SDM-CVO4 4-Channel Current/Voltage Output Module
; then set the value to –3000
13: Z=F (P30)
1:
-3000
F
2: 00
Exponent of 10
3: 5
-- Z Loc [ ScldOut_1 ]
14: End (P95)
15: End (P95)
; Now update the SDM-CVO4 with the information
; for the four channels
16: SDM-AO4 (P103)
1: 4
Reps
2: 30
SDM
Address
3: 5
Loc [ ScldOut_1 ]
6.2.3 Providing Isolated Power Supplies to Sensors
SDM-CVO4 to 10 V to provide
t
; {CR10X}
This program example sets all the outputs of the
isolated power supplies to four separate sensors. The program includes code to pu
the SDM-CVO4 into standby mode after the measurements are made.
; An example program which show use of the SDM-CVO4
; as an isolated power supply for 4 sensors requiring
; 10 V drive and producing 0-100 mV signals.
; This shows how to set the SDM-CVO4 into standby mode.
*Table 1 Program
01:
60
Execution Interval (seconds)
; S
ixed val
5000 = 10 V output
tore a f
ue of
; in the four scaling locations
1: Bulk Load (P65)
1: 5000
F
2: 5000
F
3: 5000
F
4: 5000
F
5: 0.0
F
6: 0.0
F
7: 0.0
F
8: 0.0
F
9: 1
Loc [ Scale_1 ]
; T
t
V
puts to 10,000 mV
ell he SDM-C O4 to set all four out
; The SDM-CVO4 address is zero in this example.
; This will cause the SDM-CVO4 to come out of standby
; mode.
2: SDM-AO4 (P103)
1: 4
Reps
2: 00
SDM
Address
3: 1
Loc [ Scale_1 ]
18