Manual und Technical Details 

 

Analog Interface CON1 (Connector Model Weidmueller 1277320000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

AC OK-1 

Output 

Closers, Signal AC OK 

Relay 

Potential-free 

DC OK-1 

Output

 

Closers, Signal DC OK

 

Relay

 

Potential-free

 

AC OK-2 

Output

 

Center, Signal AC OK

 

Relay

 

Potential-free

 

DC OK-2 

Output

 

Center, Signal DC OK

 

Relay

 

Potential-free

 

AC OK-3 

Output

 

Break, Signal AC OK

 

Relay

 

Potential-free

 

DC OK-3 

Output

 

Break, Signal DC OK

 

Relay

 

Potential-free

 

NC 

NC 

Not Connected

 

 

No Function 

SD 

Input 

Control Signal Shutdown 

Switch / Open Collector 

 

DGND 

Digital Ground 

 

10 

NC 

NC 

Not Connected

 

 

No Function 

11 

DGND 

Digital Ground 

 

12 

INH 

Input 

Control Signal Inhibit (Interlock) 

Switch 

 

Analog Interface CON2 (Connector Model Weidmueller 1277330000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

DGND 

Digital Ground 

 

NC 

NC 

Not Connected

 

 

No Function 

DGND 

Digital Ground

 

 

NC 

NC

 

Not Connected

 

 

No Function 

NC 

NC 

Not Connected

 

 

No Function 

NC 

NC 

Not Connected

 

 

No Function 

FF 

Output

 

Signal Fan Failure

 

Open Collector 

 

NC 

NC 

Not Connected

 

 

No Function 

OT 

Output

 

Signal Over Temperature 

Open Collector 

 

10 

NC 

NC 

Not Connected

 

 

No Function 

11 

NC 

NC 

Not Connected

 

 

No Function 

12 

NC 

NC 

Not Connected

 

 

No Function 

13 

NC 

NC 

Not Connected

 

 

No Function 

14 

NC 

NC 

Not Connected

 

 

No Function 

Analog Interface CON3 (Connector Model Weidmueller 1277340000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

AGND 

Analog Ground 

 

Imon 

Output

 

Current Monitor

 

0-5Vdc / 5mA 

 

NC 

NC

 

Not Connected

 

 

No Function 

NC 

NC 

Not Connected

 

 

No Function 

CS 

I/O

 

Current Share Bus (CSB)

 

Parallel Operation 

Bidirectional 

NC 

NC 

Not Connected

 

 

No Function 

AGND 

-

 

Analog Ground

 

 

NC 

NC 

Not Connected

 

 

No Function 

AGND 

-

 

Analog Ground

 

 

10*

 

NC 

NC 

Not Connected

 

 

No Function 

11 

NC 

NC 

Not Connected

 

 

No Function 

12*

 

NC 

NC 

Not Connected

 

 

No Function 

13 

CS 

I/O

 

Current Share Bus (CSB) 

Parallel Operation 

Bidirectional

 

14 

NC 

NC 

Not Connected

 

 

No Function 

15 

AGND 

-

 

Analog Ground 

 

16 

NC 

NC 

Not Connected

 

 

No Function 

Analoge Interface CON4 (Connector Model Weidmueller 1277290000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

Sense - 

Input 

Sense Connection 

2V / load line 
 

Sense - 

Input 

Sense Connection

 

-

 

3, 4 

 

 

NC 

Must not be connected

 

5, 6 

 

 

NC 

Sense + 

Input

 

Sense Connection

 

-

 

2V / load line 
 

Sense + 

Input

 

Sense Connection

 

-

 

 
 
 

Summary of Contents for CPS-EP2000

Page 1: ...positions PFC 0 99 Features 3D Heat Dissipation CSB Current Share Bus Inhibit for safe interlocking Remote Shutdown Sense mode Current Monitoring 0 5V Power Good Relay DC ok Precise dynamics on load...

Page 2: ...ns call for the highest standards of safety and interference suppression The device was developed in accordance with the requirements of EN61010 1 EN61010 2 201 EN62368 1 and the EMC standards EN55032...

Page 3: ...witching contacts Inhibit Mode Interlock The inhibit circuit reliably prevents unintentional starting of the power supply The control loop is internally locked Since this blocking is done progressivel...

Page 4: ...l shutdown autorecovery 70 C outside measuring point distance 10mm Hold Up Time 30ms 230Vac mains buffering at full load Inrush Current 14 6Aeff 20 7Apeak 230Vac active electronic inrush protection no...

Page 5: ...nnected No Function 3 DGND Digital Ground 4 NC NC Not Connected No Function 5 NC NC Not Connected No Function 6 NC NC Not Connected No Function 7 FF Output Signal Fan Failure Open Collector 8 NC NC No...

Page 6: ...01 1 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherei...

Page 7: ...ercon powercon 20 a nac3fca CON1 Push In 0 14 1 5mm AWG26 16 CON2 CON3 CON4 DC M8 200A 60 C 250Vac 20A Neutrik PowerCon 3x2 5 mm Neutrik NAC3FCA Interface pluggable Push Pull Connectors from Weidmuell...

Page 8: ...rop over long load lines The compensation amounts to a maximum of 2V per load line Under certain circumstances it can be expected to apply more complicated external interference suppression If sense i...

Page 9: ...the participating power supplies is important To prevent one of the power supplies going early into the current limitation and display error message An uneven load and thus premature aging of the part...

Page 10: ...orced Isolation of max 400Vdc and a basic isolation of max 600Vdc working voltage DC OK Relay DC Power Good The signal DC OK has potential free relay contacts changeover The contacts of CON1 Pin2 and...

Page 11: ...ues to protect the unit from operating under overload conditions also see OT thermal SD Model Value UA1 V Value IA1 A Value UA2 V Value IA2 A Pmax IA1 IA2 CPS EP2000 024 30Vdc 66 7A 24Vdc 84A 2001 201...

Page 12: ...licable to EN62368 1 Due to the dielectric strength of the internal components used only the models with an output voltage of 48Vdc and later are approved for series operation Other power supplies are...

Page 13: ...Germany P 13 19 01 2018 01 1 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as lif...

Page 14: ...al Safety Factory Test Field Test Owner 48Vdc 2800Vdc Type and factory test are the manufacturer While repating damage can happen to the power supply unit For the field test owner follow the below ins...

Page 15: ...esult in injury or death Mechanics Aluminium housing IP20 Cooling is achieved via front to rear fans To ensure adequate heat dissipation 50mm to the front and 150mm blockade free distance from the dev...

Page 16: ...w camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in inju...

Page 17: ...o custom design power supplies Steplessly hard mount of the CPS EP2000 3000 power supply modules in a 3D room In practice that means that one can mount the modules into every angle imaginable Our 3D H...

Page 18: ...on Article Number CPS EP2000 024 R2 24Vdc model incl analogue interface 3041101002CA CPS EP2000 036 R2 36Vdc model incl analogue interface 3041101003CA CPS EP2000 048 R2 48Vdc model incl analogue inte...

Page 19: ...olts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to per...

Reviews: