resolution 0 5 FS measurement error 8 FS maximum 7 typical electronic...

Page 45: ...2 a Then the user can choose to directly access to the list of parameters for the EVD evolution 1 saved to EEPROM select tLAN This is done in real time ONLINE mode at the top right set the network add...

Page 46: ...e code Different firmware versions may cause compatibility problems Setting the default parameters 12 4 When the program opens select the model from the range and load the associated list of parameter...

Page 47: ...46 ENG EVD evolution 030222041 rel 1 0 01 06 2008...

Page 48: ......

Page 49: ...CAREL S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency 030222041 rel 1 0 01 06 2008...

Reviews: