Technical Data Table 

AC Input Range 

184 – 264Vac 

AC Input Frequency 

47 – 63Hz 

DC Input Range 

250 – 375Vdc 

AC Input Rated 

230Vac <10,0A 

DC Input Rated 

250Vdc <9,3A  375Vdc <6,2A 

DC Voltage Rated 

24Vdc 

36Vdc 

48Vdc 

72Vdc 

110Vdc 

DC Voltage Setting Range 

24 - 30Vdc 

30 - 45Vdc 

45 - 58Vdc 

58 - 90Vdc 

90 - 150Vdc 

DC Current Rated 

84A 

56A 

42A 

28A 

18,2A 

Over Voltage Protection 

35Vdc 

52,5Vdc 

68Vdc 

105Vdc 

175Vdc 

Over Current Protection 

85,7A 

57,1A 

42,8A 

28,6A 

18,6A 

Ripple Noise 230Vac 20MHz  35mVpp 

35mVpp 

75mVpp 

100mVpp 

200mVpp 

Power Rated 

2000W, 184-264Vac 

Cooling 

Continuously controlled and monitored fans from EBM Papst (Germany) 

Efficiency 

typ. 92-94% 230Vac at full load  

Power Factor Control (PFC)  0,99 / 230Vac full load 
Short Circuit Resistance 

yes 

Open Circuit Protected 

yes 

Base Load (OCP) 

Non required (open circuit protected) 

Load Regulation 

< ± 0,05% 0-100% 

Load Regulation Time 

<1ms on load switch 10-100% 

Accuracy Imon 

 ± 1% 

Temperature Control 

yes, thermal shutdown & autorecovery (+70°C, outside measuring point distance 10mm) 

Hold Up Time 

>30ms 230Vac

 

mains buffering at full load 

Inrush Current 

<14,6Aeff <20,7Apeak 230Vac active electronic inrush protection (no simple NTC) 

Startup Delay 

typ. 1s 

Softstart 

typ. 100ms 

Ambient Temperature 

- 20°C…+60°C operating, derating 2,5%/°C >50°C 

Storage Temperature 

- 40°C…+85°C 

Ambient Conditions 

Humidity 95% non-condensing @ 25°C, climate class 3K3, pollution degree 2 

ROHS 

2011/65/EU, (EU) 2015/863 conform 

REACH 

EG No. 1907/2006 conform 

EMI 

EN55032, conducted .024/.036/.048 class B / .072/.110 class A, all models radiated class A 

EMS/EMI 

EN61000-6-2,3,4 

Safety 

EN61010-1, EN61010-2-201, EN62368-1, EN60950-1, EN60204-1 

Protection Class I 

PE connection required 

Leakage Current 

Typical 1.9mA, <2.8mA, 230Vac 50Hz 

Isolation Input to Output 

3000Vac 

Isolation Input to Case 

2500Vac 

Isolation Output to Case 

500Vdc , 

48Vdc= 2800Vdc 

MTBF (IEC61709) 

419000h (Meantime Between Failures: statistic time between failures after repairs) 

MTTF (IEC61709) 

146105h (Meantime To Failure: statistic time to ever fails) 

Dimensions (HxWxD) 

84x126,4x444mm | 3,3x5x17,5 Inch (without frontplate, note cable outlet in planning) 

Weight 

4,4kg / 9,7lbs 

Input Power Connections 

Neutrik NAC3FCA (locked by bajonett) included 

Output Power Connections 

Brass-Powerbars with metric M8 thread, a touch protection is included 

 

Output Ratings 

Model

 

24Vdc

 

36Vdc

 

48Vdc

 

72Vdc

 

110Vdc 

Slew Rate 90-10%, 10/100% Load, [ms] typ. 

70/7,0

 

30/3.0

 

46/4,6

 

35/3,5

 

47/4,7

 

Output Capacity, [mF] typ. 

19,4

 

3,74

 

3,4

 

1,07

 

0,52

 

 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for CPS-EP2000

Page 1: ...positions PFC 0 99 Features 3D Heat Dissipation CSB Current Share Bus Inhibit for safe interlocking Remote Shutdown Sense mode Current Monitoring 0 5V Power Good Relay DC ok Precise dynamics on load...

Page 2: ...ns call for the highest standards of safety and interference suppression The device was developed in accordance with the requirements of EN61010 1 EN61010 2 201 EN62368 1 and the EMC standards EN55032...

Page 3: ...witching contacts Inhibit Mode Interlock The inhibit circuit reliably prevents unintentional starting of the power supply The control loop is internally locked Since this blocking is done progressivel...

Page 4: ...l shutdown autorecovery 70 C outside measuring point distance 10mm Hold Up Time 30ms 230Vac mains buffering at full load Inrush Current 14 6Aeff 20 7Apeak 230Vac active electronic inrush protection no...

Page 5: ...nnected No Function 3 DGND Digital Ground 4 NC NC Not Connected No Function 5 NC NC Not Connected No Function 6 NC NC Not Connected No Function 7 FF Output Signal Fan Failure Open Collector 8 NC NC No...

Page 6: ...01 1 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherei...

Page 7: ...ercon powercon 20 a nac3fca CON1 Push In 0 14 1 5mm AWG26 16 CON2 CON3 CON4 DC M8 200A 60 C 250Vac 20A Neutrik PowerCon 3x2 5 mm Neutrik NAC3FCA Interface pluggable Push Pull Connectors from Weidmuell...

Page 8: ...rop over long load lines The compensation amounts to a maximum of 2V per load line Under certain circumstances it can be expected to apply more complicated external interference suppression If sense i...

Page 9: ...the participating power supplies is important To prevent one of the power supplies going early into the current limitation and display error message An uneven load and thus premature aging of the part...

Page 10: ...orced Isolation of max 400Vdc and a basic isolation of max 600Vdc working voltage DC OK Relay DC Power Good The signal DC OK has potential free relay contacts changeover The contacts of CON1 Pin2 and...

Page 11: ...ues to protect the unit from operating under overload conditions also see OT thermal SD Model Value UA1 V Value IA1 A Value UA2 V Value IA2 A Pmax IA1 IA2 CPS EP2000 024 30Vdc 66 7A 24Vdc 84A 2001 201...

Page 12: ...licable to EN62368 1 Due to the dielectric strength of the internal components used only the models with an output voltage of 48Vdc and later are approved for series operation Other power supplies are...

Page 13: ...Germany P 13 19 01 2018 01 1 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as lif...

Page 14: ...al Safety Factory Test Field Test Owner 48Vdc 2800Vdc Type and factory test are the manufacturer While repating damage can happen to the power supply unit For the field test owner follow the below ins...

Page 15: ...esult in injury or death Mechanics Aluminium housing IP20 Cooling is achieved via front to rear fans To ensure adequate heat dissipation 50mm to the front and 150mm blockade free distance from the dev...

Page 16: ...w camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in inju...

Page 17: ...o custom design power supplies Steplessly hard mount of the CPS EP2000 3000 power supply modules in a 3D room In practice that means that one can mount the modules into every angle imaginable Our 3D H...

Page 18: ...on Article Number CPS EP2000 024 R2 24Vdc model incl analogue interface 3041101002CA CPS EP2000 036 R2 36Vdc model incl analogue interface 3041101003CA CPS EP2000 048 R2 48Vdc model incl analogue inte...

Page 19: ...olts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to per...

Reviews: