CPS-EX2000(R2) MANUAL 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  DE-76327  Pfinztal / Germany   

P.8/21 (07/2017.01.3) 

Tel. +49 (721) 46596 - 0  Fax +49 (721) 46596 - 77    

www.camtec-gmbh.com

   -   

[email protected]

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 

LED Operating Signal 

CV/OVP 

CV Constant Voltage Mode LED lights Green 
OVP Overvoltage maloperation or interference voltage LED lights Red 

CC/OCP 

CC Constant Current Mode LED lights Yellow 
OCP Over Current Protection LED flashes Red, also see >>Fuse Mode<< 

TA/OT 

TA Temperature Alarm LED lights Yellow, warning temperature shutdown pending 
OT Over Temperature Shutdown LED lights Red 

INH/FF 

INH Inhibit (Interlock) Shutdown LED lights Yellow 
FF Fan Failure LED lights Red 

SD/SB 

SD Shutdown LED lights Yellow 
SB Standby LED lights Red 

 

Configuration of the Current Share Bus (CS) and Over Current Protection 

Mode 

S11 

S12 

CS active 

 

CS non-active 

 

Fuse Mode 

 

Continuous Mode 

 

Warning!

 

CS (Current Share Mode) only applies when a current distribution must take place while parallel 

operation mode. In single or parallel operation without the need of CS, always switch CS with S11 to OFF=1. 
Factory set: CS non-active (S11=1), Continuous Mode (S12=1) 
Note that for DIGI3201 interface equipped unit settings will be made with the browser in the software. 

 

Programming/Monitoring V/C Analog Interface (Ureg-IN/Ireg-IN) (Umon/Imon) 

The standard programming of the CPS-EX Series is an analog interface. The output voltage is linearly 
proportional to the adjusted analog control signal.  
 
The monitor signal is analog linear to the output voltage. The monitor signal for current and voltage is the real 
value that is measured directly at the output of the power supply. If a sense line is connected to compensate for 
the voltage drop across the load lines, the monitor signal is exactly the value that is measured at the connection 
point of the sense line. The description of the power supply in the sense operation is carried out in a separate 
section. 
The analog inputs and outputs are non-floating. The mass is connected to the DC negative output. 
 
The burden of the control voltages is 1M

Ω

. The latency to full compensation of V/C on the interface from 0-

100% is 15ms for all CPS-EX models. 

 

Programming V/C via Potentiometer (Uadj/Iadj) – Stand Alone Operation 

The power supply is equipped with 2 potentiometers Uadj and Iadj for setting voltage and current.  
Connect each Uadj and Iadj of CON3 to the inputs Ureg-IN and Ireg-IN. If one of the two potentiometers is not 
used, the other value can still be programmed via the interface. In such case, only the control signal 0-5V can 
be used. 

 

Fuse Mode  

The Fuse Mode can be used mode to prevent a major damage to a defective load. Fuse Mode can be activated 
via the associated switch S12 DIP switch. 
If the device is in the Fuse Mode (DIP switch S12=0), the device switches off when the constant current 
operation is taking longer than typ. 5s. The red OCP LED flashes with a period of 0,4s. The PSU is locked. The 
interlock can be canceled by the power supply is either switched off by the mains input, SB or SD contact for a 
moment. 

 

Continuous Mode 

If you select Continiuous Mode at DIP switch S12 (DIP switch S12=1), the device provides continuous power. It 
also applicable in the Constant Current Mode. Factory setup = Continuous Mode 

Summary of Contents for 3041110002CA

Page 1: ... Heat Dissipation Real time I V programming Real time I V monitoring Reference voltage f autonomous programming CSB Current Share Bus Inhibit for safe interlocking Remote Shutdown Sense mode Power Good Relay DC ok Precise dynamics on load change Series parallel operation up to 100kW EMC conducted class B radiated class A Efficiency 92 94 PFC Powerfactor 0 99 Variable controlled fans from Papst Lon...

Page 2: ...ghest standards of safety and interference suppression The device was developed in accordance with the requirements of EN61010 1 EN61010 2 201 EN62368 1 and the EMC standards EN55032 conducted Class B radiated Class A The mechanical design of the CPS EX2000 device series is unique It is the first power supply line in the world market which can be flexibly adapted to any installation situation The ...

Page 3: ...ect load The lock can be controlled remotely or repeal by disconnection from the mains again Continuous Mode The unit can be operated in continuous mode In the continuous mode the power supply provides constant current mode in a continuous flow and no ticker operation Master Slave Mode Ureg OUT Ireg OUT The master slave mode can be defined in the parallel operation One device can be set as the mas...

Page 4: ...over all Accuracy Ureg 0 5 Ireg 1 Umon 0 5 Imon 1 Uref 1 Temperature Control yes thermal shutdown autorecovery 70 C outside measuring point distance 10mm Hold Up Time 30ms 230Vac mains buffering at full load Inrush Current 14 6Aeff 20 7Apeak 230Vac active electronic inrush protection no simple NTC Startup Delay typ 1s Softstart typ 100ms Ambient Temperature 20 C 60 C operating derating 2 5 C 50 C ...

Page 5: ...ailure Open Collector 8 INH Output Signal Inhibit Active Open Collector 9 OT Output Signal Over Temperature Open Collector 10 TA Output Signal Temperature Alarm Open Collector Early warning 11 OCP Output Signal Over Current Protection Open Collector 12 CC Output Signal Constant Current Mode Open Collector 13 OVP Output Signal Over Voltage Open Collector 14 CV Output Signal Constant Voltage Mode Op...

Page 6: ...7 01 3 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death Schematic of the internal circuits CON1 4 NC NC ...

Page 7: ...60 C 250Vac 20A Neutrik PowerCon 3x2 5 mm Neutrik NAC3FCA Copy of the original instruction http www neutrik com de powercon powercon 20 a nac3fca Interface pluggable Push Pull Connectors from Weidmueller included Input Power Connector Neutrik NAC3FCA included Output Power Connection M8 Powerbars Lock Pins snap into the 2U 3U 19 subrack WARNING OUTPUT CONNECTION INSTRUCTION Mount the cable lugs dir...

Page 8: ...usted analog control signal The monitor signal is analog linear to the output voltage The monitor signal for current and voltage is the real value that is measured directly at the output of the power supply If a sense line is connected to compensate for the voltage drop across the load lines the monitor signal is exactly the value that is measured at the connection point of the sense line The desc...

Page 9: ...y To avoid interference twist the sense lines To reduce inductive effects we recommend that the load lines position is close to each other To supply a pulsating load the use of an electrolytic capacitor and a cermic capacitor has proved The internal Over Voltage Protection OVP of the power supply controls the DC power directly to the DC output terminals In case of an error the OVP acts automatical...

Page 10: ... message An uneven load and thus premature aging of the participating devices is prevented Connect CON3 contact 5 CS to contact 13 of the slave Are other devices involved in the parallel operation you may grind the CS bus through from unit to unit The current division between the devices will be performed automatically The accuracy of the current distribution is 5 at Iout 0 5 x Iout max Derate the...

Page 11: ...uxiliary Voltage 12V AUX The power supply offers an auxiliary voltage 12V 500mA The accuracy is 500mV Ripple Noise 30mVpp The auxiliary voltage is not affected by the control signals Standby SB Shutdown SD and Inhibit INH and remains always active Between auxiliary voltage and the power output is a reinforced Isolation of max 400Vdc and a basic isolation of max 600Vdc working voltage DC OK Relay D...

Page 12: ...en Collector IMAX 10mA VLOW 0 6V VMAX 30V When OVP INH SB SD FF OCP OT or defective PFC occur the mes sage signal CC is low because the power output is switched off The change between the CV and the CC mode is automatic Please pay attention to the DIP switch setting of the Fuse Mode to avoid provoking malfunction CC Mode Over Current Protection in the Fuse Mode OCP The alarm signal OCP is high whe...

Page 13: ...r proportional to the control signal Ureg The desired control signal is selected via the DIP switcher 0 5V 0 10V 0 20mA oder 4 20mA Model Value UA1 V Value IA1 A Value UA2 V Value IA2 A Pmax IA1 IA2 CPS EX2000 024 30Vdc 66 7A 24Vdc 84A 2001 2016W CPS EX2000 036 45Vdc 44 4A 36Vdc 56A 1998 2016W CPS EX2000 048 58Vdc 34 5A 48Vdc 42A 2001 2016W CPS EX2000 072 90Vdc 22 2A 72Vdc 28A 1998 2016W CPS EX200...

Page 14: ...internal components used only the models with an output voltage of 48Vdc and later are approved for series operation Other power supplies are not approved for series operation above 60Vdc If the units are remotely controlled via the analog interface it is compulsory to use a potential free control voltage Parallel Operation N 1 Decoupling To increase the overall power of the power supply up to 5 u...

Page 15: ...l Germany P 15 21 07 2017 01 3 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death ...

Page 16: ...ting damage can happen to the power supply unit For the field test owner follow the below instruction a Use suitable test equipment raising the voltage slowly b Short circuit L1 and N and all the DC output terminals c Use only test voltages of 50 60Hz The outputs are unearthed and therefore they have no resistance to GND PE d If the residual voltage is 60Vdc observe the safety standards Use only s...

Page 17: ...result in injury or death Mechanics Aluminium housing IP20 Cooling is achieved via front to rear fans To ensure adequate heat dissipation 50mm to the front and 150mm blockade free distance from the device back wall must be guaranteed The harnesses are to be designed and installed to that the air outlet of the unit is not being blocked In a rack mounting of multiple subracks the rear distance of th...

Page 18: ...ww camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death 19 Subrack 2U 3U 2U Subrack for 1 3 CPS EX2000 with up to 6kW continuous power 3U Subrack for 1 5 CPS EX2000 with up to 10kW continuous power ...

Page 19: ...to custom design power supplies Steplessly hard mount of the CPS EX2000 3000 power supply modules in a 3D room In practice that means that one can mount the modules into every angle imaginable Our 3D Heat Dissipation 3D HD ensures optimal cooling in each mounting position you may consider All you may consider is to make sure that at least a distance of 5cm 2 Inch to the front cooling slots and 15c...

Page 20: ...on Article Number CPS EX2000 024 R2 24Vdc model incl analogue interface 3041110002CA CPS EX2000 036 R2 36Vdc model incl analogue interface 3041110003CA CPS EX2000 048 R2 48Vdc model incl analogue interface 3041110004CA CPS EX2000 072 R2 72Vdc model incl analogue interface 3041110005CA CPS EX2000 110 R2 110Vdc model incl analogue interface 3041110006CA Certifcate Calibration Separate works certific...

Page 21: ...bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 16A It is prohibited to use the unit without PE It may be necessary upstrea...

Reviews: