Over Load Behaviour 

The CPS-EP changes from the standard operation mode into the high current mode when high and quick 
overload occurs. Thus, it provokes a restart after a 30ms break and delivers continuous current to the output. 
This special behaviour is a protection for the power supply and for the connected load. 

 

Inhibit / Interlock (INH) 

The power supply is equipped with a control input Inhibit (INH) 
to interlock a DC-shutdown of the power supply. 
 
For the nominal operation of the power supply the connections 
of the control input "INH" must always be short-circuited. 
The power output is switched off as soon as the connection 
between the contacts of the control input INH is interrupted. 
If Inhibit is repealed, the power supply starts with a delay of 
35ms. Using the softstart the current and the voltage rises 
within 100ms continuously to the default set values. Between 
the INH contacts applies a current of typical 2mA. 
 
 
 

! Warning against damage in case of incorrect connection assignment

 

Never apply any external voltage to the control input INH. Never connect a resistor to the INH interface. The 
INH can only be connected to a floating contact (e.g., mechanical switch or relay). Between control input INH 
and power output is a reinforced Isolation of max. 400Vdc and a basic isolation of max. 600Vdc working 
voltage. 

 

DC-OK Relay (DC Power Good) 

The signal DC OK has potential-free relay contacts (changeover). The contacts of CON1 Pin2 and CON1 Pin4 
are closed (relay coil is energized) when the power operates as a connstant voltage source. The contacts 
CON1 Pin2 and CON1 Pin4 are open when the power output is inhibited by SD, INH, OT, FF, OVP, OCP or a 
defective PFC. Contact load (resistive load): 30Vdc/1A, 60Vdc/0.3A, 30Vac/0.5A. Betwenn the intermediate 
relay contact and the power output is a reinforced Isolation of max. 400Vdc and a basic isolation of max. 
600Vdc working voltage. 

 

AC-OK Relay (AC Power Good) 

The Power Good relay reports whether the input voltage is too low or missing. The notification signal AC OK is 
generated with potential-free relay contacts (changeover). 
The contacts of CON1 Pin1 and CON1 Pin3 are closed (relay coil is energized) when the input voltage is higher 
than typ. 175Vac or 210Vdc (switch-on). The contacts of CON1 Pin5 and CON1 Pin3 are closed (relay coil is 
not energized) when the input voltage is lower than typical 165Vac or 145Vdc (turn-off). Contact load (resistive 
load): 30Vdc/1A, 60Vdc/0.3A, 30Vac/0.5A.  
Between the relay contacts and the power output is a reinforced isolation of max. 400Vdc and a basic isolation 
of max. 600Vdc working voltage. 

 

Over Voltage Protection Signaling (OVP) 

If an over-voltage occurs to the output (for example, defective components, external feed voltage), it is followed 
by the shutdown of the power output. A periodic restart attempts (ticker operation period 1s). The LED OVP 
lights red. 

 

Over Temperature Shutdown (OT) 

The alarm signal OT is high when the temperature of the power supply is higher than the over-temperature 
protection threshold. Output Open Collector I

MAX

=10mA, V

LOW

0,6V, V

MAX

=30V. 

 
 

 

Summary of Contents for CPS-EP2000

Page 1: ...positions PFC 0 99 Features 3D Heat Dissipation CSB Current Share Bus Inhibit for safe interlocking Remote Shutdown Sense mode Current Monitoring 0 5V Power Good Relay DC ok Precise dynamics on load...

Page 2: ...ns call for the highest standards of safety and interference suppression The device was developed in accordance with the requirements of EN61010 1 EN61010 2 201 EN62368 1 and the EMC standards EN55032...

Page 3: ...witching contacts Inhibit Mode Interlock The inhibit circuit reliably prevents unintentional starting of the power supply The control loop is internally locked Since this blocking is done progressivel...

Page 4: ...l shutdown autorecovery 70 C outside measuring point distance 10mm Hold Up Time 30ms 230Vac mains buffering at full load Inrush Current 14 6Aeff 20 7Apeak 230Vac active electronic inrush protection no...

Page 5: ...nnected No Function 3 DGND Digital Ground 4 NC NC Not Connected No Function 5 NC NC Not Connected No Function 6 NC NC Not Connected No Function 7 FF Output Signal Fan Failure Open Collector 8 NC NC No...

Page 6: ...01 1 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherei...

Page 7: ...ercon powercon 20 a nac3fca CON1 Push In 0 14 1 5mm AWG26 16 CON2 CON3 CON4 DC M8 200A 60 C 250Vac 20A Neutrik PowerCon 3x2 5 mm Neutrik NAC3FCA Interface pluggable Push Pull Connectors from Weidmuell...

Page 8: ...rop over long load lines The compensation amounts to a maximum of 2V per load line Under certain circumstances it can be expected to apply more complicated external interference suppression If sense i...

Page 9: ...the participating power supplies is important To prevent one of the power supplies going early into the current limitation and display error message An uneven load and thus premature aging of the part...

Page 10: ...orced Isolation of max 400Vdc and a basic isolation of max 600Vdc working voltage DC OK Relay DC Power Good The signal DC OK has potential free relay contacts changeover The contacts of CON1 Pin2 and...

Page 11: ...ues to protect the unit from operating under overload conditions also see OT thermal SD Model Value UA1 V Value IA1 A Value UA2 V Value IA2 A Pmax IA1 IA2 CPS EP2000 024 30Vdc 66 7A 24Vdc 84A 2001 201...

Page 12: ...licable to EN62368 1 Due to the dielectric strength of the internal components used only the models with an output voltage of 48Vdc and later are approved for series operation Other power supplies are...

Page 13: ...Germany P 13 19 01 2018 01 1 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as lif...

Page 14: ...al Safety Factory Test Field Test Owner 48Vdc 2800Vdc Type and factory test are the manufacturer While repating damage can happen to the power supply unit For the field test owner follow the below ins...

Page 15: ...esult in injury or death Mechanics Aluminium housing IP20 Cooling is achieved via front to rear fans To ensure adequate heat dissipation 50mm to the front and 150mm blockade free distance from the dev...

Page 16: ...w camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in inju...

Page 17: ...o custom design power supplies Steplessly hard mount of the CPS EP2000 3000 power supply modules in a 3D room In practice that means that one can mount the modules into every angle imaginable Our 3D H...

Page 18: ...on Article Number CPS EP2000 024 R2 24Vdc model incl analogue interface 3041101002CA CPS EP2000 036 R2 36Vdc model incl analogue interface 3041101003CA CPS EP2000 048 R2 48Vdc model incl analogue inte...

Page 19: ...olts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to per...

Reviews: