Cannon Fitzroy Inbuilt Power Flue | 9
regUlatory loCation
MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE
TERMINALS, FAN ASSISTED FLUE TERMINALS, ROOM SEALED APPLIANCE
TERMINALS OR THE TERMINALS OF OUTDOOR APPLIANCES.
F
n
b
d
a
k
k
h
h
h
j
e
e
g
c
T
T
T
g
d
j
j
See note 2
See note 3
Openable
window
Door
I
P
M
T = Flue terminal M = Gas meter
I = Mechanical air inlet P = Electricity meter or fuse box
Shading indicates prohibited
areas for flue terminals
Ref Item
Minimum clearances
(mm)
Natural
draft
Fan
assisted
- unless appliance is certified for closer installation
Notes:
1 All distances are measured to the nearest part of the terminal.
2 Prohibited area below electricity meter or fuse box extends to ground level.
3 See clause 5.13.6.6 for restrictions on the flue terminal under covered areas.
4 See Appendix J. Figures J2(a) and J3(a), for clearances required from a flue terminal to an LP
Gas Cylinder. A flue terminal is considered to be a source of ignition.
5 For appliances not addressed above acceptance should be obtained from the technical regulator.
Special Note:
This chart MUST be read in-conjunction with
the full Australian Standard Gas Installations AS 5601.
THE POWER FLUE HEATER IS FAN ASSISTED. SEE COLUMN HIGHLIGHTED
a Below eaves, balconies and other projections:
Appliances up to 50 MJ/hr input 300 200
Appliances over 50 MJ/hr input 500 300
b From the ground, above a balcony or other surface 300 300
c From a return wall or external corner 500 500
d From a gas meter (M) (see 4.7.11 for vent location of regulator) 1000 1000
e From electricity meter or fuse box (P) 500 500
f From a drain pipe or soil pipe 150 75
g Horizontally from any building structure or obstruction facing a terminal 500 500
h From any other flue terminal, cowl, or combustion air intake 500 500
j Horizontally from an openable window, door, non-mechanical air inlet or other opening into a
building with the exception of sub-floor ventilation:
Appliances up t 150 MJ/hr input 500 300
Appliances over 150 MJ/hr input up to 200 MJ/hr input 1500 1500
Appliances over 200 MJ/hr input 1500 1500
All fan assisted flue appliances, in the direction of discharge 1500
k From a mechanical air inlet, including a spa blower 1500 1500
n Vertically below an openable window, non-mechanical air inlet, or any other opening into a building
with the exception of sub-floor ventilation:
Space heaters up to 50 MJ/hr input 150 150
Other appliances up to 50 MJ/hr 500 500
Appliances over 50 MJ/hr input and up to 150 MJ/hr input 1000 1000
Appliances over 150 MJ/hr 1500 1500
fig 4