RAWS-P Remote Automated Weather Station
CS100 Barometric Pressure Sensor wires attached to CR1000 Wiring
Panel
CS100 Blue wire
to CR1000 wiring panel 5H
CS100 Yellow wire
to CR1000 wiring panel AG
CS100 Red wire
to CR1000 wiring panel 12V
CS100 Clear wire
to CR1000 wiring panel Ground
CS100 Black wire
to CR1000 wiring panel Ground
CS100 Green wire
to CR1000 wiring panel C4
The CS100 is sensitive to static when the back plate is
removed. To avoid damage, take adequate anti-static
measures when handling this sensor.
CAUTION
4.5.3 Troubleshooting, Barometric Pressure (part #CS100)
Verify the sensor wires are securely fastened to the CS100 Barometric Pressure
Sensor
connector and the CR1000 printed circuit board wiring panel. Use a
DVM to check the sensor output voltage on the CR1000 printed circuit board
wiring panel (0 to 2.5 VDC) between terminals 5H and AG.
For the DVM test, “temporarily” move the green wire from “C4”
to “5V” terminal. No voltage indicates a problem with the sensor
or a bad sensor cable connection. Try connecting a substitute
sensor.
NOTE
Obtain a Return Material Authorization (RMA) number before returning this
sensor to Campbell Scientific for repair.
Consult the CS100 manual for more information.
NOTE
4.6 Fuel Moisture and Fuel Temperature
4.6.1 General Description, Fuel Moisture/Fuel Temperature
(part #CS515-LQ)
The Campbell Scientific Fuel Moisture/Fuel Temperature Sensor (part
#CS515-LQ)
consists of a CS505 Fuel Moisture Probe, CS205 Fuel
Temperature Stick, and 107-LQ thermistor mounted on a 10974 fuel
moisture/temperature mounting stake. The fuel moisture probe provides the
moisture content of a standard 10-hour fuel moisture dowel. This moisture
represents the moisture content of small-diameter (10-hour time lag) forest
fuels. The fuel temperature probe consists of a Ponderosa pine dowel with a
bored hole and a Model 107 Temperature Probe inserted into the dowel. The
CS205 mounts on the mounting stake with the CS505.
4.6.2 Wiring, Fuel Moisture/Fuel Temperature (part #CS515-LQ)
The Campbell Scientific CS505 and CS205 sensors are combined into one
connector (part#CS515-LQ). This sensor is internally wired from the RAWS
connector panel to the CR1000 datalogger. This sensor is connected to the
RAWS connector panel “FM/FT” connector COLOR CODED BROWN.