C&M 24 Installation And Operating Instructions Manual Download Page 7

7

4

Location

The boiler can be installed on any suitable internal wall.
Provision must be made to allow the correct routing of the flue
and siting of the terminal to allow the safe and efficient
removal of the flue products. A compartment or cupboard may
be used provided that it has been purpose-built or modified for
the purpose. It is not necessary to provide permanent
ventilation for cooling purposes. Detailed recommendations
are given in BS 5440 pt 2. If it is proposed that it is installed in
a timber framed building then reference must be made to
British Gas Document DM2, or advice sought from CORGI.
Avoid to install the boiler where the air inlet can be polluted
by chemical products such as chlorine (swimming pool aera),
or ammonia (hair dresser), or alcalin products (launderette)

Flue

Detailed information on flue assembly is contained in the
appropriate starter pack.
The boiler must be installed so that the flue terminal is
exposed to the free passage of external air at all times. It must
not be allowed to discharge into another room or space such
as an outhouse or closed lean-to. The minimum acceptable
clearances are shown below:

- A Directly below an opening, window, etc

300 mm

- B Above an opening, window, etc

300 mm

- C Horizontally to an opening, window, etc

300 mm

- D Below gutters, soils pipes or drain pipes

75 mm

- E Below eaves

200 mm

- F Below balconies or car port roof

200 mm

- G From a vertical drain pipe or soil pipe

150 mm

- H From an internal or external corner

300 mm

- I Above ground roof or balcony level

300 mm

- J From a surface facing the terminal

600 mm

- K From a terminal facing the terminal

1200 mm

- L From an opening in the car port into the dwelling 1200 mm
- M Vertically from a terminal on the same wall

1500 mm

- N Horizontally from a terminal on the same wall

300 mm

- Q Fixed by Ubbink Rolux 4 GM flue terminal
It may be necessary to protect the terminal with a 
guard. Reference should be made to the Building 
Regulations for guidance. Suitable guards may be 
obtained from the following manufacturer: 

Quinnel Barret & Quinnel Wireworks
Old Kent Road
London SE15 1NL
Tel: 0171 639 1357

Ventilation
The room in which the boiler is installed does not require specific
ventilation.  If it is installed in a cupboard or compartment
permanent ventilation is not required for cooling purposes.

Gas Supply
The gas installation and soundness testing must be in
accordance with the requirements of BS 6891.The boiler
requires a 22 mm supply. Ensure that the pipe size is
adequate for demand including other gas appliances on the
same supply.
Combustion system protection
The sulphur level contained in the gas should comply with
the européan Standards which are :

- maximum 150 mg/m3 for a short period in a year
- average level of 30 mg/m3 during one year

Electrical Supply
The appliance requires an earthed 230V - 50 Hz supply and
must be in accordance with current I.E.E. It must also be
possible to be able to completely isolate the appliance

electrically. Connection should be via a 3 amp fused double-

pole isolating switch with contact separation of at least 3 mm
on both poles. Alternatively, a fused 3 Amp. 3 pin plug and
unswitched socket may be used, provided it is not used in a
room containing a bath or shower. It should only supply the
appliance.

The boiler is suitable for sealed systems only. The maximum
working pressure for the appliance is 10 bar. All fittings and
pipework connected to the appliance should be of the same
standard. If there is a possibility of the incoming mains
pressure exceeding 10 bar, particularly at night, then a
suitable pressure limiting valve must be fitted.
The boiler is designed to provide hot water on demand to
multiple outlets within the property. If there is a requirement
for greater demands, for example if the property has several
bathrooms and cloakrooms, a vented or unvented hot water
storage system may be used.

Showers
Any shower valves used with the appliance should be of a
thermostatic or pressure balanced type. Refer to the shower
manufacturer for performance guidance and suitability.

Flushing and Water Treatment
The performance of the appliance could be impaired by
system debris or the effects of corrosion. The system must
be flushed thoroughly to remove metal filings, solder,
machining oils and other fluxes and greases before
connecting the boiler. If it is an existing system, an
appropriate flushing and descaling agent should be used.
Refer to BS 7593 (1992) for guidance. For more information
on the use of corrosion inhibitors, flushing and descaling
agents, advice can be sought from the manufacturers of
water treatment products such as:

Betz Dearborn Ltd
Foundry Lane
Widnes
Cheshire
WA8 8UD
Tel: 0151 424 5351
Fernox Manufacturing
Britannica Works
Clavering
Essex
CB11 4QZ
Tel: 01799 550811

System Controls
The boiler is electrically controlled and is suitable for most
modern electronic time and temperature controls. The
addition of such external controls can be beneficial to the
efficient operation of the system. The boiler connections for
external controls are 24V and so only controls of 24V or that
have voltage free contacts should be used.

Fig. 7

A

B

G

H

J

C

L

M

N

K

I

D,E

F

Q

H

N

M

Q

Q

I

Installation Requirements

Summary of Contents for 24

Page 1: ...system 30 c Manufactures N Model Type Gas Council N 200905821037 31 Centora Green System 24 Nat 41 980 12 200906822037 31 Centora Green System 30 Nat 41 980 31 GB IE U n i t 3 A T h o r n t o n R o a...

Page 2: ...ors and windows to ventilate the room Shut the gas mains tap on the gas meter or the valve of the gas cylinder and call your Gas Supplier immediately If you are going away for a long period of time re...

Page 3: ...S 7671 and document IGE UP 7 In the Republic the Republic of Ireland the installation should be carried out in accordance with the following codes of practice I S 813 Domestic Gas Installation the fol...

Page 4: ...T FUNCTION 21 19 TECHNICAL DATA 22 This instruction booklet is especially designed for appliances installed in the The United Kingdom and The Republic of Ireland INTRODUCTION The CENTORA GREEN SYSTEM...

Page 5: ...at sensor 42 Silencer 1 2 3 4 5 6 8 11 12 13 14 35 30 24 34 1 INSTALLER S INSTRUCTIONS 7 Fig 1 Fig 3 15 21 10 9 Fig 2 33 36 31 32 19 18 23 16 29 24 Display 27 Setting key 28 Setting key 29 Central Hea...

Page 6: ...m The expansion vessel is pre charged to 0 7 bar 10 lb in 2 The vessel is suitable for systems up to 145 litres capacity For systems of greater capacity an additional expansion vessel will be required...

Page 7: ...ulphur level contained in the gas should comply with the europ an Standards which are maximum 150 mg m3 for a short period in a year average level of 30 mg m3 during one year Electrical Supply The app...

Page 8: ...e system should be carefully checked for leaks as frequent refilling could cause premature system corrosion or unnecessary scaling of the heat exchanger The pipe from the siphon 12 fig 1 should be con...

Page 9: ...of 5 mm If the flue is a side exit installation then calculate the position of the hole with a slope of 5 mm metre towards the boiler from the terminal The flue should rise up slightly to the terminal...

Page 10: ...rthing continuity DHW Open the main cold feed valve 40 Open all hot taps to purge DHW system Check for water soundness Check flow rate at the bath tap is set correctly see technical data Central Heati...

Page 11: ...available in C H mode Post Commissioning Ensure system pressure has been set correctly Set all parameters of the boilers as shown in chapter 9 ADJUSTMENTS AND SETTINGS Set boiler thermostat and contro...

Page 12: ...eter in a section Press on setting key key on the Left side to enter in modification mode The 2nd and 3rd digits are flashing Press on or on the Right side to select the correct value then press on Se...

Page 13: ...ersion of display PCB 0 10 to 99 Flue type 2 1 FF variable speed Room thermostat is calling for heat 3 0 no 3 1 yes Theoretical position of the 3 way valve 4 0 DHW 4 1 CH DHW flow temperature in Celsi...

Page 14: ...min 2 1 0 min 2 5 0 min Maximum Central Heating flow temperature 4 50 C 4 80 C CH anti cycling delay 8 0 0 min From 0 to 7 minutes by step of 0 5 min 8 0 5 min 8 2 5 min 8 5 0 min CH maximum output li...

Page 15: ...erature is displayed in celsius degrees The 3 dots indicate that the combustion rate control is ON at maximum output X X Switching off the combustion rate control mode press once press once press once...

Page 16: ...side times The display shows 906 which corresponds to the 18 kW which is the factory setting 9 section 9 06 18 kW press on setting key on the Left side one time the 2nd and 3rd digits flash together T...

Page 17: ...l Heating thermistor faulty open circuit 12 Central Heating thermistor faulty open circuit 18 Attempt to re light 20 Wiring problem 23 Fan speed too low 24 Fan control system defective 31 Communicatio...

Page 18: ...nge indicator Burner ON 35 Red indicator Lock out flame failure 36 Reset button 12 Connecting bracket Taps shown in Open position fig 21 37 Central heating flow isolating valve 39 Gas service tap 41 C...

Page 19: ...ing Press on key 29 the green indicator 30 will light and the display will show the Heating flow temperature Keys 31 and 32 allow to adjust the temperature required in the Central Heating system regar...

Page 20: ...and the burner will start 13 15 The manufacturer s guarantee is for 12 months from the date of purchase The guarantee is voidable if the appliance is not installed in accordance with the recommendati...

Page 21: ...system and rise up the system pressure chapter 8 Close the heating flow isolating valve Don t forget to open it again when you will start heating Gas Conversion Incorrect Operation Helpful suggestions...

Page 22: ...0 87 m3 h 31 ft3 h 1 m3 h 35 ft3 h Gas valve restrictor diameter without without Propane L P G G31 Gas rate C H max 1 94 kg h 36 ft3 h 2 21 kg h 41 ft3 h Gas rate C H mini 0 64 kg h 12 ft3 h 0 73 kg h...

Page 23: ...23 U n i t 3 A T h o r n t o n R o a d I n d E s t a t e O f f H o c k n e y R o a d B r a d f o r d B D 8 9 H Q 0 1 2 7 4 4 8 8 3 8 8 w w w h e a t i n g s p a r e s 2 4 7 c o m...

Page 24: ...ited MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone 01494 755600 Fax 01494 459775 Internet www chaffoteaux co uk E mail info uk mtsgroup com Technical Support Help Line 0870 241 8...

Reviews: