
PM 1000268 000 00
Device handbook SIRAX MM1200
33/48
Inductive
Quadrant 3
-P
-Q
Quadrant 4
+P
-Q
Quadrant 1
+P
+Q
Quadrant 2
-P
+Q
Capacitive
Capacitive
Inductive
90 degrees (0.000)
0 degrees (+1.000)
180 degrees (-1.000)
270 degrees (0.000)
300 degrees (+0.500)
330 degrees (+0.866)
30 degrees (+0.866)
60 degrees (+0.500)
120 degrees (-0.500)
150 degrees (-0.866)
240 degrees (-0.500)
210 degrees (-0.866)
Export
Quadrant 1:
0° to 90°
Quadrant 2:
90° to 180°
Quadrant 3:
180° to 270°
Quadrant 4:
270° to 360°
Import
15. Phasor Diagram
Hi Alarm:
If Hi-Alarm Energized or Hi Alarm De-Energized option is selected then relay will get energized or De-energized,if selected parameter is greater
than or equal to trip point.
Low Alarm:
If Lo-Alarm Energized or Lo Alarm De-Energized option is selected then relay will get energized or De-energized,if selected parameter is less
than or equal to trip point.
Trip point:
Trip point can be set in the range of 10% to 120 % of nominal value for Hi-Alarm & 10% to 100 % of nominal value for Lo-Alarm.
Hysteresis:
Hysteresis can be set in the range of 0.5% to 50 % of set trip point. If Hi-alarm Energized or Hi-alarm De-energized is selected then relay will get
De-energized or Energized respectively, if set parameter value is less than Hysteresis Similarly if Lo-alarm Energized or Lo-alarm De-Energized.
Energizing Delay:
The energizing delay can be set in the range from1 to 10 sec.
De-Energizing Delay:
The De-energizing delay can be set in the range from1 to 10 sec.
Note: In case of lo alarm if trip point is set at 100% then maximum 20%
Hysterisis can be set.
Example of diff erent confi guration.
Parameter No: 4 (Current 1)
Trip Point = 50%
Hysteresis = 50% of trip point
Energising Delay: 2s
De-energising Delay: 2s
In this diagram a technical
visualization of the current and
voltage phasors is shown, using a
clockwise rotation.
Hysterisis point
Trip point
Relay Energise
Relay De-energise
Time
25%
50%
Input
2s
2s
1) Hi alarm & Energised relay
Hysterisis point
Trip point
Relay De-energise
Relay Energise
Time
25%
50%
Input
2s
2s
2) Hi alarm & De-energised relay
Trip point
Relay Energise
Relay De-energise
Time
50%
75%
Input
2s
2s
4) Lo alarm & De-energised relay
Trip point
Relay De-energise
Relay Energise
Time
50%
75%
Input
2s
2s
3) Lo alarm & Energised relay
Hysterisis point
Hysterisis point