background image

 

 

   

CPS-EC1000(R2) MANUAL

                 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  76327 Pfinztal  -  Germany      

P.3/12 (03.2022.00.0)

 

Phone +49(721)46596-0  -   Fax +49(721)46596-77  -   

www.camtec-gmbh.com

 - 

[email protected]

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 

Technical Data Table 

AC Input Range 

90 – 132Vac / 184 – 264Vac , 47 – 63Hz  (115/230Vac input selector, factory setting is 230Vac) 

DC Input Range 

250Vdc – 375Vdc (input selector set to 230Vac) 

AC Input Rated 

115Vac<17,2A  230Vac<9,8A 

DC Input Rated 

250Vdc<5,0A  375Vdc<3,3A (input selector set to 230Vac rated) 

Rated DC Voltage 

24Vdc 

36Vdc 

48Vdc 

60Vdc 

72Vdc 

110Vdc 

150Vdc 

220Vdc 

300Vdc 

Rated DC Current 

42A 

28A 

21A 

16,7A 

13,9A 

9,1A 

6,7A 

4,55A 

3,33A 

DC Voltage Setting Range 

24 – 
30Vdc 

36 – 
45Vdc 

48 – 
58Vdc 

60 – 
75Vdc 

72 – 
90Vdc 

110 – 
137,5Vdc 

132 – 
180Vdc 

220 – 
264Vdc 

264 – 
360Vdc 

DC Current Setting Range 

21 –   
44,1A 

14 – 
29,4A 

10,5 –  
22A 

8,0 –    
17,6A 

7,0 –  
14,6A 

4,6 – 
9,6A 

3,4 – 
7,0A 

2,3 – 
4,8A 

1,7 – 
3,5A 

Over Voltage Protection 

34Vdc 

50Vdc 

67Vdc 

84Vdc 

100Vdc 

154Vdc 

210Vdc 

310Vdc 

420Vdc 

Over Current Protection 

44,1A 

29,4A 

22A 

17,6A 

14,6A 

9,6A 

7,0A 

4,8A 

3,5A 

Ripple Noise 230Vac 20MHz  40mV 

40mV 

100mV 

150mV 

200mV 

300mV 

400mV 

400mV 

400mV 

Power Rated 

1008W, 90-132Vac, 184-264Vac 

Potentiometer C/V Setting 

15 turns high precision, protective forced isolation to the inputs and the output 3000Vac 

Operation Failure Relay 

Yes, break contact, protective forced isolation to the inputs and the output 3000Vac 

Sense Function 

Compensation 1V per load line 

Remote Shutdown 

Yes, protective forced isolation to the inputs and the output 3000Vac 

Inhibit Function (Interlock) 

Yes, protective forced isolation to the inputs and the output 3000Vac 

Derating 

+60°C...+70°C 2.5%/°C 

Accuracy 

< ± 1.5% interface 

Load Regulation 

< ± 0.05% 0-100% 

Start up from Shutdown 

Typ. 320ms 

Start up from Inhibit 

Typ. 320ms 

Response to Load Change 

<1ms 10-100%, 100-10% 

Base Load 

None required (open circuit proof) 

Efficiency 230Vac 

Up to 92% at 90% load 

Short Circuit Protection 

Continuous 

Open Circuit Proof 

Continuous 

Temperature Control 

Yes, thermal shutdown with auto recovery (+70°C, metering distance 10mm) 

Hold Up Time 

>30ms 230Vac 

Inrush Current 

<9,8Aeff < 13.8Apeak (230Vac) active inrush current limiter 

Soft Start  

100ms typical 

Cooling 

Controlled Fan from manufacturer EBM Papst (Germany) 

Ambient Operating Temp. 

- 25°C…+70°C 

Ambient Storage Temp. 

- 40°C…+85°C 

Environment 

Humidity 95% non-condensing @ 25°C, climate class. 3k3, pollution rate II 

ROHS 

2011/65/EU, (EU)2015/863 

REACH 

EG No. 1907/2006 

EMI 

EN55032 conducted class B, radiated class A, EN61000-6-3 

EMS 

EN61000-6-2 

Safety 

EN61010-1, EN61010-2-201, EN62368-1 (not 300Vdc model), EN60950-1, EN60204-1    

Protection Class 1 

PE connection required 

Isolation Paths 

> 8mm creepage distance & clearance paths 

Input to Output Isolation 

3000Vac 

Input to Case Isolation 

2500Vac 

Output to Case Isolation 

500Vdc , models 

48Vdc 2500Vdc 

Meantime By Failure (MTBF)  389000h (IEC61709) 
Meantime To Failure (MTTF)  143034h (IEC61709) 
Dimensions (HxWxD) 

156x200x114.5mm 

Weight 

3400g 

AC Terminals  

Input Screw Terminal 3x AWG22 – AWG6 / 0,5 – 16mm² (L,N,PE) 

DC Terminals 

Output Screw Terminal 4x AWG22 – AWG6 / 0,5 – 16mm² (+ + / - - ) 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for CPS-EC1000

Page 1: ...1V per load line Electronic inrush current limiter 13 8Apeak Inhibit function Interlock External shutdown Efficiency up to 92 Precise dynamic response to load change Designed for long life under full...

Page 2: ...with a 15 turns high precision potentiometer The listed values are guaranteed by the factory The tolerance of the upper margin is 0 5 The tolerance of the lower margin is 5 0 Output Current Monitorin...

Page 3: ...to the inputs and the output 3000Vac Sense Function Compensation 1V per load line Remote Shutdown Yes protective forced isolation to the inputs and the output 3000Vac Inhibit Function Interlock Yes pr...

Page 4: ...put Sense Compensation 1V per load line AWG22 AWG6 0 25 2 5mm Sense Aux 3000Vac to input Power Good Relay b contact AWG22 AWG6 0 25 2 5mm DC OK 3000Vac to input output All potentiometers and all the i...

Page 5: ...ARNING Reverse polarity of the sense lines can cause damages to the power supply unit To basically prevent from interferences enable to twist sense compensation lines To reduce inductive influences ma...

Page 6: ...setting for DC input supply The below table of values shows the hysteresis of the lower and upper threshold margins where the DC OK Relay indicates a low voltage The nominal voltage of the cell voltag...

Page 7: ...48 21 0 1008W CPS EC1000 060 75 13 3 60 16 7 1008W CPS EC1000 072 90 11 1 72 13 9 1008W CPS EC1000 110 137 5 7 3 110 9 1 1008W CPS EC1000 150 180 5 6 150 6 7 1008W CPS EC1000 220 264 3 8 220 4 5 1008W...

Page 8: ...lies from each other To increase the power capability RED models can be connected in parallel For higher voltages an external decoupling diode shall be installed from the system engineer Coating Optio...

Page 9: ...in injury or death Mechanics Mechanics Stable metal aluminium housing IP20 To allow adequate convection a free air space of 50mm top bottom and 5mm sidewalls is required for active devices 15mm space...

Page 10: ...and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the CPS EC1000 One can use the DIN Rail installation equipped standard with our patented 35mm...

Page 11: ...46228 pt 1 min max 2 5 10mm 0 2 1 5mm Plug gauge in accordance with EN 60999 a x b 5 4 x 5 1mm 5 3mm 2 4 x 1 5mm 2 3mm Pitch P 10 16mm 3 5mm Wire Stripping Length fine wired Nominal Cross Section Wir...

Page 12: ...g bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to...

Reviews: