background image

Instruction Manual 

Where the SDM-CVO4 is going to be used in applications where the potential 
difference between the datalogger and the output terminals exceeds 50 V RMS 
AC, 74 VDC then careful consideration has to be taken to ensure safe operation 
and compliance with local safety regulations. For such applications Campbell 
Scientific does not supply the device as a stand-alone device which will meet all 
safety requirements. The SDM-CVO4 is supplied as a component for the user to 
install in a system that is, itself, designed to comply with such regulations. The 
following guidance is given to help users meet the requirements of such 
regulations. 

The SDM-CVO4 is designed such that the internal safety barrier meets the 
requirements of BS EN 61010-1 (similar to IEC 950). However, the method of 
wire connection and earthing facilities prevents the unit being claimed as 
compliant with such standards, when supplied as a stand-alone unit. 

To meet the safety requirements of most countries, wires carrying hazardous 
voltages, terminated in screw terminals must be housed in an enclosure requiring a 
tool to open it, and the enclosure must have international symbols on the outside 
warning of high voltages. An additional warning label, in the local language, may 
be required stating that the source of hazardous voltage must be turned off before 
the enclosure is opened. 

The exact nature of the enclosure is covered by the standards, but an enclosure 
designed to house electrical equipment will usually meet the requirements. 
Campbell Scientific's ENC 12/14 or 16/18 enclosures meet these requirements if 
fitted with a padlock and with the correct labels on the door. 

It is also necessary to ensure that metal parts on the outside of the enclosure that 
might come in contact with active high voltage circuits are connected to a safety 
ground. The ground lug of Campbell Scientific enclosures is the main issue for the 
above enclosures, but this would, in any case, normally be the point of contact to a 
good ground point. 

Cables that connect to the output of the SDM-CVO4 should have adequate strain 
relief at the point of exit from the enclosure, and the cable and any connectors 
used should be rated to a high enough voltage and assembled in a safe fashion. 

If possible, the external device which is operating at a high voltage relative to 
ground should be configured with an earth leakage breaker system to disconnect it 
from the voltage source in the event of a breakdown of the insulation in the 
system causing a leak to ground. 

With a system made to the above requirements the maximum recommended 
continuous operating voltage between the datalogger and input is 240 VAC. This 
value is derived from the voltage rating of the terminal blocks used and an internal 
suppression capacitor (see below). 

The unit is designed to withstand a transient flash test of 1500 V RMS AC, for 
two seconds. However, you need to be aware of some aspects of the design which 
can influence the results of such a test if made. 

a)

 

To help suppress emissions of electromagnetic interference the isolation 
barrier is bridged by a 1nF, class ‘Y’ safety capacitor. This is rated to 
withstand a 2700V, 2 second flash test, but will fail if exposed to 
voltages in excess of 240 V RMS for long periods. 

b)

 

To provide protection from transients and static for this capacitor and the 
opto-isolation component that bridges the barrier, there is a spark gap 
across the barrier that has a 2500 VDC nominal breakdown voltage. If 

11 

Summary of Contents for 4-Channel Current/Voltage SDM-CVO4

Page 1: ...SDM CVO4 4 Channel Current Voltage Output Module User Guide Issued 13 3 08 Copyright 2001 2007 Campbell Scientific Inc Printed under Licence by Campbell Scientific Ltd CSL 436...

Page 2: ......

Page 3: ...lieu of all other guarantees expressed or implied including those of suitability and fitness for a particular purpose Campbell Scientific is not liable for consequential damage Please inform us before...

Page 4: ......

Page 5: ...eneral Principles of Use 12 5 1 Voltage or Current Signalling 12 5 2 Providing Excitation Supplies to Sensors 12 6 Datalogger Instruction 103 13 6 1 Edlog Instruction 103 13 6 2 Edlog Program Examples...

Page 6: ...Contents Tables 4 1 Datalogger to SDM CVO4 Connections 4 4 2 Switch Position and Addresses 10 6 1 Description of Instruction 103 14 ii...

Page 7: ...ed by the application Typical applications will include driving remote current loop display units re transmitting measured values to industrial control systems which have current or high voltage input...

Page 8: ...ed with the CR800 CR1000 CR3000 and CR5000 2 Specifications 2 1 General Specifications Compatible dataloggers CR10X CR800 CR1000 CR3000 CR5000 and CR7 Also compatible with many retired dataloggers suc...

Page 9: ...m load Please contact Campbell Scientific for the accuracy specification on extended temperature tested units 2 3 Isolation Specifications Design criteria The unit has an internal isolation barrier an...

Page 10: ...cific to the installation see section 4 5 4 1 Connection to a Datalogger For datalogger connections see Table 4 1 below Table 4 1 Datalogger to SDM CVO4 Connections Connection Order SDM CVO4 Datalogge...

Page 11: ...the screwdriver to release the spring The wire will now be firmly held in place See Figures 4 1 and 4 2 below Figure 4 1 Use of the Spring Loaded Terminal Blocks Top Position Figure 4 2 Use of the Spr...

Page 12: ...ower source in current mode In voltage mode the connection to a remote device is a simple two wire connection Inputs Remote Voltage Input CVO4 Vo 4 2 2 Current Output Mode The Id terminal acts as the...

Page 13: ...ted drop of 20 mA flowing through the total resistance of the cable in the loop plus any voltage drop in the remote device normally the voltage drop across a fixed sense resistor As a simple example c...

Page 14: ...SDM CVO4 to provide a low impedance path to ground In doing this though there is a risk that you will nullify the effects of the isolation barrier e g if the ground you connect to is the same ground t...

Page 15: ...mode which may result in abnormal operation and change of output accuracy CAUTION The jumper settings can be overridden by the datalogger program if required using special commands Please contact Cam...

Page 16: ...here the potential voltage difference between the datalogger and the SDM CVO4 outputs is considered to be non hazardous less than 50 V then the unit can be used as any other peripheral without undue c...

Page 17: ...ct labels on the door It is also necessary to ensure that metal parts on the outside of the enclosure that might come in contact with active high voltage circuits are connected to a safety ground The...

Page 18: ...equired inputs for Instruction 103 and also to preserve the original measurement values for other purposes Instruction 103 would then be executed at the same rate as the measurements have been made to...

Page 19: ...quence It is possible that you can power more than one sensor from each output of the SDM CVO4 either by parallel connection in voltage output mode or serial connection in current output mode Make sur...

Page 20: ...in a limit of 0 5 in terms of the scaling value stored in the input location The number of repetitions parameter 1 specifies the total number of SDM CVO4 output channels to be set The address of the f...

Page 21: ...0 mA depending on the output jumper settings Programming for the CR10X is very similar CR23X Example weather station program to show scaling values for the SDM CVO4 Table 1 Program 01 1 Execution Inte...

Page 22: ...ues and update the SDM CVO4 As we have four channels to output we will first copy the current readings with P54 block move in a block of four input locations to hold the scaled outputs 9 Block Move P5...

Page 23: ...structions in the example above Then apply the scaling with one instruction P53 The readings are scaled 3000 to 5000 i e to cover the range which would equate to 4 20 mA in current mode Windspeed to c...

Page 24: ...he SDM CVO4 into standby mode after the measurements are made An example program which show use of the SDM CVO4 as an isolated power supply for 4 sensors requiring 10 V drive and producing 0 100 mV si...

Page 25: ...eps 2 04 250 mV Slow Range 3 1 DIFF Channel 4 5 Loc Press_1 5 1 0 Mult 6 0 0 Offset Now turn o SDM CV ff the O4 by using the command with 0 reps 5 SDM AO4 P103 1 0 Reps 2 00 SDM Address 3 1 Loc Scale_...

Page 26: ...er of channels of all devices e g to set all four channels on two devices set the CVO4Reps parameter to 8 If the CVO4Reps parameter is set to 0 power to the device will be turned off SDMAddress The SD...

Page 27: ...0_540 Public Flag Public CVO4Output 4 Alias CVO4Output 1 WSOut Alias CVO4Output 2 WDOut Alias CVO4Output 3 TempOut Alias CVO4Output 4 RHOut Code for DataTable OneMin DataTable OneMin 1 1 DataInterval...

Page 28: ...V WSOut WS_ms 200 WS 0 50 m s 0 10000 mV WDOut WD_0_540 18 59 WD 0 540 deg 0 10000mV TempOut 100 Temp_C 40 Temp 40 60 deg C 0 10000 mV RHOut RH 100 RH 0 100 RH 0 10000 mV Send mV outputs to SDM CVO4 u...

Page 29: ......

Page 30: ...campbellsci com br suporte campbellsci com br Campbell Scientific Canada Corp CSC 11564 149th Street NW Edmonton Alberta T5M 1W7 CANADA www campbellsci ca dataloggers campbellsci ca Campbell Scientifi...

Reviews: