Configure Via Control Unit

17. CONFIGURE VIA CONTROL UNIT

DIP SWITCHES

DIP SWITCH “A” - UNIT ID

Switches A1 and A2 are used to set the Unit ID of the lock (1 or 2). Switches A3 and A4 are not 
used and should be in the UP (OFF) position. 

Slide

 

switch A1 to DOWN (ON) to set the Unit ID to 1 (default):

Slide

 

switch A2 to DOWN (ON) to set the Unit ID to 2:

DIP SWITCH “B” - NET ID

Switches B1-B6 are used to set a Network ID which can be from 1 to 63 and must match the Net-
work ID of the Via Hub with which this lock will communicate. Do not duplicate Via Hub Network 
IDs unless they are well out of the range of each other (500 feet should be safe). This switch is ori-
ented vertically.  Set the Network ID according to the table below: 

ON

ON

Figure 4: Configure Via Control Unit

ON

UNIT ID

NET ID

ON

+

-

FA

CT

OR

ON

LY

PROG

READER

RST

OPTIONS

LED CABLE (4-PIN)

FROM READER

READER CABLE

FROM READER

LOCK MOTOR CABLE (2-PIN)

FROM LOCK

DOOR CONTACT CABLE

REX CABLE FROM LOCK

ON

ON

ON

ON

cansec.com

CONNECTION 

STATUS LED 

(BLUE)

A

B

C

D

E

Summary of Contents for VIA

Page 1: ...July 2018 Cutting edge simplicity WIRELESS LOCK INSTALLATION MANUAL UNIVERSAL...

Page 2: ...E SIDE 7 10 REMOVE INSIDE TRIM 8 11 ADJUST DOOR THICKNESS 8 12 INSTALL OUTSIDE LEVER ASSEMBLY 8 13 INSTALL INSIDE MOUNTING PLATE AND ROSE LINER 9 14 INSTALL INSIDE ROSE AND LEVER 9 Install Door Contac...

Page 3: ...turn sends the data to a Wiegand reader port on the associated access control panel for verification If the lock relay operates indicating that access is granted the Hub will send a wireless unlock c...

Page 4: ...ELESS LOCK 2 ACCESS CONTROL PANEL FORCEDENTRYOUTPUT LOW BATTERY OUTPUT FORCED ENTRY OUTPUT LOW BATTERY OUTPUT The Via Universal Wireless Lock package consists of Via Lockset Via Reader Via Control Uni...

Page 5: ...eader Control Unit 4 AA batteries Temperature 30 C to 65 C 22 F to 149 F Dimensions Via Reader 2 24 L x 3 5 H x 0 79 D 57 mm L x 89 mm H x 20 mm D Via Control Unit 3 L x 5 2 H x 1 5 D 77 mm L x 133 mm...

Page 6: ...r on door face NOTE BACKSET ON DOOR FACE MUST BE SAME AS BACKSET OF YOUR LOCK c Mark two holes for screw post Drill holes as marked NOTE DRILL 21 8 54mm HOLE FROM BOTH SIDES TO AVOID SPLITTING WOOD 3...

Page 7: ...3 76mm PILOT HOLE FOR READER MO UNTIN G SCREWS 0 1 2 5mm PILOT HOLE FOR READER MO UNTIN G SCREWS 0 1 2 5mm PILOT HOLE FOR READER MO UNTIN G SCREWS 0 1 2 5mm 1 25 4mm P1 P2 P4 P3 1 25 4mm FOLD ON DOOR...

Page 8: ...ng plate 11 ADJUST DOORTHICKNESS 12 INSTALL OUTSIDE LEVER ASSEMBLY Remove outside mounting plate toward cylindrical case Put the catch tool into the allocated position of outside mounting plate as the...

Page 9: ...Install inside mounting plate to lock body b Press inside rose liner onto mounting plate and tighten mounting screws securely a Be sure to fit rose in recess of rose liner b Depress lever catch with...

Page 10: ...LVIA READER a Install Via Reader back plate and secure using 4 screws S1 S4 b Install Via Reader and secure with 2 screws S9 S10 Make sure the reader is securely snapped onto the back plate by pressin...

Page 11: ...hes B1 B6 are used to set a Network ID which can be from 1 to 63 and must match the Net work ID of the Via Hub with which this lock will communicate Do not duplicate Via Hub Network IDs unless they ar...

Page 12: ...N ON DOWN OFF ON DOWN 14 OFF OFF ON DOWN ON DOWN ON DOWN OFF 15 OFF OFF ON DOWN ON DOWN ON DOWN ON DOWN 16 OFF ON DOWN OFF OFF OFF OFF 17 OFF ON DOWN OFF OFF OFF ON DOWN 18 OFF ON DOWN OFF OFF ON DOWN...

Page 13: ...OFF ON DOWN ON DOWN OFF ON DOWN 46 ON DOWN OFF ON DOWN ON DOWN ON DOWN OFF 47 ON DOWN OFF ON DOWN ON DOWN ON DOWN ON DOWN 48 ON DOWN ON DOWN OFF OFF OFF OFF 49 ON DOWN ON DOWN OFF OFF OFF ON DOWN 50 O...

Page 14: ...OFF to enable door contact ON ON VIA UNIVERSAL HUB WIEGAND WIEGAND UNLOCK CMD WIEGAND UNLOCK CMD WIEGAND LOCK RELAY LOCK RELAY ANY ACCESS CONTROL PANEL DOOR 1 DOOR 2 12VDC FROM ACCESS CONTROL PANEL UN...

Page 15: ...heduled Wake Up mode POWER LEVEL SETTING STRATEGY By default the power levels for the Via Lock and Via Hub are set to LOW This provides a range of approx 70 range in a typical office environment When...

Page 16: ...THREE times if the signal level is weak AND the battery level is low If access is granted the Lock will beep ONCE and the GREEN LED will come on momentarily If access is denied the RED LED will flash...

Page 17: ...TROL UNIT BACK PLATE P5 P7 P8 S6 P6 a Install Via Control Unit back plate and secure using 4 screws S5 S8 b Install Via Control Unit PCB and secure using 3 screws S11 S13 c Install cover using 2 screw...

Page 18: ...20 HOWTO PRINTTEMPLATES To print the templates without scaling in the Print dialog box click Size and then specify the Actual size option Use a ruler to check the measurements before the templates are...

Page 19: ...PLATE FOLD ON DOOR EDGE PILOT HOLE FOR READER MOUNTING SCREWS 0 1 2 5mm 2 51mm DOOR THICKNESS HOLE CENTERS FOR DOOR THICKNESSES 3 76mm PILOT HOLE FOR READER MOUNTING SCREWS 0 1 2 5mm PILOT HOLE FOR RE...

Page 20: ...SECURE SIDE TEMPLATE 1 25 4mm FOLD ON DOOR EDGE 3 76mm 1 25 4mm PILOT HOLE FOR CONTROL UNIT MOUNTING SCREWS 0 1 2 5mm PILOT HOLE FOR CONTROL UNIT MOUNTING SCREWS 0 1 2 5mm PILOT HOLE CONTROL UNIT MOU...

Reviews: