10
Part Number 3E1086 R2
September 2002
Tamper the URI by opening the door of the cabinet. This releases the tamper switch.
The URI has a set of six jumpers grouped into two sets of three. One group is labelled
ENTRY and the other is labelled EXIT.
ENTRY jumpers set the voltage and card type of the reader connected to plug P5. EXIT
jumpers set the voltage and card type of the reader connected to plug P4.
Set the Entry and Exit jumpers for the Prox Plus 125 reader as shown below:
Entry and Exit Jumper Settings
Cardax
12 V
1
2
3
4
5
6
= jumper in place
Pins 3 and 6 = voltage supplied to reader
Pins 1,2 4 and 5 = reader type
Exit
Entry
Connector J2 controls the Confirmed Entry function. If you initialise the URI with no
jumper fitted on J2 the Confirmed Entry function will be ON. To switch the Confirmed
Entry function OFF, you must initialise the URI with one a mini jumper fitted across both
pins of connector J2.
Connect the Prox Plus 125 reader to the URI Entry plug (P5).
Note: If you are installing two entry readers (2 door URI software) you must
connect the second entry reader to Plug P4 to initialise the URI.
If you are installing only an Exit reader you must connect the reader to the
Entry Plug P5 to initialise the URI. Ensure Entry and Exit jumpers are set to
the same configuration. After you have initialised the URI you should
connect the Exit reader to Exit Plug P4.