Technical Data Table
AC Input Range
184-264Vac
AC Input Frequency
47-63Hz
DC Input Range
250-375Vdc
AC Input Rated
230Vac <10A
DC Input Rated
250Vdc <9,3A 375Vdc <6,2A
DC Voltage Rated
24Vdc
36Vdc
48Vdc
72Vdc
110Vdc
DC Voltage Programmable
24 - 30Vdc
30 - 45Vdc
45 - 58Vdc
58 - 90Vdc
90 - 150Vdc
DC Current Programmable
42 - 84A
28 - 56A
21 - 42A
14 - 28A
9,1 - 18,2A
Over Voltage Protection
35Vdc
52,5Vdc
68Vdc
105Vdc
175Vdc
Over Current Protection
92A
62A
46A
31A
20A
Ripple Noise 230Vac 20MHz 35mVpp
35mVpp
75mVpp
100mVpp
200mVpp
Auxiliary Voltage
12Vdc/0,5A accuracy ±0,5V R&N 30mVpp, not influenced from SB, SD, INH operations
Power Rated
2000W, 184-264Vac
Cooling
Continuously controlled and monitored fans from EBM Papst (Germany)
Efficiency
typ. 92-94% 230Vac at full load
Power Factor Control (PFC)
0,99 / 230Vac full load
Short Circuit Resistance
yes
Open Circuit Protected
yes
Base Load (OCP)
Non required (open circuit protected)
Load Regulation
< ± 0,05% 0-100%
Load Regulation Time
<1ms on load switch 10-100%
Rise Time and Latency
0V – Vout
max
, 15ms over all
Accuracy
Ureg:
≤
± 0,5%, Ireg:
≤
± 1%, Umon:
≤
± 0,5%, Imon:
≤
± 1%, Uref:
≤
±1%
Temperature Control
yes, thermal shutdown & autorecovery (+70°C, outside measuring point distance 10mm)
Hold Up Time
>30ms 230Vac
mains buffering at full load
Inrush Current
<14,6Aeff <20,7Apeak 230Vac active electronic inrush protection (no simple NTC)
Startup Delay
typ. 1s
Softstart
typ. 100ms
Ambient Temperature
- 20°C…+60°C operating, derating 2,5%/°C >50°C
Storage Temperature
- 40°C…+85°C
Ambient Conditions
Humidity 95% non-condensing @ 25°C, climate class 3K3, pollution degree 2
ROHS
2011/65/EU, (EU) 2015/863 conform
REACH
EG No. 1907/2006 conform
EMI
EN55032, conducted .024/.036/.048 class B / .072/.110 class A, all models radiated class A
EMS/EMI
EN61000-6-2,3,4
Safety
EN61010-1, EN61010-2-201, EN62368-1, EN60950-1, EN60204-1
Protection Class I
PE connection required
Leackage Current
Typical 1,9mA, <2,8mA, 230Vac 50Hz
Isolation Input to Output
3000Vac
Isolation Input to Case
2500Vac
Isolation Output to Case
500Vdc ,
≥
48Vdc= 2800Vdc
MTBF (IEC61709)
419500h (Meantime Between Failures: statistic time between failures after repairs)
MTTF (IEC61709)
146110h (Meantime To Failure: statistic time to ever fails)
Dimensions (HxWxD)
84x126,4x444mm | 3,3x5x17,5 Inch (without frontplate, note cable outlet in planning)
Weight
4,4kg / 9,7lbs
Input Power Connections
Neutrik NAC3FCA (locked by bajonett) included
Output Power Connections
Brass-Powerbars with metric M8 thread, a touch protection is included
Programming Time Vout [ms]
Model
24Vdc
36Vdc
48Vdc
72Vdc
110Vdc
Slew Rate 90-10%, 10/100% Load, [ms] typ.
70/7,0
30/3,0
46/4,6
35/3,5
47/4,7
Output Capacity, [mF] typ.
19,4
3,74
3,4
1,07
0,52