CS210 Enclosure Humidity Sensor 

1.  General 

The CS210 Enclosure Humidity sensor contains an Elan HM2000 series precision 
bulk-polymer relative humidity sensor.  It is used to monitor the relative humidity 
inside an equipment enclosure deployed in the field. 

The CS210 was once known as the 10162. 

NOTE 

2.  Specifications 

Sensor:  Elan HM2000 series precision bulk-polymer 

Relative Humidity Measurement Range:  0 to 100% non-condensing 

RH Output Signal Range:  0 to 1.0 VDC 

Accuracy at 25

°

unspecified (0 to 10% Relative Humidity) 

±

3% RH (10 to 90% Relative Humidity) 

unspecified (90 to 100% Relative Humidity) 

Typical Long Term Stability:  Better than 3% RH per year 

Response Time (at 25

°

C, 90% response):  10 seconds for a 30% to 90% RH 

step change 

Operating Temperature:  0

°

C to +50

°

Storage Temperature:  -40

°

C to +80

°

Probe Length:  2.6 cm (1.02 in.) 

Probe Cross Section Area:  0.6 cm x 1.1 cm (0.23 in. x 0.43 in.) 

Current Consumption:  <0.5 mA 

Supply Voltage:  5 

±

 0.25 VDC 

Settling Time:  10 seconds 

3.  Installation 

Mount the CS210 inside the environmental enclosure or onto a datalogger 
using the mounting block and the wire tie included with the sensor (Figure 1). 

The black outer jacket of the cable is Santoprene

® 

rubber.  This 

compound was chosen for its resistance to temperature extremes, 
moisture, and UV degradation.  However, this jacket will 
support combustion in air.  It is rated as slow burning when 
tested according to U.L. 94 H.B. and will pass FMVSS302.  
Local fire codes may preclude its use inside buildings. 

NOTE 

Summary of Contents for CS210

Page 1: ...CS210 Enclosure Relative Humidity Sensor Revision 10 07 C o p y r i g h t 1 9 9 6 2 0 0 7 C a m p b e l l S c i e n t i f i c I n c...

Page 2: ...f all other warranties expressed or implied including warranties of merchantability or fitness for a particular purpose CAMPBELL SCIENTIFIC INC is not liable for special indirect incidental or consequ...

Page 3: ...inks to specific sections 1 General 1 2 Specifications 1 3 Installation 1 4 Wiring 2 5 Programming 3 5 1 CRBasic Examples 3 5 2 Edlog Examples 5 6 Enclosure Humidity 7 7 Maintenance 7 Figures 1 CS210...

Page 4: ...This is a blank page...

Page 5: ...er year Response Time at 25 C 90 response 10 seconds for a 30 to 90 RH step change Operating Temperature 0 C to 50 C Storage Temperature 40 C to 80 C Probe Length 2 6 cm 1 02 in Probe Cross Section Ar...

Page 6: ...ended analog input channel TABLE 1 Datalogger Connections Description Color CR200 series CR800 CR850 CR1000 CR3000 CR5000 CR9000 X CR10 X CR500 CR510 CR23X 21X Relative Humidity White Single Ended Si...

Page 7: ...rned on Depending on the scan rate the first few measurements from the CS210 could be low The probe output scale is 0 to 1000 millivolts for the relative humidity range of 0 to 100 Table 2 provides ca...

Page 8: ...d a delay VoltSe Enc_RH 1 mV2500 1 1 0 250 0 1 0 Set the sensor to 100 if it exceeds 100 If Enc_RH 100 Then Enc_RH 100 CallTable Daily NextScan EndProg Example 2 Sample CR200 Program CR200 Series Data...

Page 9: ...ple 4 is an Edlog program written for a 21X Micrologger wiring used for the 21X program is included in Table 3 The 21X program turns on control port 1 to power the CS210 Notice that the scan rate is s...

Page 10: ...o P86 1 41 Set Port 1 High 4 Volt SE P1 1 1 Reps 2 15 5000 mV Fast Range 3 1 SE Channel 4 3 Loc Enc_RH 5 0 1 Multiplier 6 0 Offset 5 If time is P92 1 0 Minutes into a 2 1440 Minute Interval 3 10 Set O...

Page 11: ...connector be sealed with plumbers putty and that desiccant packs be placed inside the enclosure Spikes in the enclosure humidity are a result of opening the enclosure door and allowing ambient air in...

Page 12: ...CS210 Enclosure Humidity Sensor This is a blank page 8...

Page 13: ...This is a blank page...

Page 14: ...L www campbellsci com br suporte campbellsci com br Campbell Scientific Canada Corp CSC 11564 149th Street NW Edmonton Alberta T5M 1W7 CANADA www campbellsci ca dataloggers campbellsci ca Campbell Sci...

Reviews: