Slave Boiler
Description
Electrical Connection(s)
Programming Instructions
•
Slave boiler lead lag setup
1)
Place toggle switch to
LOCAL
2)
Press
and
3)
Select
System Identification & Access
4)
Verify
Modbus address
. To be in sequential order
5)
Select
Lead Lag Slave Configuration
6)
Select
Slave Enabled = Enable slave for built-in Lead Lag master
The following steps are performed at the factory and verifying on site
will be sufficient:
7)
Select
Pump Configuration
8)
Press
[Advanced Options >>]
9)
Press the to arrive at
Central Heat Pump
or
DHW Pump
10)
On Options: Local burner demand
11)
On Options: Local Lead Lag Service Active
12)
Force On: Outlet high limit