Modulation: Boiler Inlet, Outdoor Reset Operation (Standalone)
Description
Electrical Connection(s)
Programming Instructions
•
Boiler operates with variable
setpoint determined by
outdoor reset curve
•
Modulates on inlet sensor
(default)
•
Heat demand is generated
when Remote Operator is
closed.
1)
Connect outdoor sensor to System/Outdoor contacts
2)
Press
and
3)
Press
Outdoor Reset Configuration
4)
Select
Enable: Enable
5)
Select
Maximum outdoor temperature
(WWSD)
6)
Select
Minimum outdoor temperature
(Outdoor
Design)
7)
Select
Low Water Temperature
(Min. Water Temp.)
8)
Select
Outdoor boost maximum off point
(Design
Max.)
9)
Press
[CH – Central Heat Configuration]
10)
Press
Sensor Configuration
11)
Select
S5 (J8-11) Sensor
12)
Select
Connector Type: 10K NTC Single Non-Safety
13)
Outdoor temperature source = S5 (J8-11) sensor
14)
The control will proceed into a Lockout 2 condition
15)
Press
[Verify]
>
[Begin]
>
[Yes]
16)
Press the reset button on the ignition control within
the alotted time
17)
Place toggle switch to
REMOTE
for remote operation
(if required)
Modulation: System Sensor, Outdoor Reset Operation (Standalone)
Summary of Contents for Dynaforce Series
Page 2: ...99 0171 REV 0 9...
Page 35: ...35...
Page 48: ...48...
Page 67: ...67 PART 12 EXPLODED VIEW 19 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 20...
Page 68: ...68 21 22 23 24 26 35 34 33 32 31 30 29 28 27 25 36 37 38 39 40 42 43 56...
Page 75: ...75 PART 13 ELECTRICAL DIAGRAMS...
Page 76: ...76...
Page 77: ...77...
Page 78: ...78...
Page 79: ...79...