4. Mechanical mounting
The SIRAX MM1200 is designed for panel mounting.
4.1 Panel cut out
Dimensional drawing MM1200: See section 17
4.2 Mounting of the device
The device is suitable for panel widths up to 8mm and a panel cutout of 96 x 96 mm.
Variant with Mounting clamps
a) Slide the device into the cutout from the outside
b) Mounting is by four side clamps, slide the side clamps through
side slot till side clamp gets fi rmly locked in a groove (Refer fi g.)
Consideration should be given to the space required behind the
instrument to allow for bends in the connection cables.
4.3 Demounting of the device
The demounting of the device may be performed only if all connected wires are out of service. Remove all plug-in terminals and all connections
of the current and voltage inputs. Pay attention to the fact, that current transformers must be shortened before removing the current connections
to the device. Then demount the device in the opposite order of mounting (4.2).
Please ensure that the operating temperature limits are not exceeded when determining
the place of mounting (place of measurement):
–10 … +55° C