LAYING THE CORRUGATED TUBES

Dig a hole for the foundation frame.
Set up the corrugated tubes needed for the wiring coming out of the junction pit. 
For connecting the gearmotor we suggest using a Ø 40 mm corrugated tube, whereas for the accessories we suggest Ø 25 mm tubes.

 The number of tubes depends on the type of system and the accessories you are going to fi t.

GENERAL INSTALLATION INDICATIONS

 Only skilled, qualified staff must install this product.

PRELIMINARY CHECKS

⚠ 

Before beginning the installation, do the following:

• check that the upper slide-guides are friction-free;
• check that the gate is stable and that the casters are in good working order and lubricated;
• check that the ground rails are well-fastened, entirely on the surface and are smooth and level so as not to obstruct the gate's movement;
• make sure you have fitted opening and closing mechanical gate stops;
• make sure that the point where theoperator is fastened is protected from any impacts and that the surface is solid enough;
• set up suitable tubes and conduits for the electric cables to pass through, making sure they are protected from any mechanical damage.

CABLE TYPES AND MINIMUM THICKNESSES

Connection

cable length

< 20 m

20 < 30 m

Input voltage for 230 V AC control board
(1P+N+PE)

3G x 1.5 mm

2

3G x 2.5 mm

2

Flashing light

2 x 0.5 mm

2

Command and control devices

2 x 0.5 mm

2

TX Photocells

2 x 0.5 mm

2

RX photocells

4 x 0.5 mm

2

 

When operating at 230 V and outdoors, use H05RN-F-type cables that are 60245 IEC 57 (IEC) compliant; whereas indoors, use H05VV-F-

type cables that are 60227 IEC 53 (IEC) compliant. For power supplies up to 48 V, you can use FROR 20-22 II-type cables that comply with EN 
50267-2-1 (CEI).

 

To connect the antenna, use the RG58 (we suggest up to 5 m).

 For paired connection and CRP, use a UTP CAT5-type cable (up to 1,000 m long).

 

If cable lengths differ from those specified in the table, establish the cable sections depending on the actual power draw of the connected 

devices and according to the provisions of regulation CEI EN 60204-1.

 

For multiple, sequential loads along the same line, the dimensions on the table need to be recalculated according to the actual power draw 

and distances. For connecting products that are not contemplated in this manual, see the literature accompanying said products

INSTALLING

The following illustrations are mere examples in that the space for fastening the operator and accessories varies depending on the installation area. 

It is up to the fi tter, therefore, to choose the most suitable solution.

 

The drawing show an operator fitted on the left. 

Summary of Contents for BX708AGS

Page 1: ...Sliding gate operator BX series BX704AGS 708AGS BX708RGS INSTALLATION MANUAL EN English FA00945 EN...

Page 2: ...2 3 1 2 3 1...

Page 3: ...well fastened to the ground entirely above the surface and free of any impediments to the gate s movement The rails of the upper guide must not cause any friction Make sure that opening and closing li...

Page 4: ...use this device in any way except as specified in this manual INTENDED USE Model BX704AGS BX708AGS BX708RGS Standard reference length of the sliding part m 4 Maximum weight of the sliding part kg 400...

Page 5: ...Cycles hour no 17 Consecutive cycles no 6 The cycles calculation refers to a gate that has a standard reference length see the intended use that are professionally installed free of any mechanical iss...

Page 6: ...ng light 7 Photocells 8 Posts 9 Mechanical gate stop 10 Sensitive safety edge 11 Junction pit DESCRIPTION OF PARTS 1 Cover 2 Front cover 3 Gear motor 4 Condenser 5 Mechanical limit switch 6 Anchoring...

Page 7: ...PES AND MINIMUM THICKNESSES Connection cable length 20 m 20 30 m Input voltage for 230 V AC control board 1P N PE 3G x 1 5 mm 2 3G x 2 5 mm 2 Flashing light 2 x 0 5 mm 2 Command and control devices 2...

Page 8: ...surface Wait at least 24 hrs for the concrete to solidify Fit the bolts into the anchoring plate and tighten them using the nuts Remove the pre shaped clamps using a screw driver or pliers Place the p...

Page 9: ...AME S p A Translated original instructions Remove the foundation frame and fill the hole with earth around the concrete block Remove the nuts from the bolts Fit the electric cables into the tubes so t...

Page 10: ...must pass under the gearmotor casing and must not touch any parts that may overheat during use such as the motor or the transformer and so on Lift the gearmotor by 5 to 10 mm from the plate by adjusti...

Page 11: ...zontal adjustment This prevents the gate s weight from bearing down on the operator FASTENING THE RACK If the rack is already set up the next step should be to adjust the rack and pinion coupling dist...

Page 12: ...he plate using the supplied hardware Spring For closing close the gate t the closing limit switch tab into the rack until the micro switch is activated spring and fasten it using the grub screws ESTAB...

Page 13: ...es DESCRIPTION OF PARTS 1 Power supply terminals 2 Gear motor terminals 3 Transformer terminals 4 Control board fuse 5 Terminals for control and safety devices 6 Fuse accessories 7 Terminals for the R...

Page 14: ...e law Before connecting all the wires set up the cables by using cable glands on the control board brace as shown in the figure The electrical cables must not touch any heated parts such as the motor...

Page 15: ...es power supply output 24 V AC max 20 W To change the motor torque plug the faston terminal as shown into one of the four positions from 1 min to 4 max 120 230 V AC 50 60 Hz POWER SUPPLY Flashing ligh...

Page 16: ...e g the AF R800 you MUST CUT OFF THE MAIN POWER SUPPLY and remove any batteries PARTIAL OPENING function from control device NO contact OPEN CLOSE INVERT step step function from control device NO con...

Page 17: ...g opening the contact triggers the inversion of movement until the gate is completely closed C3 partial stop Stopping of the gate if it is moving with consequent automatic closing if the automatic clo...

Page 18: ...d WARNING For the system to work properly before fitting the control board you MUST CUT OFF THE POWER MAINS and remove any emergency batteries Serial RS485 connection via CRP Came Remote Protocol or f...

Page 19: ...closing by sensitive safety edges with clean contact C8 reclosing during opening by sensitive safety edges with clean contact r7 reopening during closing for sensitive safety edges 8K2 resistive inpu...

Page 20: ...hing light default 1 Cycle F19 Automatic Closing Time The automatic closing wait starts when the opening limit switch point is reached and can be set to between 1 and 180 seconds The automatic closing...

Page 21: ...available P0 stop gate and exclude any automatic closing to resume movement use the control device P7 reopening during closing P8 reclosing during opening For programming see the instructions that com...

Page 22: ...f swing see the CALIBRATING SWING paragraph This function only appears if function F11 is activated If the operator is not calibrated it excludes all commands OFF default ON A 4 Resetting parameters C...

Page 23: ...an opening maneuver until it reaches a final stop MANAGING USERS When adding and deleting users the flashing numbers appearing are those numbers that are available and usable to assign to a new user m...

Page 24: ...9 130 131 132 133 134 135 136 137 138 139 140 141 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53...

Page 25: ...2 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 20...

Page 26: ...ror messages appear on the display Memory roll Memory roll SAVING AND UPLOADING ALL DATA USERS AND CONFIGURATION WITH THE MEMORY ROLL Procedure for memorizing all of the system s user and configuratio...

Page 27: ...el calibration The programming keys on the SLAVE control panel are disabled Operating modes Either STEP STEP or ONLY OPEN command Both leaves open PARTIAL PEDESTRIAN OPENING command Only the MASTER op...

Page 28: ...lla Libert 15 31030 Dosson di Casier Treviso Italy tel 39 0422 4940 fax 39 0422 4941 Manual FA00945 EN 01 2018 CAME S p A Translated original instructions The contents of this manual may change at any...

Reviews: