Via Wireless Lock
Installation Manual
July 2018 • Rev. 1.3
Page
of
11
20
Configure Via Control Unit
17. CONFIGURE VIA CONTROL UNIT
DIP SWITCHES
DIP SWITCH “A” - UNIT ID
Switches A1 and A2 are used to set the Unit ID of the lock (1 or 2). Switches A3 and A4 are not
used and should be in the UP (OFF) position.
Slide
switch A1 to DOWN (ON) to set the Unit ID to 1 (default):
Slide
switch A2 to DOWN (ON) to set the Unit ID to 2:
DIP SWITCH “B” - NET ID
Switches B1-B6 are used to set a Network ID which can be from 1 to 63 and must match the Net-
work ID of the Via Hub with which this lock will communicate. Do not duplicate Via Hub Network
IDs unless they are well out of the range of each other (500 feet should be safe). This switch is ori-
ented vertically. Set the Network ID according to the table below:
ON
ON
Figure 4: Configure Via Control Unit
ON
UNIT ID
NET ID
ON
+
-
FA
CT
OR
Y
ON
LY
PROG
READER
RST
OPTIONS
LED CABLE (4-PIN)
FROM READER
READER CABLE
FROM READER
LOCK MOTOR CABLE (2-PIN)
FROM LOCK
DOOR CONTACT CABLE
REX CABLE FROM LOCK
ON
ON
ON
ON