background image

  | 

EN-Rev IM/GN-BM-EU/1.93 Copyright ©  August, 2021. CSI Solar Co., Ltd.

 

www.csisolar.com

 

frame  is  connected  to  the  bracket  or  where  the 
grounding is connected. Should the installation location 
be  near  the  ocean,  Canadian  solar  recommends 
stainless  steel  or  aluminum  materials  be  used  in  the 
areas with direct contact with the PV modules, and the 
connection  point  should  be  protected  with  anti-
corrosion  measures.  For  more  information,  please 
contact Canadian solar technical support team. 

 

CS7L-MB-AG & CS7N-MB-AG modules shall not be used 
in any rooftop application. 

INSTALLATION REQUIREMENTS   

 

Ensure  that  the  module  meets  the  general  technical 
system requirements. 

 

Ensure that other systems components do not damage 
the module mechanically or electrically. 

 

Modules can be wired in series to increase voltage or in 
parallel  to  increase  current.  To  connect  modules  in 
series, connect the cables from the positive terminal of 
one module to the negative terminal of the next module. 
To  connect  in  parallel,  connect  the  cables  from  the 
positive terminal of one module to the positive terminal 
on the next module. 

 

The quantity of bypass diodes in the module’s junction 
box provided may vary depending on the model series. 

 

Only connect the quantity of modules that corresponds 
to the voltage specifications of the inverters used in the 
system.  In  addition,  modules  must  not  be  connected 
together to create a voltage higher than the maximum 
permitted  system  voltage  stated  on  the  module 
nameplate,  even  under  the  worst  local  temperature 
conditions  (see  Table  1  for  the  correction  coefficients 
that apply to open-circuit voltage).     

 

A maximum of two strings can be connected in parallel 
without using an over-current protection device (fuses, 
etc.) incorporated in series within each string. Three or 
more  strings  can  be  connected  in  parallel  if  an 
appropriate  and  certified  over-current  protection 
device  is  installed  in  series  within  each  string.  And  it 
shall  be  ensured  in  the  PV  system  design  that  the 
reverse current of any particular string is lower than the 
module maximum fuse rating at any circumstances. 

 

Only modules with similar electrical parameters should 
be connected in the same string to avoid or minimize 
mismatch effects in arrays. 

 

To  minimize  risk  in  the  event  of  an  indirect  lightning 
strike,  avoid  forming  loops  with  the  wiring  when 
designing the system. 

 

The  recommended  maximum  series  fuse  rating  is 
stated in a table in the Annex A. 

 

Modules  should  be  safely  fixed  to  bear  all  expected 
loads, including wind and snow loads.   

 

After the installation of double glass modules, a 30 mm 
deflection for framed module is allowed. 

 

For framed modules, a minimum clearance of 6.5 mm 
(0.25 in) between modules is required to allow thermal 
expansion of the frames and modules. 

OPTIMUM ORIENTATION AND TILT 

 

To  maximize  the  annual  yield,  please  calculate  the 
optimum  orientation  and  tilt  for  PV  modules  in  that 
specific installation site. The highest yields are achieved 
when  sunlight  shines  perpendicularly  onto  the  PV 
modules. 

AVOID SHADING 

 

Even  minor  partial  shading  (e.g.  from  dirt  deposits) 
reduces  yields.  A  module  can  be  considered  to  be 
unshaded if its entire surface is free from shading all 
year round. Sunlight should be able to reach at least the 
module even on the shortest day of the year. 

 

For optimizing the power generation of the rear side of 
bifacial modules, obstacles between modules and the 
mounting  ground  should  be  avoided  as  much  as 
possible 

 

Constant shading conditions can affect module service 
lifetime, due to accelerated ageing of the encapsulation 
material and thermal stress on the bypass diodes.   

RELIABLE VENTILATION 

 

Bifacial  modules  use  direct,  reflected,  or  diffuse 
sunlight on the backside to generate additional power. 
Therefore,  bifacial  modules  are  not  suggested  to  be 
used in building attached photovoltaic systems (BAPV). 

Summary of Contents for CS3W-PB-AG Series

Page 1: ...For professional use only INSTALLATION MANUAL OF DOUBLE GLASS MODULE...

Page 2: ...NICAL ELECTRICAL SPECIFICATIONS 4 4 0 UNPACKING AND STORAGE 5 5 0 MODULE INSTALLATION 6 5 1 MODULE WIRING 9 5 2 GROUNDING 11 6 0 MOUNTING INSTRUCTIONS 12 6 1 MOUNTING METHODS BOLTING 13 6 2 MOUNTING M...

Page 3: ...on a regular basis 1 2 LIMITATION OF LIABILITY Canadian Solar shall not be held responsible for damages of any kind including without limitation bodily harm injury or damage to property in connection...

Page 4: ...tration above 0 1 weight by weight The copper ribbons used in our solar modules to interconnect solar cells use a thin solder coating layer that contains lead CAS no 7439 92 1 Under normal or reasonab...

Page 5: ...ghest 3 hour current average resulting from the simulated local simultaneous irradiances on the front and rear sides of the PV array accounting for elevation and orientation IscSTC the listed short ci...

Page 6: ...ing of modules should be limited to no more than 12 modules and frames should be aligned with one another on the pile Do not place excessive loads on the module or twist the module Do not carry module...

Page 7: ...nsidered acceptable for use with Canadian Solar modules provides the mounting system does not violate any other requirements of this manual Any mounting system limitations on inclination or accessorie...

Page 8: ...lel if an appropriate and certified over current protection device is installed in series within each string And it shall be ensured in the PV system design that the reverse current of any particular...

Page 9: ...e the connectors For double glass modules Canadian Solar offers several cable length options to match various system configurations which are shown in table 2 On below figures bold lines represent cab...

Page 10: ...umper cable CS6R Cable length 410 mm 290 mm 1500 mm jumper cable CS6RA Cable length 410 mm 290 mm 1100 mm jumper cable Note Modules in adjacent rows need to be rotated 180 degrees for proper installat...

Page 11: ...lations i e NEC 690 8 D CABLE AND CONNECTOR PROTECTION Secure the cables to the mounting system using UV resistant cable ties Protect exposed cables from damage by taking appropriate precautions e g p...

Page 12: ...y with all applicable local codes and requirements from all relevant authorities The loads described in this manual correspond to test loads For installations complying with UL 61730 and IEC 61215 2 2...

Page 13: ...be M8 with outer diameter 16 mm The yield strength of bolt and nut should not be less than 450MPa Suitable bolt length should be chosen based on actual module frame height For bifacial module with 30...

Page 14: ...lation method B Installation Method Module Types Inner four holes installation method A Inner four holes installation method B Middle four holes installation method A Middle four holes installation me...

Page 15: ...ounting rails shall be designed to limit as much as possible shade on module rear side cells Canadian Solar s warranty may be void in cases where improper clamps or unsuitable installation methods are...

Page 16: ...Max Mechanical Load Pa 3600 2400 5400 2400 5400 3600 A Range mm CS3W 410 490 CS3Y 300 600 400 550 CS6R 400 550 450 500 CS6RA 300 450 350 400 CS6W 300 600 400 500 CS7N CS7L 400 500 6 2 2 Clamp mountin...

Page 17: ...he long side frame Module Types Max Mechanical Load Pa 3600 2400 3800 3200 4000 3200 4400 3200 4400 3600 A1 Range mm CS3W 410 490 CS3Y 400 550 CS6W 400 500 CS6RA 300 400 CS7N CS7L CS6R 400 500 6 2 4 F...

Page 18: ...opyright August 2021 CSI Solar Co Ltd www csisolar com 6 2 5 Six clamps on long side of frame and rails perpendicularly to the long side frame Module Types Max Mechanical Load Pa 6000 3600 A3 A5 Range...

Page 19: ...r design of support structure Canadian Solar warranty may be void in cases where improper insertion systems or unsuitable installation methods are found When installing insertion profiles please take...

Page 20: ...ethod Install and tighten the module clamps to the mounting rails using the torque stated by the mounting hardware manufacturer M6 X 1 1 4 bolt and nut are used for this bolting method Tightening torq...

Page 21: ...600 CS7N MB AG 400 40 1500 1500 Tracker 2P Bolting method Module type Mounting hole space mm Mounting hole location Plain washer outer diameter mm Test load Pa CS3W PB AG CS3W MB AG A1 A3 400 B1 B3 11...

Page 22: ...potential electric shock hazard Cracked or broken modules represent an electric shock hazard due to leakage currents and the risk of shock is increased when modules are wet Before cleaning thoroughly...

Page 23: ...ith low mineral content Near neutral pH water The maximum water pressure recommended is 4 MPa 40 bar CLEANING METHODS Method A Compressed Air Canadian Solar recommends cleaning the soft dirt like dust...

Page 24: ...0PB AG 410 39 1 10 49 47 6 11 06 25 CS3W 415PB AG 415 39 3 10 56 47 8 11 14 25 CS3W 420PB AG 420 39 5 10 64 48 0 11 26 25 CS3W 425PB AG 425 39 7 10 71 48 2 11 29 25 CS3W 430PB AG 430 39 9 10 78 48 4 1...

Page 25: ...A 320H AG 320 26 4 12 20 31 2 13 00 26 4 CS6RA 325H AG 325 26 6 12 26 31 4 13 09 26 6 CS6RA 330H AG 330 26 8 12 32 31 6 13 15 26 8 CS6RA 335H AG 335 27 1 12 38 31 9 13 21 27 1 CS6R 405H AG 405 33 5 12...

Page 26: ...15 41 1 18 42 35 CS7L 600MB AG 600 34 9 17 20 41 3 18 47 35 CS7L 605MB AG 605 35 1 17 25 41 5 18 52 35 CS7L 610MB AG 610 35 3 17 29 41 7 18 57 35 CS7N 630MB AG 630 37 1 16 99 44 2 18 23 35 2384 x 130...

Page 27: ...aken on hourly basis or even more frequently For a standard year the 98th percentile temperature would be met or exceeded 175 2 hours The operational module temperature is influenced by the environmen...

Page 28: ...ember 2019 Rev 1 4 is released in December 2019 Rev 1 5 is released in April 2020 Rev 1 6 is released in May 2020 Rev 1 7 is released in December 2020 Rev 1 71 is released in December 2020 Rev 1 8 is...

Reviews: