PM 1000268 000 00
Device handbook SIRAX MM1200
40/48
Adress
(Register)
Parameter No.
Parameter
Modbus Start Adress Hex
3P 4W
3P 3W
High Byte
Low Byte
30053
27
Watt Sum
00
34
•
•
30055
28
VA Ave
00
36
•
•
30057
29
VA Sum
00
38
•
•
30059
30
VAR Ave
00
3A
•
•
30061
31
VAR Sum
00
3C
•
•
30063
32
PF Ave
00
3E
•
•
30065
33
PF Sum
00
40
•
x
30067
34
Phase Angle Ave
00
42
•
•
30069
35
Phase Angle Sum
00
44
•
x
30071
36
Freq
00
46
•
•
30073
37
Wh Import / Utility
00
48
•
•
30075
38
Wh Export / Gen
00
4A
•
•
30077
39
Capacitive / Utility VARh
00
4C
•
•
30079
40
Inductive / Gen VARh
00
4E
•
•
30081
41
VAh / Vah Utility
00
50
•
•
30083
42
Ah
00
52
•
•
30085
43
W Demand (Import)
00
54
•
•
30087
44
W Max Demand (Import)
00
56
•
•
30089
45
W Demand (Export)
00
58
•
•
30091
46
W Max Demand (Export)
00
5A
•
•
30093
47
–
–
–
–
–
30095
48
–
–
–
–
–
30097
49
–
–
–
–
–
30099
50
–
–
–
–
–
30101
51
VA Demand
00
64
•
•
30103
52
VA Max Deman
00
66
•
•
30105
53
A Demand
00
68
•
•
30107
54
A Max Demand
00
6A
•
•
30133
67
System Max Voltage
00
84
•
•
30135
68
System Min Voltage
00
86
•
•
30141
71
System Max Currrent
00
8C
•
•
30143
72
System Min Current
00
8E
•
•
30201
101
VL 1 - 2 (Calculated)
00
C8
•
x
30203
102
VL 2 - 3 (Calculated)
00
CA
•
x
30205
103
VL 3- 1 (Calculated)
00
CC
•
x
30207
104
V1 THD (%)
00
CE
•
•
30209
105
V2 THD (%)
00
D0
•
•
30211
106
V3 THD (%)
00
D2
•
•
30213
107
I1 THD (%)
00
D4
•
•
30215
108
I2 THD (%)
00
D6
•
•
30217
109
I3 THD (%)
00
D8
•
•
30219
110
System Voltage THD (%)
00
DA
•
•
30221
111
System Current THD (%)
00
DC
•
•
30225
113
I Neutral
00
E0
•
x
30227
114
Run Hour
00
E2
•
•
30229
115
On Hour
00
E4
•
•
30231
116
No. of Interruptions
00
E6
•
•
Note: Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W.