- make sure that the cold water inlet valve item 

(fig. 6) and the gas valve

item 

(fig.5) are open

- make sure that there is no leakage along the entire gas line
- fit the gas knob temporarily
- turn on the water heater
- follow the instructions in section 6, Controls and use.

14

19

4. Commissioning

5

s t o p

detail 

driving

cam

Maximum gas power adjustment

(if necessary) :
The appliance is adjusted in the factory for

a  rated  gas  supply  pressure  (refer  to  the

Technical characteristics).
In the case of a higher supply pressure, the

maximum  gas  power  can  be  adjusted  by

proceeding as follows :
detach the stop from the fascia (fig. 7a)
place it on the gas control cam (fig. 7b).

Fig. 7a

Fig. 7b

Water pressure adjustment

(if necessary) :
The  appliance  is  configured  for  normal

water pressure
If your water supply pressure is low (< 2,5

bar), your appliance should be converted by

proceeding as follows :

- remove the case (refer to section 5)

- remove the pin 

A

(fig. 8)

- withdraw the water control 

B

(fig.8)

- remove the water filter 

C

(fig. 9)

- remove the governor 

D

(fig. 9)

- replace the water filter and reassemble

the components in reverse order.

B

A

Fig. 8

D

C

Fig. 9

Summary of Contents for CELT STAR C

Page 1: ...s one piece case the water heater comprises One piece chassis made of protected steel sheet Deflector Heat exchanger made of protected copper Combustion chamber Multi gas burner made of stainless stee...

Page 2: ...bar 3 lb in2 Minimum water pressure to operate the low pressure valve 0 1 bar 1 5 lb in2 Maximum normal pressure water pressure with governor 10 bar 145 lb in2 Maximum low pressure water pressure with...

Page 3: ...rised contractor Installation pipes should be fitted in accordance with BS 6891 Pipework from the meter must be of adequate size Pipes of a smaller size than the gas connection should be not used The...

Page 4: ...appliance is delivered complete ready to install The accessories pouch contains the following items Natural gas connection fig 5 one valve 3 4 F 1 2 M with 1 2 gasket one brazed angle socket 14 x 0 75...

Page 5: ...refer to the Technical characteristics In the case of a higher supply pressure the maximum gas power can be adjusted by proceeding as follows detach the stop from the fascia fig 7a place it on the ga...

Page 6: ...the gas control knob 6 Fig 10 6 Controls and use Fig 11 Control panel fig 11 Gas control knob symbols Off Reduced power Pilot ignition Intermediate piezo triggering powers Pilot position Maximum power...

Page 7: ...fitted with a system enabling the user to limit its maximum power To do this turn the knob until it is between the and This appliance operates in such a way that it can be used over a wide range of f...

Page 8: ...thout being connected to a flue After shutdown the water heater is in the safety position After approximately five minutes it can be turned on again manually following the normal lighting procedure If...

Reviews: