Set value of the Protected Start
5
~
500kW
Set value of the protected
operation delay time
0.2
~
20S
Reverse Power Protection
Return set value of the
protected operation
5 kW
~
STart value
Delay time of the protected return
1.0
~
360S
Protected alarm DO output
Set one DO of the signal units as“power error”.
(not m muST
,
if not set this item
,
the alarm infor
can be only read from the screen of the controller,
without connecting port output
; )
Alarm/trip/close
Performing way
Operating phase sequence
Δφ
:
A
,
B
,
C /
Δφ
:
A
,
C
,
B
Phase sequence protection
Protected alarm DO output
Set one DO of the signal units as“phase sequence
error”. (not m muST
,
if not set this item
,
the alarm
infor can be only read from the screen of the
controller, without connecting port output
; )
Alarm/trip/close
Performing way
Current Setting of Alarm Action
0.5
~
30.0A
Alarm Action Time Delay
0.0
~
1.0S
Leakage Alarm
Alarm Return Current Setting
0.5
~
30.0A
Alarm Return Delay
0.0
~
1.0S
Alarm DO Output
Set one DO of the signal unit as “Leakage Alarm”.
Alarm + Switch Off
Performance
Delay Set Value
0
.
1~40.0S
Current Unbalance Protection
Power ON LED
Available
Return Value
Over Load Flashing LED
5%~STart Value
Available
Indication
Return Delay
OL/ SC/ EF Trip LED
10~200S
Available
Alarm DO Output
Set one of the DO of the signal unit as
“I unbalance alarm”.
Alarm/Break/Close
Performance
Available
LCD Display
Modbus
Converter
RS485/232
Protocol
Micropro 2 - 7.1
Set value of the Protected Start
45.0
~
return value
Set value of the protected
operation delay time
0.2
~
5.0S
Underfrequency Protection Parameters
Return set value of the
protected operation
Start value
~
65Hz
Delay time of the protected return
0.2
~
36.0S
Protected alarm DO output
Set one DO of the signal units as“underfrequency
error”.
(
not muST
,
if not set this item
,
the alarm
infor can be only read from the screen of the
controller, without connecting port output
; )
Alarm/trip/close
Performing way
Set value of the Protected Start
Return value
~
65.0HZ
Set value of the protected
operation delay time
0.2
~
5.0S
Over frequency Protection Parameters
Return set value of the
protected operation
45.0HZ
~
STart value
Delay time of the protected return
0.2
~
36.0S
Protected alarm DO output
Set one DO of the signal units as“overfrequency
error”.
(
not m muST
,
if not set this item
,
the
alarm infor can be only read from the screen of the
controller, without connecting port output
; )
Alarm/trip/close
Performing way
Set value of the protected Starting
Return value~1200V
Delay time of protection returns
0.2
~
60S
Over Voltage Protection Parameters
Delay time set of the protected
operation
0.2
~
60S
Set value of the protected
operation returns
Start Value
~
1200V
Protect alarming DO output
Set one DO of the signal units as“overvoltage error”.
(not muST
,
if not set this item
,
the alarm information
will only be read from the screen of the controller,
without the connecting point output
; )
Protection operating way
alarm/trip/close
2%~30%
set value of the Protected Start
0.2~60.0S
Set value of the protected
operation delay time
2%~ STarting value
Return set value of the
protected operation
0.2~60.0S
Delay time of the protected return
Set one DO of the signal units “U imbalance
alarm”.
(
not muST, if not set this item,
alarm infor can only be read from the screen
of the controller, without the connecting
port output
)
Protected alarm DO output
Alarm/trip/close
Performing way
Voltage Unbalance Protection
Intelligent Release
30
C&S Electric Limited
31
C&S Electric Limited
Intelligent Release
Micropro 2 - 7.1
W Nmaster 2
i
W Nmaster 2
i
Summary of Contents for WiNmaster 2
Page 1: ...Air Circuit Breaker Ro S H Compliant W Nmaster 2 i 630A 3200A www cselectric co in ...
Page 3: ......
Page 5: ...6 C S Electric Limited Complete Modular construction ...
Page 7: ...Fixed Type Drawout Type 8 C S Electric Limited Available in both Fixed Drawout version ...
Page 13: ...RoHS Compliant 14 C S Electric Limited ...
Page 15: ......
Page 16: ......
Page 25: ......
Page 35: ......
Page 36: ...Micropro 2 3 1 Micropro 2 4 1 37 C S Electric Limited Characteristics Curve W Nmaster2 i ...
Page 50: ...51 C S Electric Limited ...
Page 60: ......