background image

PROPER SIZING 
 

     It is important to consider that some manufacturers have inaccuracies within their generator ratings. In order to compare 
sizes, a very simple conversion can be used to determine a CO

2

 generator’s ACTUAL capacity to produce CO

2

. That is 

assuming you know the actual Btu output of the unit. British thermal units (BTUs) are stated as the actual heat output of the 
unit. Heat output (BTU), is determined simply by knowing the pressure of the gas, the type of gas (LP or natural) and the 
volume of gas allowed to flow to the burner.  
 

To convert an LP generator’s Btu rating into cubic feet of CO

2

 per hour:  

 

Btu / Hr X 1.18                               Example:   22,352 Btu X 1.18        22,352 X 1.18 = 26,375   
        1000                                                                      1000                                               1000 =  

26.4 cuft CO

2

 /hr

  

  

To  convert a natural gas generator’s Btu rating into cubic feet of CO

2

 per hour: 

 

    Btu / Hr                                          Example:   25,080 Btu                                       25,080   
      1000                                                                  1000                                               1000  =  

25.0 cuft CO

2

 /hr  

  

     So a CO

2

 generator running propane, with a rating of 22,352 Btu will produce 26.4 cubic feet of CO

2

 per hour assuming a 

standard pressure of 11”WP is used. A natural gas fired generator rated at 25,080 will produce up to 25 cuft / hr of CO

2

 per 

hour. That’s not the only thing to consider.  
     Before operating your CO

2

 generator, make sure you have accounted for the heat it will be producing. The ratings in the 

specification section of this manual give you the Btu per hour rating. Keep in mind that if the CO

generator is only ON for 30 

minutes each hour, the Btu / hr rating would be reduced by one half resulting in CO

outputs of ½ the capacity rating. 

     Determining what size unit and how long to allow the unit to run for is almost impossible due to the variables which 
different areas exhibit. Areas which are well sealed and have coordinated cooling devices can be easily maintained compared to 
areas which are not sealed or use a exhaust fan at all times.  
 

EXPANDING / ADDING BURNERS 

 
  The unique ability to increase the CO

2

 production capacity of the GEN-2 by adding burners allows you to expand as 

necessary.    Installing additional brass burners can increase the GEN-2’s CO

2

 producing capacity. Use only CAP burners.  The 

brass burners CAP uses are customized specifically for CO

2

 production.  Each burner installed adds approximately 3 cubic feet 

of CO

2

 per hour.   

*  People operating at altitudes higher than 3000ft above sea level may need to use slightly smaller burners to reduce 
fuel flow due to lower levels of oxygen available. If the flames appear yellowish or too large, please contact your dealer 
or CAP for special burners which are designed to operate at higher altitudes. 
 
 (LPC-1 & NGC-1)

 

Conversion Kits

: .Your generator can easily be converted to operate on either LP or natural gas by 

changing the brass burners and the pilot orifice. A conversion kit is available from your dealer. 

 

(PXO-1) Propane crossover:  

The Propane crossover assembly allows you to run your generator off of 2 propane tanks.  You 

can run it so that both will run down at the same time, or you can choose which tank to run the generator off of. That way the 
pilot flame never has to be re-lighted when changing out tanks.

 

 
CONTROLLER OPTIONS 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

     CAP offers a full line of CO

2

 controllers from simple to sophisticated. Controllers such as the 

CO

2

-2 or CO

2

-4 controllers intelligently coordinate your exhaust fans with the GEN-2. They also 

have built-in recycling timers and an optional Part-Per-Million upgrade. The simple and 
economical PPM-3 is designed specifically for people who want Part-Per-Million accuracy from 
their generator. 
     Some people believe that because a generator is so much cheaper to operate than compressed 
CO

2

 systems, they will not need a CO

2

 controller to regulate the CO

2

level inside their area. This is 

incorrect. CO

2

 generators produce quite a bit of heat and water vapor, which must be considered 

during your setup. Remember that the longer the CO

2

 generator runs, the more heat you are 

producing. In some cases the extra heat is not a problem, but for some setups, it is almost 
imperative to use some type of controller that turns on the generator only when the CO

2

 level is 

below the desired level. Using a timer to control the generator can be done with some success but 
you may end up quite a bit above or even worse quite a bit below your intended CO

2

 level.  

 

CO2-2 

PPM-3 

Summary of Contents for GEN-2

Page 1: ...t off valve on your gas supply Install the shut off valve in an accessible location Install the in line regulator to the gas supply 3 8 NPT female thread Connect the hose to the in line regulator To connect the hose use two wrenches in order to properly tighten the connection Open the gas valve on the gas line Check for leaks on all connections using a spray bottle with soapy water Look for bubble...

Page 2: ... for years of trouble free service The brass burners have been chosen over steel because of their superior performance over long periods of operation The powder coated enclosure can be cleaned with normal cleaners and will not fade over time However if for any reason the generator is not performing correctly shut off the gas supply and turn the unit OFF Simple problems can be remedied by consultin...

Page 3: ...clude the following 1 Powder coated steel enclosure The attractive steel enclosure has been powder coated for a long lasting finish that will not fade or shift color with time The enclosure itself has been engineered to allow the heat produced by the unit to dissipate and also to operate cooler than other competing generators 2 Visual appearance Keeping in mind the importance of the generator s fu...

Page 4: ... the GEN 2 s CO2 producing capacity Use only CAP burners The brass burners CAP uses are customized specifically for CO2 production Each burner installed adds approximately 3 cubic feet of CO2 per hour People operating at altitudes higher than 3000ft above sea level may need to use slightly smaller burners to reduce fuel flow due to lower levels of oxygen available If the flames appear yellowish or...

Page 5: ...have a bad thermocouple The flames on the main burner seem either too large with yellow flames or too small flashing ON and OFF You may have mixed burners Verify you are using natural gas burners with natural gas and propane burners with propane Lazy yellow flames indicate low gas flow due to low propane tank level or low natural gas pressure Long piping runs with natural gas need to be appropriat...

Reviews: