Page 9 of 16
Installation Manual
Oct 2013 • Rev. 1.6
EXIT BUTTON AND DOOR CONTACT
NOTE
:
1.
Do not
apply power or attempt to switch any current through these inputs as this
will result in damage to the controller.
2.
The door contact input is used for forced entry and door-held-open
annunciation. The lock relay is deactivated when the door closes before the
unlock time ends.
3.
If door contact is
not
used, you
must
connect a jumper wire between the door
contact input and Ground. Connecting a door contact will enable door-held-
open annunciation via the reader’s beeper and will also deactivate the lock relay
when the door closes before the unlock time ends.
4.
Requires momentary closure to activate the lock relay.