CONNECTION OF GAS (Propane) TO THE APPLIANCE
MANUAL SHUT OFF VALVE REQUIRED
A manual shut off valve shall be provided on the inlet connection of the appliance. The valve shall be accessible
for operation and firmly fixed.
A hose assembly used to connect rigid consumer pipe work to an appliance shall:-
a) Not exceed 1.2m in length; and
b) Be of adequate diameter for the maximum gas consumption of the appliance.
c) Flexible hose to AS 1869 Type “B” or “D”
Make sure that the route of the flexible hose does not touch any metal parts, which get heated during operation
of the appliance, such as the part beneath the burners. It must also be installed so that there is no contact with
moving parts (e.g. drawers etc.) and must not pass through spaces where it can be compressed.
With rigid connection of the appliance, the pipe work and fittings shall be free from defects and of an approved
type as stated in AS 5601 / AG601 “Gas Installations”. (Code for gas burning appliances and equipment) Published
by the Australian Gas Association.
Ensure there is enough free pipe work so the appliance can be removed slightly for servicing
Once installed, the installation must be checked for leaks by means of an approved testing method
NEVER USE
A NAKED FLAME.
GAS CONNECTION POINT
The gas connection point is located at the rear of the appliance, in the top right corner.
DUPLICATE DATA PLATE
The duplicate data plate should be attached where it is accessible after the appliance has been installed. (eg: inside
a cupboard door).
CONNECTION TO THE ELECTRICITY SUPPLY
240 Volt a.c. SUPPLY CONNECTION.
240 Volts a.c. 50 Hz for Optional Electric Hob Element ONLY.
This Appliance must be wired, to include a Circuit Breaker or Isolating Switch, as per AS/NZS3000.
This appliance must be connected with wiring of an appropriate temperature rating, exceeding T75.
12 Volt DC ELECTRICAL SUPPLY CONNECTION.
12 Volts d.c. ALL Models for Ignition of Gas Burners, Light and Optional Rotisserie.
The 12 Volts d.c. is to be wired using twin cable, (red / black, 1.5 mm2) to the terminal block situated at the back of
the appliance. It is important to observe the correct polarity; + positive, red, - negative black. If polarity is incorrect
electronic igniter will not function. The 12 Volts d.c. circuit must be protected by a 3 ampere fuse.
12
NOTE:
ALL INSTALLATION SHOULD BE CARRIED OUT BY AUTHORIZED TRADE’S PERSONS
ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS, RELEVANT FEDERAL AND
STATE REGULATIONS, AND WITH THE REQUIREMENTS OF SECTION 5.12, 6.2 AND
6.3 OF AS 5601 / AG601 “GAS INSTALLATIONS”, PUBLISHED BY THE AUSTRALIAN GAS
ASSOCIATION. FOR INFORMATION REGARDING INPUTS AND GAS PRESSURES REFER
TO THE DATA PLATE ATTACHED TO THE APPLIANCE.